Operator Control Panel and Display
Table 21 Descriptions of UPS menus and data window items (continued)
| Menu | 
 | 
 | |
| Type | Item Type | Explanation | |
| 
 | 
 | 
 | |
| 
 | Sout (kVA) | Sout: Apparent power | |
| 
 | 
 | 
 | |
| 
 | Pout (kW) | Pout: Active power | |
| System | 
 | 
 | |
| Qout (kVAR) | Qout: Reactive power | ||
| 
 | 
 | 
 | |
| 
 | Single unit, no parallel data | When configured as a single unit, UPS has only native load, no system | |
| 
 | 
 | load. | |
| 
 | Battery voltage (V) | Battery bus voltage | |
| 
 | 
 | 
 | |
| 
 | Battery current (A) | Battery bus current | |
| 
 | 
 | 
 | |
| 
 | Battery temperature (°C) | Internal battery temperature °C | |
| Battery | 
 | 
 | |
| Remain Time Min. | Battery run time remaining | ||
| 
 | 
 | 
 | |
| 
 | Battery boost charging | Battery is boost charging | |
| 
 | 
 | 
 | |
| 
 | Battery float charging | Battery is float charging | |
| 
 | 
 | 
 | |
| 
 | Battery disconnected | Battery is not connected | |
| 
 | 
 | 
 | |
| Records | (history log) | Displays all records in the history log | |
| 
 | 
 | 
 | |
| Language | (choices for text displayed) | User may select any of 12 languages for LCD text. | |
| 
 | 
 | 
 | |
| 
 | Display contrast | Adjust the LCD display contrast | |
| 
 | 
 | 
 | |
| 
 | Date format set | Choose the format for date display: M/D/Y, D/M/Y, M/D/Y, Y/M/D | |
| 
 | 
 | 
 | |
| 
 | Date & time | Set the date and time | |
| 
 | 
 | 
 | |
| 
 | Comm1 baud rate | Communication baud rate setting for Intellislot 1 | |
| 
 | 
 | 
 | |
| 
 | Comm2 baud rate | Communication baud rate setting for Intellislot 2 | |
| 
 | 
 | 
 | |
| 
 | Comm3 baud rate | Communication baud rate setting for Intellislot 3 | |
| 
 | 
 | 
 | |
| 
 | Communication address | This setting is applicable to RS485 communication mode | |
| 
 | 
 | 
 | |
| Settings | Communication mode | Communication Mode Setting | |
| 
 | 
 | ||
| 
 | Callback times | When Intellislot 1 Communication mode is Modem, this parameter sets | |
| 
 | the number of times a number is redialed to send an alarm notification. | ||
| 
 | 
 | ||
| 
 | Phone No.1 | When Intellislot 1 Communication mode is Modem, this is the first phone | |
| 
 | number to be dialed (to send an alarm notification). | ||
| 
 | 
 | ||
| 
 | Phone No.2 | When Intellislot 1 Communication mode is Modem, this is the second | |
| 
 | phone number to be dialed (to send an alarm notification). | ||
| 
 | 
 | ||
| 
 | Phone No.3 | When Intellislot 1 Communication mode is Modem, this is the third phone | |
| 
 | number to be dialed (to send an alarm notification). | ||
| 
 | 
 | ||
| 
 | Command password | User can modify the command password. | |
| 
 | Battery maintenance test | This test performs a partial discharge of the battery to obtain a rough | |
| 
 | estimate of the battery capacity. Load must be between 20% and 100%. | ||
| 
 | 
 | ||
| 
 | Battery capacity test | This test performs a full discharge of the battery to obtain a precise | |
| 
 | measure of the battery capacity. Load must be between 20% and 100%. | ||
| Command | 
 | ||
| 
 | This is a  | ||
| (start/stop | System test | ||
| battery & | 
 | up window appears about 5 seconds later to show the results. | |
| system | Stop testing | Manually stops a battery maintenance test, battery capacity test or system | |
| tests) | test. | ||
| 
 | 
 | 
 | |
| 
 | Freshening Charge | This command will allow a temporary Equalize charge for the batteries. | |
| 
 | This charge is configurable for 1 to 36 hours | ||
| 
 | 
 | ||
| 
 | Stop Freshening Charge | Manually stop a Freshening Charge | |
| 
 | 
 | 
 | |
| 
 | UPS version | Provides UPS firmware version numbers for the inverter, rectifier and | |
| Version | software display board. | ||
| 
 | |||
| 
 | UPS model | Provides UPS model  | |
| 
 | 
 | 
 | 
59