APC 20 - 200 KVA Start-up of a module, Start-up of a rectifier/ charger, Start-up of an inverter

Page 18

Start-up (cont.)

Start-up of a module

Start-up of a rectifier/ charger

rectifier/charger start-up is automatic when the normal AC input switch Q1 is closed:

the green "rectifier/charger" light 1 on the control panel goes on;

close battery circuit breaker QF1.

Start-up of an inverter

When the rectifier/charger is on:

press the "inverter ON" button 8 on the control panel;

the green "inverter" light 4 flashes.

Single-UPS unit

the inverter starts, then, if the bypass AC source transfer conditions are satisfied, the load is transferred to the inverter if the on-line mode is selected, or the load remains on the static bypass if the "ECO" mode is selected. For on-line mode:

the green "inverter" light 4 remains on,

the "static-bypass" light 3 goes off.

For "ECO" mode:

the green "inverter" light 4 flashes,

the "static-bypass" light 3 remains on.

Parallel UPS unit

the inverter starts and awaits the start of the other inverters;

when they are all on or enough have been started to supply the rated load power, the output switch for each running inverter closes and the load is supplied with power:

the green "static-bypass" light 3 goes off,

the green "inverter" light 4 on the control panels of the running inverters goes on.

Single-converter unit

the inverter starts up, then connects. The load is then supplied by the inverter:

the green lights 4 and 5 go on.

Parallel-converter unit

the inverter starts and awaits the start of the other inverters;

when they are all on or enough have been started to supply the rated load power, the output switch for each running inverter closes and the load is supplied with power:

the green lights 4 and 5 on the

control panels of the running inverters go on.

18 - E-51028230XT/BG

Image 18
Contents MGE Galaxy PW 51028230XT/BG Contents Page General characteristics of MGE Galaxy PW UPSs IntroductionSchematic diagram of the MGE Galaxy PW system System descriptionSystem may also include Isolation and protection devices Frequency converter with battery backup powerDifferent types of MGE Galaxy PW systems External bypass for parallel UPSs and the hot-swap optionMode Battery timeOperation in on-line Operation with the normalOperation with the normal AC source restored Battery charge cycleOperation with the bypass AC source outside tolerances Operation in ECO modeOperation with bypass AC source restored Forced transfer and return transferParallel UPSs with redundancy Single-UPS unit on-line or ECO modeInverter shutdown or overload Parallel UPSs without redundancySteady state voltage regulation Example of an installation with an engine generator setOutput voltage quality and continuity Transient voltage regulation80 100 120 kVA Description of MGE Galaxy PW cubiclesUPS cubicle 20 30 40 50 60 kVA 160 200 kVABattery cubicle Control panelGeneral Presentation Buzzer reset key Battery keyAlarm reset key Anomaly indicator lightParallel UPS unit for increased output Start-upSystem start-up Single-converter unit or redundant parallel converter unitStart-up of a module Start-up of a rectifier/ chargerStart-up of an inverter Shutdown of the inverter UPS in ECO modeShutdown Shutdown of a rectifier/ chargerDisplay of alarms Control-panel displayGeneral organisation Load Protected ON-LINE Mode List of primary messagesList of secondary messages Load on MainsBattery Charging BAT. = XXX a U BAT. = XXX Measurement system Voltage measurementsCurrent measurements Battery measurements Selections and settingsSet date and time Battery test Inverse videoPast events Test Interrupted Check Presence of the Battery Check Alarms Alarms Maintenance bypassSignal reception Signal transmissionEnvironment information Logging and time-stamping General instructions for using most screensSetting the date and time for the UPS Utilisation via the MGE Galaxy PW displayConsulting statistics ExampleMin nb of backups 3 min this Elapsed backup time min this isNb of backups 1 min this is Total time with Tbatt 25 C hUtilisation via Teleservice Single-UPS unit or UPS in ECO mode MaintenanceMaintenance configuration UPS isolationRedundant, parallel UPS Start-upParallel UPS for increased output Isolate all UPSsFunctional check Battery maintenanceVisual check Vented lead-acid batteriesTraining center Harmonics filter and power factor improvement Safety of life and propertyOptions Empty cubicles Electrical supervision