Start-up
System start-up
See figure 20.
Proceed in the following order:
◗close the upstream switches supplying normal and bypass AC source power (on the LV switchboard);
◗close normal AC input switch Q1. The system powers up:
◗the rectifier/charger automatically starts,
◗green light 1 on the control panel goes on,
◗light 2 turns red;
◗close bypass AC input switch Q4S:
◗green lights 3 and 5 on the control panel go on;
◗close inverter output switch Q5N;
◗close battery circuit breaker QF1;
◗light 2 goes off;
◗open maintenance bypass switch Q3BP;
◗press the "inverter on" button 8 on the control panel:
◗the green "inverter" light 4 flashes,
◗the inverter starts, then, if the bypass AC source transfer conditions are satisfied, the load is transferred to the inverter if the
◗the green
◗the green "inverter" light 4 shines for
|
| Q1 | Q4S | Q3BP | Q5N | |||
1 | 0 | 1 | 0 | 1 | 0 | 1 | 0 | 1 |
|
|
|
| |||||
2 | 0 | 1 | 0 | 1 | 0 | 1 | 0 | 1 |
|
|
|
| |||||
3 | 0 | 1 | 0 | 1 | 0 | 1 | 0 | 1 |
|
|
|
|
QF1 | |
4 |
|
0 | I |
5 | 0 | 1 | 0 | 1 | 0 | 1 | 0 | 1 |
|
|
|
|
6
20 - 200 kVA
Fig. 20
Parallel UPS unit for increased output
See figure 21.
Proceed in the following order:
◗check that all load devices are off or that the load is disconnected;
◗close the upstream switch supplying normal AC source power (on the LV switchboard);
◗close the normal AC input switches Q1 on the UPS units. The system powers up:
◗the rectifier/chargers automatically start,
◗the green "rectifier/charger" lights 1 in the control panels go on,
◗lights 2 turn red;
◗close the battery circuit breakers QF1;
◗lights 2 go off;
◗close Mains 2 input switch Q4S in the external bypass unit:
◗green lights 3 and 5 on the control panels go on;
◗close output switches Q5N for the inverters and in the external bypass unit;
◗open maintenance bypass switch Q3BP in the external bypass unit;
◗press the "inverter on" button 8 on each control panel:
◗the green "inverter" lights 4 flash;
◗when a sufficient number of inverters are ready, the
◗the green "inverter" lights 4 shine permanently green;
◗the
|
| Q1 | Q5N | |
1 | 0 | 1 | 0 | 1 |
|
|
QF1
2 |
| I |
|
Q1 | 0 | Q5N |
3 | 0 | 1 | 0 | 1 |
|
|
4
20 - 200 kVA
Fig. 21
Single-converter unit or redundant parallel converter unit
See figure 21.
Proceed in the following order:
◗close the upstream switch supplying normal AC source power (on the LV switchboard);
◗close normal AC input switch Q1. The system powers up:
◗the rectifier/charger automatically starts,
◗green light 1 on the control panel goes on;
◗close battery circuit breaker QF1;
◗close inverter output switch Q5N;
◗press the "inverter on" button 8 on the control panel:
◗the green "inverter" light 4 flashes,
◗the inverter starts up, then connects. The load is then supplied by the inverter,
◗the green light 4 shines permanently, and light 5 turns green.
Note:
Each time a device is switched on, a lamp test is run: all the lights turn orange for roughly 1 second. The message "autotest OK" is displayed until the first primary message is sent.