APC 20 - 200 KVA user manual List of primary messages, Load Protected ON-LINE Mode

Page 21

Control-panel display (cont.)

List of primary messages

LOAD PROTECTED

ON-LINE MODE

This is the normal display when there are no alarms or problems and the load is correctly supplied by the inverter, in on-line mode.

LOAD PROTECTED

PARALLEL ON-LINE MODE

This is the normal display when there are no alarms or problems and the load is correctly supplied by the inverter in a parallel UPS system, in on-line mode.

LOAD NOT PROTECTED

ON-LINE MODE

This display indicates that the load is not supplied by the inverter, or that there is no battery backup. The arrow indicates the presence of one or more problems specified in secondary messages.

The buzzer sounds continuously.

LOAD NOT PROTECTED

PARALLEL ON-LINE MODE

Situation identical to that in the previous screen, but for parallel UPS systems.

LOAD PROTECTED BATTERY DISCHARGING Remaining battery time (min) = XX % kW used = XXX

The load is supplied by the inverter, but the normal AC source is down or outside tolerances and power is supplied by the battery.

This message indicates the remaining battery time in minutes prior to inverter shutdown and the percent load. The battery time calculation takes into account:

the percentage of full rated load power currently being drawn;

the type of battery;

battery temperature;

battery age.

The buzzer sounds slowly and discontinuously.

LOAD PROTECTED, LOW-BATTERY SHUTDOWN WARNING,

Remaining battery time (min) = XX % kW used = XXX

This message replaces the preceding if the power outage persists and the warning level has been reached.

The user is warned that the battery is about to shut down.

The buzzer sounds rapidly and discontinuously.

LOAD PROTECTED

ECO MODE

This is the normal display when there are no problems: the load is supplied by the inverter or the bypass AC source, and battery backup is available.

LOAD NOT PROTECTED

ECO MODE

This display indicates that the load is supplied but has no battery backup. The arrow indicates the presence of one or more problems specified in secondary messages.

The buzzer sounds continuously.

LOAD FORCED TO INVERTER ECO MODE

The load has been transferred to the inverter following a specific request by the user.

E-51028230XT/BG - 21

Image 21
Contents MGE Galaxy PW 51028230XT/BG Contents Page Introduction General characteristics of MGE Galaxy PW UPSsSchematic diagram of the MGE Galaxy PW system System descriptionSystem may also include Different types of MGE Galaxy PW systems Frequency converter with battery backup powerIsolation and protection devices External bypass for parallel UPSs and the hot-swap optionOperation in on-line Battery timeMode Operation with the normalBattery charge cycle Operation with the normal AC source restoredOperation with bypass AC source restored Operation in ECO modeOperation with the bypass AC source outside tolerances Forced transfer and return transferInverter shutdown or overload Single-UPS unit on-line or ECO modeParallel UPSs with redundancy Parallel UPSs without redundancyOutput voltage quality and continuity Example of an installation with an engine generator setSteady state voltage regulation Transient voltage regulationUPS cubicle Description of MGE Galaxy PW cubicles80 100 120 kVA 20 30 40 50 60 kVA 160 200 kVABattery cubicle Control panelGeneral Presentation Alarm reset key Battery keyBuzzer reset key Anomaly indicator lightSystem start-up Start-upParallel UPS unit for increased output Single-converter unit or redundant parallel converter unit Start-up of a module Start-up of a rectifier/ charger Start-up of an inverter Shutdown UPS in ECO modeShutdown of the inverter Shutdown of a rectifier/ chargerDisplay of alarms Control-panel displayGeneral organisation List of primary messages Load Protected ON-LINE ModeLoad on Mains List of secondary messagesBattery Charging BAT. = XXX a U BAT. = XXX Measurement system Voltage measurementsCurrent measurements Battery measurements Selections and settingsSet date and time Battery test Inverse videoPast events Test Interrupted Check Presence of the Battery Check Alarms Maintenance bypass AlarmsSignal reception Signal transmissionEnvironment information Setting the date and time for the UPS General instructions for using most screensLogging and time-stamping Utilisation via the MGE Galaxy PW displayExample Consulting statisticsNb of backups 1 min this is Elapsed backup time min this isMin nb of backups 3 min this Total time with Tbatt 25 C hUtilisation via Teleservice Maintenance configuration MaintenanceSingle-UPS unit or UPS in ECO mode UPS isolationStart-up Redundant, parallel UPSIsolate all UPSs Parallel UPS for increased outputVisual check Battery maintenanceFunctional check Vented lead-acid batteriesTraining center Harmonics filter and power factor improvement Safety of life and propertyOptions Electrical supervision Empty cubicles