APC 60-80kW manual Appendix

Page 79

Appendix

Notes:

1.Nominal input current based on rated load.

2.Maximum input current based on rated load + full battery recharge. Full battery recharge assumed to increase input current with 10%.

3.Nominal power consumption (column 1c) based on nominal input current (1e) and the corresponding input voltage (1a).

4.Maximum power consumption (1d) based on maximum input current (1f) and the corresponding input voltage (1a).

5.Suggested input overcurrent protection (1h) based on continous full load maximum input current (1f). MCCB breaker selection based on continous full load nominal input current (1e) is acceptable, provided battery recharge time is short.

6.Fuses according to DIN LV HRC type gL, 500V assumed. MCCB load capacity must be 8xIn (nominal current) for minimum 10ms.

7.Suggested load side overcurrent protection (3b) based on nominal output current (3a).

8.Nominal battery voltage assumed to be 2V/cell (Lead technologi).

9.Recommended cable sizes, see "External Connection" section of this guide. CAUTION! Cable sizes must comply with national and/or local legal regulations.

10.Nominal battery discharge current (2c) based on full rated load and nominal battery voltage (2V/cell).

11.Maximum battery discharge current (2d) based on full rated load and battery voltage at end of discharge (1.7V/cell).

12.Full load discharge power from battery based on nominal battery discharge current

(2c) x nominal battery voltage (2x192cells x 2V/cell), or maximum battery discharge current (2d) x battery voltage at end of discharge (2x192cells x 1.7 V/cell).

13.Heat dissipation based on nominal full load capacity and linear load.

990-4051

Installation Guide APC Silcon 60-80kW 400V UPS

79

Image 79
Contents 60-80kW 400V UPS Installation Guide Safety Symbols used in this manual Installation Guide APC Silcon 60-80kW 400V UPSThank You Contents Appendix System SpecificationsWarranty 10.0 How to Contact APCTools IntroductionIntroduction Tools and EquipmentUnpacking UnpackingPlease Recycle Installation InstallationRequirements on Site 1 800mm Cabinet for 60-80kW UPS FootprintExternal Connection Connecting the UPSExternal Connection 125 Output CableFuses 100 80kWSystem Integration Interface Connections Parallel Board Parallel BoardTerminal Blocks X003/X004 Anxiliary Contacts X005 Output RelaysExternal Connection External Control Cables Power CablesCommunication Interface Board Connecting of APC Silcon Tripel Chassis 2.1Monitoring Port Safety WarningsAPC Silcon Triple Chassis Product DescriptionIf the LED is… Then the Silcon Triple Chassis… 2.4Optional Power InputInstalling Management Peripherals 2.3LEDs3.3Daisy-chaining the APC Silcon Triple Chassis 3.2Installing Management Peripheral Cards3.1Order of Management Peripheral Cards Management Priority Position Peripheral CardManagement Peripheral Draw mA Problem Possible Cause Solution Troubleshooting5.1If Problems Persist External Connection External Connection Physical 6.2Power, Physical, and Environmental SpecificationsEnvironmental Important Safety Instructions APC Silcon Battery CabinetsAPC Silcon Battery Cabinets Diagram UPS with Battery Cabinet 1.1Installation of BatteriesSilcon Battery Breaker Box/Fuse-box 80 kW Battery Breaker BoxAmpere Connection Max Dimensions Weight Rating Cable Short Circuit Current kA 60 kWBattery Battery Breaker Box Connection Diagram540x540x183 80 kW Fuse-box504x540x183 Fuse-box Connection Diagram External Connection Parameters Parameter Setting CommentsProgramming Parameters Programming ParametersProgramming Keys Programming Example Switch to Bypass Operation System ConfigurationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Change parameters by pressing Programming Parameters for Advanced Parallel Operation Description of SettingsProgramming example Battery MonitorOptions/Accessories Options/AccessoriesService Bypass Panel for Single Operation 10 x 0.75mm2 max mm2 Options/Accessories Display shows Operating The External Service Bypass SwitchLamp indication On Servive Bypass Panel 3.1Switching from External Bypass to Normal UPS OperationService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories H002a Action Options/Accessories Action Lamp indication On Service Bypass PanelDisplay shows Following can be carried out on any UPS Isolating One UPS for Service/MaintenanceSwitching Back to Normal Parallel/Redundant Operation Intersystem Synchronization Unit System ISU System Intersystem Synchronization UnitIntersystem Synchronization Unit ISU Relays Relay BoardRelay Board/Relay Functions Relay Number Message Alarm-trigging EventsSee .2 in this guide for System configuration Footprint 600mm Weight EqualizerFootprint 1000mm Cabinet Extension of Remote Display Communication Distance Remote DisplayStandard Short-haul RS232 Modem Async Pin Connections for cable from host to ME800A-R2 Host 1.1Connections Without ConverterHost DTE Remote Display DTE 1.2Connections With ConverterRemote Display Cables 2.2Remote Display Power SupplyRemote Display Use 3.2Communication FaultRemote Display Setting 3.6Alarms1400 600 800 625 Height mm Width mm Depth mm Weight kgIsolation Transformer Mm wideInput Fuses Input Cable PE Cable Output Temp FM a Connecting Isolation TransformerCable mm2 Signal Cable Isolation ExternalOptions/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Dimensions / Weight System SpecificationsSystem Specifications Technical DataWarranty WarrantyAPC Silcon Series Limited Factory Warranty Appendix Installation Planning DataAppendix Appendix APC Denmark How to Contact APCHow to Contact APC APC Corporate