Maintenance (cont.)
Redundant, parallel UPS
See figures 27 and 28 in the Appendix. During maintenance, a UPS unit must be isolated from the normal AC source, its battery and the output circuits of the other UPS units.
◗isolate one UPS (see figure 27) Proceed in the following order (see figure 25 without Q3BP):
◗shut down the inverter (press the "inverter OFF" button 9 for three seconds),
◗open isolating switches Q5N, Q4S, QF1 and Q1.
The UPS unit is powered down once the capacitors have discharged (a few minutes);
◗start-up
Following servicing, proceed in the following order (see figure 26 without Q3BP):
◗close switch Q1, then after approximately ten seconds, switches QF1, Q5N and Q4S,
◗start the inverter (press the "inverter ON" button 8 ).
Note: if the load is still supplied
by an inverter, the Q3BP switch on the unit undergoing maintenance must not be closed.
To fully isolate the installation, proceed as indicated below:
◗isolate all UPSs (see figure 28) Proceed in the following order (see figure 25):
◗shut down the inverters (press the "inverter OFF" buttons 9 for three seconds),
◗close the Q3BP switches used to bypass the units (no units have priority),
◗open isolating switches Q5N, Q4S, QF1 and Q1.
The UPS units are powered down once the capacitors have discharged (a few minutes).
◗
Following servicing, proceed in the following order (see figure 26):
◗close switches Q1, then after approximately ten seconds, switches QF1, Q5N and Q4S,
◗open the Q3BP switches,
◗start the inverters (press the "inverter ON" buttons 8 ).
Q1 | A | B |
| Q5N | |
1 |
|
|
| QF1 |
|
| D |
|
2 | Q4S |
|
|
| |
| Q3BP | C |
Q1 | A | B |
| Q5N | |
1 |
|
|
| QF1 |
|
| D |
|
2 | Q4S |
|
|
| |
| Q3BP | C |
Fig. 27
Q1 | A | B |
| Q5N | |
1 |
|
|
| QF1 |
|
| D |
|
2 | Q4 |
|
|
| |
| Q3BP | C |
Q1 | A | B |
| Q5N | |
1 |
|
|
| QF1 |
|
| D |
|
2 | Q4S |
|
|
| |
| Q3BP | C |
Fig. 28