External Connection
| UPS | External | External | External PE | Maximum | External | 
| 
 | Input | Input Cable | Cable | External | Output | 
| 
 | Fuses* FM | [mm2] | [mm2] | Output | Cable | 
| 
 | [A] | 
 | Fuses* | [mm2] | |
| 
 | 
 | 
 | [A] | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
| 60kW | 125 | 50 | 16 | 100 | 35 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
| 80kW | 160 | 70 | 35 | 125 | 50 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
NOTICE!
Check correct phase rotation of mains input voltage!!
Max. input/output cables: 120mm2.
If there is no neutral input Dzn0 or Dyn11 input isolation transformer is required.
* DIN gL types
| UPS | External Alarm | External System | External | External Battery | 
| 
 | Cable max. | Earth Cable | Battery Breaker | Cable | 
| 
 | [mm2] | [mm2]** | [A] | [mm2] | 
| 
 | 
 | 
 | 
 | 
 | 
| 60kW | 2 | 25 | 125 | 50 | 
| 
 | 
 | 
 | 
 | 
 | 
| 80kW | 2 | 25 | 125 | 50 | 
| 
 | 
 | 
 | 
 | 
 | 
NOTICE!
All cable dimensions are recommended sizes only.
Refer to local legal regulations.
PVC cables insulated to withstand ambient temperature of max. 30oC
** Must be rated as external PE cable if mains system is not supplying PE
NOTICE!
Install gland plate in bottom of unit.
| 
 | |
| 
 | 
 | 
| Installation Guide APC Silcon  | 11 |