APC 20 - 200 KVA user manual Presentation

Page 15

Control panel (cont.)

Presentation

See figure 19.

"Rectifier/charger" light 1

light off: rectifier/charger OFF;

light shines green: rectifier/charger ON;

light shines red: rectifier/charger fault, the stored alarm indicates one or several of the following faults:

input switch Q1 open,

protection fuse at the rectifier/charger input (FUE) blown,

abnormally high internal rectifier/ charger temperature,

abnormally high battery charge current,

abnormally high battery voltage,

fault, non-calibration or non- personalisation of the electronic control board for the rectifier/charger,

fault on the electronic power-supply board.

"Battery light" 2

light off: battery float charging;

light flashing green: battery

recharging;

light shines green: load on battery

power;

"Inverter" light 4

light off: inverter OFF;

light flashing green: inverter starting, inverter ON but not connected to the load;

light shines green: normal inverter operation;

light shines red: inverter fault, the stored alarm indicates one or several of the following faults:

inverter shutdown due to inverter output voltage outside specified tolerances,

protection fuse at the inverter output (FUS) blown,

abnormally high inverter-output transformer temperature,

abnormally high inverter temperature,

output-voltage fault (amplitude or phase) (parallel UPSs),

fault, non-calibration or non- personalisation of the electronic control board for the inverter,

fault on the electronic power-supply board.

"Load" light 5

light off: load not supplied;

light shines green: load supplied via the inverter or the bypass AC source (via the static bypass).

Buzzer 6

The buzzer sounds in the following situations:

load supplied by the bypass AC source;

load on battery;

operating problems.

It sounds slowly and discontinuously for a minor problem or when the inverter is on battery power.

When the alarm "LOW BATTERY SHUTDOWN" is activated, the buzzer sounds more rapidly. Finally, if the inverter shuts down, the beep is loud and continuous. The buzzer may be reset by pressing a button. If the buzzer is reset, a higher level alarm will set it off again.

"Full-shutdown" button 7

Pressing this button shuts down the entire UPS (shutdown of the inverter and rectifier/charger, opening of the battery circuit breaker and activation of a relay contact on the Media Contacts 11 board).

"Inverter ON" button 8

This button is used to start the inverter locally.

light flashing red: low-battery

shutdown warning;

light shines red: battery at end of

backup time and circuit breaker QF1

open, or battery fault.

"Static-bypass" light 3

light off: bypass AC source within specified tolerances and static bypass open;

light shines green: static bypass closed;

light shines red: the stored alarm indicates one or several of the following faults:

bypass AC source voltage or frequency outside specified tolerances,

static-bypass fault,

abnormally high internal static- bypass temperature,

static-bypass ventilation fault,

power-supply fault for the static- bypass control function,

fault on the electronic board controlling the transfer function,

non-calibration or non- personalisation of the electronic control board for the inverter,

fault on the electronic power-supply board,

fault on monitoring the "inverter ready" response channels (parallel UPS system).

"Inverter OFF" button 9

This button turns the inverter off locally.

1

2

3

4

5

 

6

7

1

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

23

 

 

 

 

 

 

9

10

11

 

12

13

14

15

16

 

 

 

 

 

V

A

W.Hz

 

 

 

 

 

 

 

18

 

 

 

 

17

 

 

19

 

 

 

 

 

 

fault

 

 

 

 

 

 

20

21

22

Fig. 19

E-51028230XT/BG - 15

Image 15
Contents MGE Galaxy PW 51028230XT/BG Contents Page Introduction General characteristics of MGE Galaxy PW UPSsSchematic diagram of the MGE Galaxy PW system System descriptionSystem may also include External bypass for parallel UPSs and the hot-swap option Frequency converter with battery backup powerDifferent types of MGE Galaxy PW systems Isolation and protection devicesOperation with the normal Battery timeOperation in on-line ModeBattery charge cycle Operation with the normal AC source restoredForced transfer and return transfer Operation in ECO modeOperation with bypass AC source restored Operation with the bypass AC source outside tolerancesParallel UPSs without redundancy Single-UPS unit on-line or ECO modeInverter shutdown or overload Parallel UPSs with redundancyTransient voltage regulation Example of an installation with an engine generator setOutput voltage quality and continuity Steady state voltage regulation20 30 40 50 60 kVA 160 200 kVA Description of MGE Galaxy PW cubiclesUPS cubicle 80 100 120 kVABattery cubicle Control panelGeneral Presentation Anomaly indicator light Battery keyAlarm reset key Buzzer reset keySingle-converter unit or redundant parallel converter unit Start-upSystem start-up Parallel UPS unit for increased outputStart-up of a module Start-up of a rectifier/ chargerStart-up of an inverter Shutdown of a rectifier/ charger UPS in ECO modeShutdown Shutdown of the inverterDisplay of alarms Control-panel displayGeneral organisation List of primary messages Load Protected ON-LINE ModeLoad on Mains List of secondary messagesBattery Charging BAT. = XXX a U BAT. = XXX Measurement system Voltage measurementsCurrent measurements Battery measurements Selections and settingsSet date and time Battery test Inverse videoPast events Test Interrupted Check Presence of the Battery Check Alarms Maintenance bypass AlarmsSignal reception Signal transmissionEnvironment information Utilisation via the MGE Galaxy PW display General instructions for using most screensSetting the date and time for the UPS Logging and time-stampingExample Consulting statisticsTotal time with Tbatt 25 C h Elapsed backup time min this isNb of backups 1 min this is Min nb of backups 3 min thisUtilisation via Teleservice UPS isolation MaintenanceMaintenance configuration Single-UPS unit or UPS in ECO modeStart-up Redundant, parallel UPSIsolate all UPSs Parallel UPS for increased outputVented lead-acid batteries Battery maintenanceVisual check Functional checkTraining center Harmonics filter and power factor improvement Safety of life and propertyOptions Electrical supervision Empty cubicles