Liebert NX UPS System user manual Safety, Hazardous battery voltage present behind covers

Models: NX UPS System

1 88
Download 88 pages 58.88 Kb
Page 26
Image 26

Battery Installation

2.2Safety

Special care should be taken when working with the batteries associated with the Liebert NX UPS system. When all the cells are connected together, the battery terminal voltage is potentially hazard- ous. The battery installation must be segregated from all but appropriately qualified maintenance personnel by locating the cells in a key-lockable cabinet or in a purpose-designed, dedicated battery room. When the batteries require maintenance, these precautions must be taken:

The rotary switch must be turned to Maint. position.

The input circuit breaker (CB1) must be opened.

The ANDERSON connector must be disconnected..

NOTE

The fuse on the battery EMI board (UHA241A2-10kkVA, UHK241A2-15/20kVA,

UHS242A2-30kVA) is 600VDC/30A, High Speed Fuse.

NOTE

Full safety instructions concerning the use and maintenance of UPS batteries are provided in the appropriate battery manufacturers manuals. The battery safety information contained in this section relates to key considerations that must be taken into account during the installation design process and might affect the design outcome depending on localised conditions.

! WARNING

Hazardous battery voltage present behind covers

No user-serviceable parts are located behind covers that require a tool for their removal. Only qualified service personnel are authorised to remove such covers.

When using internal batteries in 10 to 30kVA units, the batteries are always connected through power fuses to the UPS and to the segregated terminal bars available for connection to an external battery.

Isolate any internal battery connections before attempting to access the segregated terminal bars available for connection to an external battery.

The following general battery safety precautions and warnings should be observed at all times:

A battery can present risk of electric shock or burn from high- short-circuit currents.

The full nominal string voltage, when the battery blocks are interconnected, is 480VDC, which is hazardous

Only qualified personnel should install or service batteries.

Eye protection should be worn to prevent injury from electrical arcs.

Remove rings, watches, necklaces, bracelets and all other metal objects.

Use only tools with insulated handles.

Wear rubber gloves and a rubber apron when handling batteries.

If a battery leaks electrolyte or is otherwise damaged, it should be placed in a container resistant to sulfuric acid and disposed of in accordance with local regulations.

If electrolyte comes into contact with the skin the affected area should be washed immedi- ately with plenty of clean water.

Batteries must always be disposed of according to local environmental laws.

When replacing batteries, use the same number and type that were originally fitted.

Disconnect charging source before connecting or disconnecting battery terminals.

Determine whether the battery is inadvertently grounded. If it is inadvertently grounded, remove the source of the ground. Contact with any part of a grounded battery can result in electrical shock.

18

Page 26
Image 26
Liebert NX UPS System user manual Safety, Hazardous battery voltage present behind covers