Introduction (cont.)
Inverter shutdown or overload
See figure 13 for devices or installations operating in
3 | 5 |
1 |
|
2 |
|
A | B |
1 |
|
D |
|
| C |
2 |
|
Fig. 13
If the conditions are not satisfied, the inverter will current limit to 165% of its rated current for 1 second before stopping;
◗in the event of a small but extended overload (i.e. a continuous level of power exceeding the full rated load), the inverter will continue to supply power for a period depending on the magnitude of the overload (10 minutes for a 125% overload, 1 minute for a 150% overload). See the overload curve in figure 14;
◗in all three of the above cases, inverter shutdown and supply of the load via the bypass AC source results in the following on the control panel:
◗light 4 goes off,
◗activation of the buzzer (continuous beep),
◗light 3 shines green,
◗the message "LOAD NOT PROTECTED,
Parallel UPSs with redundancy
◗the shutdown of one UPS unit is of no consequence for the load. The others each take up an equal amount of load power and the load continues to be supplied normally;
Unit shutdown results in the following on the control panel:
◗ lights 4 and 5 go off,
◗activation of the buzzer (continuous beep),
◗the message "LOAD NOT PROTECTED, PARALLEL
◗in the event of an overload, the system only loses its redundancy as long as the overload is less than the total rated power of the functioning units. If the overload is greater, the operating mode is that previously described for systems without redundancy.
Single-UPS unit (on-line or "ECO" mode)
◗ in the event of a UPS shutdown |
(initiated by the user or by an internal |
protective device), the load is |
automatically transferred to the bypass |
AC source. If transfer conditions are |
satisfied, transfer takes place instantly, |
without interruption to the load; |
Note: transfer conditions are not |
satisfied when bypass AC source |
characteristics are outside tolerances |
(voltage: ±10%; frequency as per |
personalisation; phase sync with |
inverter ±3°); |
◗ in the event of a major transient |
overload (greater than 1.65 In), |
immediate transfer takes place as |
above, without interruption to the load. |
The return to the inverter is automatic |
when the overload disappears if the |
number of possible returns has not |
been reached (0 to 255, programmable |
by personalisation). If this number has |
Parallel UPSs without redundancy
The shutdown of one inverter results in overload on the other inverters in operation. Two cases may then arise:
◗if the overload on each remaining inverter is > than 1.65 ln, the load is immediately transferred to the bypass AC source;
◗if the overload is less than 1.65 ln, the remaining inverters support the overload (see curve in figure 14), and the load is transferred to the bypass AC source;
◗after this transfer:
◗the light 4 goes off,
◗the buzzer is activated and sounds continuously,
◗the light 3 goes on and turns green,
◗the message "LOAD NOT PROTECTED, PARALLEL
Frequency converters
◗in the event of a shutdown, the load is no longer supplied with power;
◗in the event of a major transient overload (greater than 1.65 In), the inverter will current limit to 165% of their rated current for 1 second before stopping;
◗in the event of a smaller but prolonged overload, the inverter respects the same overload curve as the single inverter and shuts down;
◗in all three of the above cases, inverter shutdown results in the following:
◗ lights 4 and 5 go off,
◗activation of the buzzer (continuous beep),
◗the message "LOAD NOT PROTECTED,
been reached, the load continues to be |
supplied by the bypass AC source. This |
operating mode allows |
devices causing high inrush currents. |
This system requires satisfied transfer |
conditions. |
| I |
|
|
|
|
|
|
|
|
|
|
|
|
1,5 | In |
|
|
|
|
|
|
|
|
|
|
|
|
1,35 | In |
|
|
|
|
|
|
|
|
|
|
|
|
1,25 | In |
|
|
|
|
|
|
|
|
|
|
|
|
1,15 | In |
|
|
|
|
|
|
|
|
|
|
|
|
1,10 | In |
|
|
|
|
|
|
|
|
|
|
|
|
1,05 | In |
|
|
|
|
|
|
|
|
|
|
|
|
| In |
|
|
|
|
|
|
|
|
|
|
|
|
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 30 | 120 | t (min) |
Fig. 14