APC 60-80kW manual Extension of Remote Display Communication Distance

Page 64

Options/Accessories

6.6Remote Display

With the remote display unit data may be displayed at distances of up to 25 m from UPS. For extended communication distance, see section below.

Remote display may easily be connected to UPS via one of the two serial communication ports on the communication interface board.

To obtain a transmission distance of up to 3.2 km normal RS232C signal levels must be converted to a long distance communication standard. The converter must be placed outside the UPS cabinet.

6.6.1 Extension of Remote Display Communication Distance

Remote display communicates with the UPS through a 3-wire RS232 interface. Remote display is a DTE (Data Terminal Equipment) employing a SUB-D 9-pin female connector. Communication speed: 9600 bps.

For communication distances, see Table 1. Insert converters if longer distances are necessary, or if communication cables are led through magnetically noisy areas. Converters must comply with local regulations

Table 1: Remote Display Communication Extensions

 

Standard

Short-haul

 

(RS232)

Modem Async

 

 

 

Max. distance

80/25 ft/m

10000/3200 ft/m

 

 

 

Converter Manufacture

No converter

BLACK BOX

Art. Code

 

ME800A-R2

 

 

 

RS232 BLACK BOX connector

 

Sub-D 25-pin female

 

 

 

BLACK BOX interconnector

 

4-screw terminal

 

 

 

Two converter boxes are required for a communication distance extension: One

box near the UPS for the conversion from RS232C to a long distance communication standard, and another box at the other end to convert back to RS232C, which is to be connected to the Remote Display. The converter provides optical signal insulation. Both converter boxes must be supplied by an uninterruptible power source.

990-4051

64

Installation Guide APC Silcon 60-80kW 400V UPS

Image 64
Contents 60-80kW 400V UPS Installation Guide Safety Symbols used in this manual Installation Guide APC Silcon 60-80kW 400V UPSThank You Contents System Specifications Warranty10.0 How to Contact APC AppendixIntroduction IntroductionTools and Equipment ToolsUnpacking UnpackingPlease Recycle Installation InstallationRequirements on Site Footprint 1 800mm Cabinet for 60-80kW UPSExternal Connection Connecting the UPSExternal Connection Output Cable Fuses100 80kW 125System Integration Interface Connections Parallel Board Terminal Blocks X003/X004 Anxiliary ContactsX005 Output Relays Parallel BoardExternal Connection Power Cables External Control CablesCommunication Interface Board Connecting of APC Silcon Tripel Chassis Safety Warnings APC Silcon Triple ChassisProduct Description 2.1Monitoring Port2.4Optional Power Input Installing Management Peripherals2.3LEDs If the LED is… Then the Silcon Triple Chassis…3.2Installing Management Peripheral Cards 3.1Order of Management Peripheral CardsManagement Priority Position Peripheral Card 3.3Daisy-chaining the APC Silcon Triple ChassisManagement Peripheral Draw mA Problem Possible Cause Solution Troubleshooting5.1If Problems Persist External Connection External Connection Physical 6.2Power, Physical, and Environmental SpecificationsEnvironmental APC Silcon Battery Cabinets Important Safety InstructionsAPC Silcon Battery Cabinets Diagram UPS with Battery Cabinet 1.1Installation of BatteriesSilcon Battery Breaker Box/Fuse-box Battery Breaker Box Ampere Connection Max Dimensions Weight Rating Cable ShortCircuit Current kA 60 kW 80 kWBattery Breaker Box Connection Diagram Battery540x540x183 80 kW Fuse-box504x540x183 Fuse-box Connection Diagram External Connection Parameter Setting Comments Programming ParametersProgramming Parameters ParametersProgramming Keys System Configuration Programming Example Switch to Bypass OperationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Change parameters by pressing Description of Settings Programming Parameters for Advanced Parallel OperationBattery Monitor Programming exampleOptions/Accessories Options/AccessoriesService Bypass Panel for Single Operation 10 x 0.75mm2 max mm2 Options/Accessories Operating The External Service Bypass Switch Display shows3.1Switching from External Bypass to Normal UPS Operation Lamp indication On Servive Bypass PanelService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories H002a Action Options/Accessories Action Lamp indication On Service Bypass PanelDisplay shows Isolating One UPS for Service/Maintenance Following can be carried out on any UPSSwitching Back to Normal Parallel/Redundant Operation Intersystem Synchronization Unit System ISU System Intersystem Synchronization UnitIntersystem Synchronization Unit ISU Relay Board RelaysRelay Number Message Alarm-trigging Events Relay Board/Relay FunctionsSee .2 in this guide for System configuration Weight Equalizer Footprint 600mmFootprint 1000mm Cabinet Extension of Remote Display Communication Distance Remote DisplayStandard Short-haul RS232 Modem Async 1.1Connections Without Converter Host DTE Remote Display DTE1.2Connections With Converter Pin Connections for cable from host to ME800A-R2 Host2.2Remote Display Power Supply Remote Display Cables3.2Communication Fault Remote Display Setting3.6Alarms Remote Display UseHeight mm Width mm Depth mm Weight kg Isolation TransformerMm wide 1400 600 800 625Connecting Isolation Transformer Cable mm2 Signal CableIsolation External Input Fuses Input Cable PE Cable Output Temp FM aOptions/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories System Specifications System SpecificationsTechnical Data Dimensions / WeightWarranty WarrantyAPC Silcon Series Limited Factory Warranty Appendix Installation Planning DataAppendix Appendix How to Contact APC How to Contact APCAPC Corporate APC Denmark