Technical Specifications

Table 32 Mechanical characteristics

 

Unit of

 

 

 

 

Rated Power, kVA

Measurement

10

15

20

30

Dimensions, WxDxH

mm (in)

 

600x700x1400

 

 

(23-9/16x27-5/8x55)

 

 

 

 

 

Mass

 

 

 

 

 

 

 

 

 

 

 

Mass without batteries

kg (lb)

180 (397)

204 (450)

204 (450)

210 (463)

 

 

 

 

 

 

Finish

N/A

 

Pantone 877 (Silver grey)

 

equivalent Becker Silver epoxy polyester powder 041-37-2

 

 

Protection Degree, IEC (60529)

N/A

IP20 (finger-proof with front doors open or closed)

 

 

 

 

 

 

Table 33 Rectifier AC input (mains)

 

Unit of

 

 

 

 

 

 

 

Rated Power, kVA

Measurement

10

 

15

20

 

30

 

 

 

 

 

 

 

 

 

Rated AC Input Voltage 1

VAC

 

 

380/400/415

 

 

 

 

 

(3-phase and sharing neutral with the bypass input)

Input Voltage Tolerance 2

VAC

 

 

 

305V to 477V

 

 

304V to 208V (output derated below 70%)

 

 

 

Frequency 2

Hz

 

 

50/60Hz (tolerance 40Hz to 70Hz)

 

 

kW/kVA, full

 

 

 

 

 

 

Power Factor

load

 

 

0.99 (0.98)

 

 

 

(half load)

 

 

 

 

 

 

Input Power

kVA rated

43

8.9 (11.7)

 

13.3 (18.9)

17.8 (23.3)

 

26.6 (35.0)

 

(maximum

)

 

 

 

 

 

 

Input Current

A rated 3

4

12.9 (16.9)

 

19.3 (27.4)

25.8 (33.8)

 

38.6 (50.7)

 

(maximum

)

 

 

 

 

 

 

Harmonic Current Distortion

THDI % FL

3

 

3

3

 

3

 

 

 

 

 

 

 

 

 

Duration of Progressive

sec

 

 

10 seconds to reach full rated current

 

Power Walk-In

 

(selectable 5 through 30 seconds in 5-second intervals)

 

 

1.Rectifier operates at any of the rated supply voltages and frequencies without further adjustment.

2.At 305V input mains the UPS maintains the specified output voltage at rated load without discharging a previously charged battery

3.IEC 62040-3 / EN 50091-3: at rated load and input voltage 400V, battery charged

4.IEC 62040-3 / EN 50091-3: at rated load and input voltage 400V, battery charging at maximum rated power.

74