Introduction
General characteristics of MGE™ Galaxy™ PW UPSs
UPS power rating in kVA |
| 20 |
| 30 |
| 40 | 50 | 60 | 80 | 100 | 120 | 160 | 200 | ||
Normal AC input |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
number of conductors |
| 3 phases |
|
|
|
|
|
|
|
|
|
| |||
rated voltage and tolerances | 380 V or 400 V or 415 V ± 10% (adjustable to ± 15%) |
|
|
|
| ||||||||||
rated frequency and tolerances | 50 Hz or 60 Hz / ± 10% |
|
|
|
|
|
|
| |||||||
THDI with THM filter |
| < 4% |
|
|
|
|
|
|
|
|
|
|
| ||
power factor with THM filter |
| up to 0,96 |
|
|
|
|
|
|
|
| |||||
Bypass AC input |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
number of conductors |
| 3 phases + neutral |
|
|
|
|
|
|
|
| |||||
rated voltage and tolerances | 380 V or 400 V or 415 V / ± 10% |
|
|
|
|
|
| ||||||||
rated frequency and tolerances | 50 Hz or 60 Hz / ± 10% |
|
|
|
|
|
|
| |||||||
Load |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
number of conductors |
| 3 phases + neutral |
|
|
|
|
|
|
|
| |||||
Ph/Ph voltages |
| 380 V or 400 V or 415 V (according to setting) |
|
|
|
|
| ||||||||
Ph/N voltages |
| 220 V or 230 V or 240 V (according to setting) |
|
|
|
|
| ||||||||
voltage fluctuations |
| ± 0,5% |
|
|
|
|
|
|
|
|
|
|
| ||
adjustable frequency and tolerances |
|
|
|
|
|
|
|
|
|
|
|
| |||
(on battery power) |
| 50 Hz or 60 Hz ± 0,05 Hz |
|
|
|
|
|
|
| ||||||
synchronisation with bypass | ± 0,5 Hz (adjustable from ± 0,25 Hz to ± 2 Hz) |
|
|
|
|
| |||||||||
voltage variation for 0 to 100% load step change | ± 2% ((with battery) |
|
|
|
|
|
|
| |||||||
permissible overloads |
| 150% for 1 minute, 125% for 10 minutes |
|
|
|
|
| ||||||||
Isc Ph/Ph (% of I rated) |
| 4.2 |
| 2.8 |
| 2.1 | 2.5 | 2.1 | 3.1 | 2.5 | 2.1 | 2.6 | 2.1 | ||
Isc Ph/N (% of I rated) |
| 6.6 |
| 4.4 |
| 3.3 | 4 | 3.3 | 5 | 4 | 3.3 | 4 | 3.3 | ||
THDU Ph/Ph and Ph/N for linear load | < 1,5% Ph/Ph, < 2% Ph/N |
|
|
|
|
|
|
| |||||||
THDU Ph/Ph and Ph/N for | < 2% Ph/Ph, < 3% Ph/N |
|
|
|
|
|
|
| |||||||
(at 80% of Pn) (1) |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Battery |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
standard battery type |
|
|
|
|
|
| |||||||||
UPS characteristics |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
active power (kW) |
| 16 |
| 24 |
| 32 | 40 | 48 | 64 | 80 | 96 | 128 | 160 | ||
efficiency at 50% load (%) |
| 87.5 |
| 90.5 |
| 91.5 | 92.5 | 93 | 91 | 91.5 | 92 | 93 | 93.2 | ||
(values ± 1%) |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
efficiency at 100% load (%) |
| 91.5 |
| 92 |
| 91.5 | 93 | 92 | 92.5 | 92 | 91.5 | 92.8 | 92.5 | ||
(values ± 1%) |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
heat losses | (2) |
| in KW | 1.5 |
| 2.1 |
| 3.4 | 3.6 | 4.7 | 6.2 | 8.1 | 10.1 | 12.2 | 14.8 |
|
|
| in cal./s | 360 |
| 504 |
| 816 | 864 | 984 | 1488 | 1950 | 2420 | 2930 | 3550 |
storage temperature range |
|
|
|
|
|
|
|
|
| ||||||
operating temperature range | 0 °C to 35 °C (40 °C for 8 hours) |
|
|
|
|
|
| ||||||||
relative humidity |
| 95% maximum |
|
|
|
|
|
|
|
| |||||
maximum operating altitude without derating | < 1000 meters |
|
|
|
|
|
|
|
| ||||||
noise level (dBA) |
| 58 |
| 58 |
| 58 | 60 | 60 | 62 | 64 | 65 | 67 | 68 | ||
dimensions (mm) | width | 715 |
|
|
|
|
|
| 1015 |
|
| 1215 |
| ||
|
|
| depth | 825 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| height | 1400 or 1900 ± 10 |
|
|
| 1900 ± 10 |
|
|
| ||||
weight (kg) (3) |
| 450 |
| 450 |
| 450 | 490 | 490 | 800 | 800 | 800 | 1200 | 1200 | ||
recommended upstream | 1 A |
|
|
|
|
|
|
|
|
|
| ||||
standards | design |
| IEC 146 |
|
|
|
|
|
|
|
|
|
| ||
|
| product |
| ENV 50091 |
|
|
|
|
|
|
|
| |||
|
| safety |
| IEC 950, ENV 50091 |
|
|
|
|
|
|
| ||||
|
| protection |
| IEC 521 (cubicles 1400 mm high = IP 21, cubicles 1900 mm high = IP 20) |
|
| |||||||||
|
| electromagnetic compatibility | IEC 62040, ENV 50091 |
|
|
|
|
|
|
|
(1): As per standards ENV
(2): The losses indicated are those produced at full rated load with the battery float charging. They must be taken into account when sizing the ventilation system.