APC 20 - 200 KVA user manual Control-panel display, General organisation, Display of alarms

Page 20

Control-panel display

General organisation

Display of messages

Display of alarms

The display is structured around primary and secondary messages, measuring tables and setting screens. As a rule, the message displayed on the screen is always a primary one. The secondary messages, if any, are accessed by pressing keys 10 and

11 (see figure 19).

The presence of secondary messages is indicated by the arrow at the end of the primary message. Return to the primary messages is automatic if the keypad is not used for 2 minutes, or direct by pressing key 18 (see figure 19). The display screen lights up when a key is pressed, and goes off if no key is pressed for 5 minutes.

Note:

Most functions may be directly accessed. For example, when voltage measurements are currently displayed, it is possible to directly access current measurements by pressing the "A" button.

In addition to keypad operations, the graphical display brings up a window giving the overall device status. The message displayed is then said to be primary (see list in the paragraph below). A primary message can be used to access the measuring tables using keys 14 , 15 , 16 and 19 on the keypad (see figure 21 in the general appendix). The configuration screens can be accessed by pressing key 13 . A flashing arrow appears at the end of a primary message if there is a problem or an alarm; secondary messages can be accessed by pressing key 10 on the keypad (see the list of secondary messages). The presence of another message is indicated by the arrows and at the end of the secondary message. They can be accessed by pressing keys 10 and 11 on the keypad.

The return to the primary message is automatic after a 2 minute time delay or by pressing key 18 on the keypad.

primary message

 

(ALARM

MESSAGE N°

1)

(ALARM

MESSAGE N°

2)

(LAST ALARM MESSAGE)

main screen

 

Fig. 22

1

2

3

4

5

 

6

7

1

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

23

 

 

 

 

 

 

9

10

11

 

12

13

14

15

16

 

 

 

 

 

V

A

W.Hz

 

 

 

 

 

 

 

18

 

 

 

 

17

 

 

19

 

 

 

 

 

 

fault

 

 

 

 

 

 

20

21

22

Fig. 19

20 - E-51028230XT/BG

Image 20
Contents MGE Galaxy PW 51028230XT/BG Contents Page General characteristics of MGE Galaxy PW UPSs IntroductionSystem may also include Schematic diagram of the MGE Galaxy PW systemSystem description Frequency converter with battery backup power Different types of MGE Galaxy PW systemsIsolation and protection devices External bypass for parallel UPSs and the hot-swap optionBattery time Operation in on-lineMode Operation with the normalOperation with the normal AC source restored Battery charge cycleOperation in ECO mode Operation with bypass AC source restoredOperation with the bypass AC source outside tolerances Forced transfer and return transferSingle-UPS unit on-line or ECO mode Inverter shutdown or overloadParallel UPSs with redundancy Parallel UPSs without redundancyExample of an installation with an engine generator set Output voltage quality and continuitySteady state voltage regulation Transient voltage regulationDescription of MGE Galaxy PW cubicles UPS cubicle80 100 120 kVA 20 30 40 50 60 kVA 160 200 kVAGeneral Battery cubicleControl panel Presentation Battery key Alarm reset keyBuzzer reset key Anomaly indicator lightStart-up System start-upParallel UPS unit for increased output Single-converter unit or redundant parallel converter unitStart-up of an inverter Start-up of a moduleStart-up of a rectifier/ charger UPS in ECO mode ShutdownShutdown of the inverter Shutdown of a rectifier/ chargerGeneral organisation Display of alarmsControl-panel display Load Protected ON-LINE Mode List of primary messagesList of secondary messages Load on MainsBattery Charging BAT. = XXX a U BAT. = XXX Current measurements Measurement systemVoltage measurements Set date and time Battery measurementsSelections and settings Past events Battery testInverse video Test Interrupted Check Presence of the Battery Check Alarms Alarms Maintenance bypassEnvironment information Signal receptionSignal transmission General instructions for using most screens Setting the date and time for the UPSLogging and time-stamping Utilisation via the MGE Galaxy PW displayConsulting statistics ExampleElapsed backup time min this is Nb of backups 1 min this isMin nb of backups 3 min this Total time with Tbatt 25 C hUtilisation via Teleservice Maintenance Maintenance configurationSingle-UPS unit or UPS in ECO mode UPS isolationRedundant, parallel UPS Start-upParallel UPS for increased output Isolate all UPSsBattery maintenance Visual checkFunctional check Vented lead-acid batteriesTraining center Options Harmonics filter and power factor improvementSafety of life and property Empty cubicles Electrical supervision