Maintenance (cont.)
Battery maintenance
Consult the instructions supplied by the battery manufacturer. Below are a few general indications:
◗sealed
◗vented lead-acid batteries:
◗check the electrolyte level regularly and add water if necessary,
◗check the voltage of each cell to determine if it is necessary to equalise the battery,
◗check the terminals of each cell and clean if necessary.
Caution:
Battery maintenance is undertaken with the system powered up. Operations must be carried out in accordance with applicable safety regulations by qualified personnel using insulated tools, gloves and safety goggles. Batteries contain dangerous substances that will harm the environment if thrown away. If you change the batteries yourself, call on qualified organisations for battery recovery and recycling.
PbPb
Visual check
◗Power down the system prior to any maintenance operations.
Note: in redundant, parallel UPS systems and frequency converters, the check may be carried out successively on each UPS unit without interrupting the load. In other configurations, the load must be supplied via the maintenance bypass (see "maintenance bypass" in the "Alarm" section);
◗clean the system regularly, particularly the air inlet and outlet grills. Check that the air circulates freely in the cubicles. Use a vacuum cleaner if necessary;
◗check that nothing hinders the ventilation at the top and at the back of the system;
◗check that all the fans operate correctly.
Functional check
◗Check that lights 1 , 2 and 3 on the control panel are not red, to avoid an interruption in the supply of power to the load due to incorrect transfer conditions or a battery problem;
◗press the "inverter OFF" button and check that the buzzer and control panel lights function correctly (see the section on operating modes in the introduction);
◗press the "inverter ON" button and check again that the control panel lights function correctly;
◗run a transfer to battery test. With the inverter on, open input switch Q1. The orange "battery" light on the control panel should light. After two minutes on battery power, close input switch Q1. The rectifier/charger should automatically restart and the orange "battery" light on the control panel should go off;
◗in parallel systems, run these tests on each UPS unit.