External Connection
UPS | External | External | External PE | Maximum | External |
| Input | Input Cable | Cable | External | Output |
| Fuses* FM | [mm2] | [mm2] | Output | Cable |
| [A] |
| Fuses* | [mm2] | |
|
|
| [A] |
| |
|
|
|
|
|
|
60kW | 125 | 50 | 16 | 100 | 35 |
|
|
|
|
|
|
80kW | 160 | 70 | 35 | 125 | 50 |
|
|
|
|
|
|
NOTICE!
Check correct phase rotation of mains input voltage!!
Max. input/output cables: 120mm2.
If there is no neutral input Dzn0 or Dyn11 input isolation transformer is required.
* DIN gL types
UPS | External Alarm | External System | External | External Battery |
| Cable max. | Earth Cable | Battery Breaker | Cable |
| [mm2] | [mm2]** | [A] | [mm2] |
|
|
|
|
|
60kW | 2 | 25 | 125 | 50 |
|
|
|
|
|
80kW | 2 | 25 | 125 | 50 |
|
|
|
|
|
NOTICE!
All cable dimensions are recommended sizes only.
Refer to local legal regulations.
PVC cables insulated to withstand ambient temperature of max. 30oC
** Must be rated as external PE cable if mains system is not supplying PE
NOTICE!
Install gland plate in bottom of unit.
| |
|
|
Installation Guide APC Silcon | 11 |