APC 60-80kW manual Operating The External Service Bypass Switch, Display shows

Page 47

Options/Accessories

6.1.3 Operating The External Service Bypass Switch

Action

 

 

 

 

1.

Press

 

on the keyboard

Display shows

 

2.

Press

 

or

on the keyboard until

Bypass operation

 

:NO

 

 

 

 

 

3.

Press

 

on the keyboard

Bypass operation

 

 

 

 

 

:YES

 

 

 

 

 

4.

Press

 

on the keyboard

Lamp indication

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

on Service Bypass Panel

5.

Check lamp indication on the Service Bypass Panel

The Green lamp (H003)

 

 

 

 

 

above the bypass switch

 

 

 

 

 

handle (Q003) lights

6.Turn the external bypass switch (Q003) to position ”1“

7.Turn the output switch (Q002) to position ”0“

8.Open the front door and press both the green ”ON“ and the red ”OFF“ keys simultaneously

The Green lamp (H002) above the output switch handle (Q002) lights

Only the lamp (H002) above the output switch handle (Q002) lights now

Display shows

** System OFF **

The acoustic alarm sounds for 30 sec.*

9.Turn the input switch to position ”0“

The red alarm LED below the display lights and the acoustic alarm sounds for 30 sec.

* The acoustic alarm can be reset by the

key

990-4051

Installation Guide APC Silcon 60-80kW 400V UPS

47

Image 47
Contents 60-80kW 400V UPS Installation Guide Thank You Installation Guide APC Silcon 60-80kW 400V UPSSafety Symbols used in this manual Contents Appendix System SpecificationsWarranty 10.0 How to Contact APCTools IntroductionIntroduction Tools and EquipmentUnpacking UnpackingPlease Recycle Requirements on Site InstallationInstallation 1 800mm Cabinet for 60-80kW UPS FootprintExternal Connection Connecting the UPSExternal Connection 125 Output CableFuses 100 80kWSystem Integration Interface Connections Parallel Board Parallel BoardTerminal Blocks X003/X004 Anxiliary Contacts X005 Output RelaysExternal Connection External Control Cables Power CablesCommunication Interface Board Connecting of APC Silcon Tripel Chassis 2.1Monitoring Port Safety WarningsAPC Silcon Triple Chassis Product DescriptionIf the LED is… Then the Silcon Triple Chassis… 2.4Optional Power InputInstalling Management Peripherals 2.3LEDs3.3Daisy-chaining the APC Silcon Triple Chassis 3.2Installing Management Peripheral Cards3.1Order of Management Peripheral Cards Management Priority Position Peripheral CardManagement Peripheral Draw mA 5.1If Problems Persist TroubleshootingProblem Possible Cause Solution External Connection External Connection Environmental 6.2Power, Physical, and Environmental SpecificationsPhysical Important Safety Instructions APC Silcon Battery CabinetsAPC Silcon Battery Cabinets Silcon 1.1Installation of BatteriesDiagram UPS with Battery Cabinet Battery Breaker Box/Fuse-box 80 kW Battery Breaker BoxAmpere Connection Max Dimensions Weight Rating Cable Short Circuit Current kA 60 kWBattery Battery Breaker Box Connection Diagram504x540x183 Fuse-box540x540x183 80 kW Fuse-box Connection Diagram External Connection Parameters Parameter Setting CommentsProgramming Parameters Programming ParametersProgramming Keys Programming Example Switch to Bypass Operation System ConfigurationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Change parameters by pressing Programming Parameters for Advanced Parallel Operation Description of SettingsProgramming example Battery MonitorService Bypass Panel for Single Operation Options/AccessoriesOptions/Accessories 10 x 0.75mm2 max mm2 Options/Accessories Display shows Operating The External Service Bypass SwitchLamp indication On Servive Bypass Panel 3.1Switching from External Bypass to Normal UPS OperationService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories H002a Action Options/Accessories Display shows Lamp indication On Service Bypass PanelAction Following can be carried out on any UPS Isolating One UPS for Service/MaintenanceSwitching Back to Normal Parallel/Redundant Operation Intersystem Synchronization Unit ISU Intersystem Synchronization UnitIntersystem Synchronization Unit System ISU System Relays Relay BoardRelay Board/Relay Functions Relay Number Message Alarm-trigging EventsSee .2 in this guide for System configuration Footprint 600mm Weight EqualizerFootprint 1000mm Cabinet Standard Short-haul RS232 Modem Async Remote DisplayExtension of Remote Display Communication Distance Pin Connections for cable from host to ME800A-R2 Host 1.1Connections Without ConverterHost DTE Remote Display DTE 1.2Connections With ConverterRemote Display Cables 2.2Remote Display Power SupplyRemote Display Use 3.2Communication FaultRemote Display Setting 3.6Alarms1400 600 800 625 Height mm Width mm Depth mm Weight kgIsolation Transformer Mm wideInput Fuses Input Cable PE Cable Output Temp FM a Connecting Isolation TransformerCable mm2 Signal Cable Isolation ExternalOptions/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Dimensions / Weight System SpecificationsSystem Specifications Technical DataAPC Silcon Series Limited Factory Warranty WarrantyWarranty Appendix Installation Planning DataAppendix Appendix APC Denmark How to Contact APCHow to Contact APC APC Corporate