Operator Control Panel and Display

Table 21 Descriptions of UPS menus and data window items (continued)

Menu

 

 

Type

Item Type

Explanation

 

 

 

 

Sout (kVA)

Sout: Apparent power

 

 

 

 

Pout (kW)

Pout: Active power

System

 

 

Qout (kVAR)

Qout: Reactive power

 

 

 

 

Single unit, no parallel data

When configured as a single unit, UPS has only native load, no system

 

 

load.

 

Battery voltage (V)

Battery bus voltage

 

 

 

 

Battery current (A)

Battery bus current

 

 

 

 

Battery temperature (°C)

Internal battery temperature °C

Battery

 

 

Remain Time Min.

Battery run time remaining

 

 

 

 

Battery boost charging

Battery is boost charging

 

 

 

 

Battery float charging

Battery is float charging

 

 

 

 

Battery disconnected

Battery is not connected

 

 

 

Records

(history log)

Displays all records in the history log

 

 

 

Language

(choices for text displayed)

User may select any of 12 languages for LCD text.

 

 

 

 

Display contrast

Adjust the LCD display contrast

 

 

 

 

Date format set

Choose the format for date display: M/D/Y, D/M/Y, M/D/Y, Y/M/D

 

 

 

 

Date & time

Set the date and time

 

 

 

 

Comm1 baud rate

Communication baud rate setting for Intellislot 1

 

 

 

 

Comm2 baud rate

Communication baud rate setting for Intellislot 2

 

 

 

 

Comm3 baud rate

Communication baud rate setting for Intellislot 3

 

 

 

 

Communication address

This setting is applicable to RS485 communication mode

 

 

 

Settings

Communication mode

Communication Mode Setting

 

 

 

Callback times

When Intellislot 1 Communication mode is Modem, this parameter sets

 

the number of times a number is redialed to send an alarm notification.

 

 

 

Phone No.1

When Intellislot 1 Communication mode is Modem, this is the first phone

 

number to be dialed (to send an alarm notification).

 

 

 

Phone No.2

When Intellislot 1 Communication mode is Modem, this is the second

 

phone number to be dialed (to send an alarm notification).

 

 

 

Phone No.3

When Intellislot 1 Communication mode is Modem, this is the third phone

 

number to be dialed (to send an alarm notification).

 

 

 

Command password

User can modify the command password.

 

Battery maintenance test

This test performs a partial discharge of the battery to obtain a rough

 

estimate of the battery capacity. Load must be between 20% and 100%.

 

 

 

Battery capacity test

This test performs a full discharge of the battery to obtain a precise

 

measure of the battery capacity. Load must be between 20% and 100%.

Command

 

 

This is a self-test of the UPS. When the user activates this function, a pop-

(start/stop

System test

battery &

 

up window appears about 5 seconds later to show the results.

system

Stop testing

Manually stops a battery maintenance test, battery capacity test or system

tests)

test.

 

 

 

 

Freshening Charge

This command will allow a temporary Equalize charge for the batteries.

 

This charge is configurable for 1 to 36 hours

 

 

 

Stop Freshening Charge

Manually stop a Freshening Charge

 

 

 

 

UPS version

Provides UPS firmware version numbers for the inverter, rectifier and

Version

software display board.

 

 

UPS model

Provides UPS model information—for example, 400V-50Hz.

 

 

 

59

Page 67
Image 67
Liebert NX UPS System user manual Number to be dialed to send an alarm notification