Technical Specifications
Table 32 Mechanical characteristics
| 
 | Unit of | 
 | 
 | 
 | 
 | |
| Rated Power, kVA | Measurement | 10 | 15 | 20 | 30 | |
| Dimensions, WxDxH | mm (in) | 
 | 600x700x1400 | 
 | ||
| 
 | 
 | |||||
| 
 | 
 | 
 | 
 | |||
| Mass | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | |
| Mass without batteries | kg (lb) | 180 (397) | 204 (450) | 204 (450) | 210 (463) | |
| 
 | 
 | 
 | 
 | 
 | 
 | |
| Finish | N/A | 
 | Pantone 877 (Silver grey) | 
 | ||
| equivalent Becker Silver epoxy polyester powder  | ||||||
| 
 | 
 | |||||
| Protection Degree, IEC (60529) | N/A | IP20  | ||||
| 
 | 
 | 
 | 
 | 
 | 
 | |
Table 33 Rectifier AC input (mains)
| 
 | Unit of | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Rated Power, kVA | Measurement | 10 | 
 | 15 | 20 | 
 | 30 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Rated AC Input Voltage 1 | VAC | 
 | 
 | 380/400/415 | 
 | 
 | ||
| 
 | 
 | 
 | ||||||
| Input Voltage Tolerance 2 | VAC | 
 | 
 | 
 | 305V to 477V | 
 | ||
| 
 | 304V to 208V (output derated below 70%) | |||||||
| 
 | 
 | 
 | ||||||
| Frequency 2 | Hz | 
 | 
 | 50/60Hz (tolerance 40Hz to 70Hz) | 
 | |||
| 
 | kW/kVA, full | 
 | 
 | 
 | 
 | 
 | 
 | |
| Power Factor | load | 
 | 
 | 0.99 (0.98) | 
 | 
 | ||
| 
 | (half load) | 
 | 
 | 
 | 
 | 
 | 
 | |
| Input Power | kVA rated | 43 | 8.9 (11.7) | 
 | 13.3 (18.9) | 17.8 (23.3) | 
 | 26.6 (35.0) | 
| 
 | (maximum | ) | 
 | 
 | 
 | 
 | 
 | 
 | 
| Input Current | A rated 3 | 4 | 12.9 (16.9) | 
 | 19.3 (27.4) | 25.8 (33.8) | 
 | 38.6 (50.7) | 
| 
 | (maximum | ) | 
 | 
 | 
 | 
 | 
 | 
 | 
| Harmonic Current Distortion | THDI % FL | 3 | 
 | 3 | 3 | 
 | 3 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Duration of Progressive | sec | 
 | 
 | 10 seconds to reach full rated current | 
 | |||
| Power  | 
 | (selectable 5 through 30 seconds in  | ||||||
| 
 | 
 | |||||||
1.Rectifier operates at any of the rated supply voltages and frequencies without further adjustment.
2.At 305V input mains the UPS maintains the specified output voltage at rated load without discharging a previously charged battery
3.IEC 
4.IEC 
74