Page 53

Options/Accessories

Action

Step 1-4 can be carried out with any of the parallel systems, however this will switch all systems into bypass operation.

1.Press on the keyboard

2.Press or on the keyboard until

3.Press on the keyboard

4.Press on the keyboard

All systems will transfer to bypass operation

Do not switch off any of the UPS systems until step 5-8 has been completed.

Display shows

Bypass operation :NO

Bypass operation

:YES

Bypass operation

Lamp indication on bypass panel

5. Check lamp indication on the Service Bypass Panel

The green lamp (H003)

 

above the bypass switch

 

handle (Q003) lights

6.Turn the external bypass switch (Q003) to position ”1“

7.Turn the output isolator (Q004) to position ”0“

8.Turn the output switches (Q002) to position ”0“

9. Open the front door and press both the green ”ON“ and the red ”OFF“ keys simultaneously in any of the systems

The acoustic alarm sounds for 30 sec.* Repeat for (all) other system(s).

10.Turn all input switches (Q001) to position ”0“ The red alarm LED below the display lights and the acoustic alarm sounds for 30 sec.

The green lamp (H004) above the output isolator (Q004 and the green lamps (H002) above the output switch handles (Q002) lights

The green lamps (H002) above the output switch (Q002) light and the green lamp (H004) above the output switch (Q004) lights

Now the lamps (H002) above the output switch handles (Q002) light and the green lamp (H004) above the output switch (Q004) lights

Display shows

** System OFF **

* The acoustic alarm can be reset by the key

990-4051

Installation Guide APC Silcon 60-80kW 400V UPS

53

Image 53
Contents 60-80kW 400V UPS Installation Guide Thank You Installation Guide APC Silcon 60-80kW 400V UPSSafety Symbols used in this manual Contents Warranty System Specifications10.0 How to Contact APC AppendixIntroduction IntroductionTools and Equipment ToolsUnpacking UnpackingPlease Recycle Requirements on Site InstallationInstallation 1 800mm Cabinet for 60-80kW UPS FootprintExternal Connection Connecting the UPSExternal Connection Fuses Output Cable100 80kW 125System Integration Interface Connections Terminal Blocks X003/X004 Anxiliary Contacts Parallel BoardX005 Output Relays Parallel BoardExternal Connection External Control Cables Power CablesCommunication Interface Board Connecting of APC Silcon Tripel Chassis APC Silcon Triple Chassis Safety WarningsProduct Description 2.1Monitoring PortInstalling Management Peripherals 2.4Optional Power Input2.3LEDs If the LED is… Then the Silcon Triple Chassis…3.1Order of Management Peripheral Cards 3.2Installing Management Peripheral CardsManagement Priority Position Peripheral Card 3.3Daisy-chaining the APC Silcon Triple ChassisManagement Peripheral Draw mA 5.1If Problems Persist TroubleshootingProblem Possible Cause Solution External Connection External Connection Environmental 6.2Power, Physical, and Environmental SpecificationsPhysical Important Safety Instructions APC Silcon Battery CabinetsAPC Silcon Battery Cabinets Silcon 1.1Installation of BatteriesDiagram UPS with Battery Cabinet Battery Breaker Box/Fuse-box Ampere Connection Max Dimensions Weight Rating Cable Short Battery Breaker BoxCircuit Current kA 60 kW 80 kWBattery Battery Breaker Box Connection Diagram504x540x183 Fuse-box540x540x183 80 kW Fuse-box Connection Diagram External Connection Programming Parameters Parameter Setting CommentsProgramming Parameters ParametersProgramming Keys Programming Example Switch to Bypass Operation System ConfigurationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Change parameters by pressing Programming Parameters for Advanced Parallel Operation Description of SettingsProgramming example Battery MonitorService Bypass Panel for Single Operation Options/AccessoriesOptions/Accessories 10 x 0.75mm2 max mm2 Options/Accessories Display shows Operating The External Service Bypass SwitchLamp indication On Servive Bypass Panel 3.1Switching from External Bypass to Normal UPS OperationService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories H002a Action Options/Accessories Display shows Lamp indication On Service Bypass PanelAction Following can be carried out on any UPS Isolating One UPS for Service/MaintenanceSwitching Back to Normal Parallel/Redundant Operation Intersystem Synchronization Unit ISU Intersystem Synchronization UnitIntersystem Synchronization Unit System ISU System Relays Relay BoardRelay Board/Relay Functions Relay Number Message Alarm-trigging EventsSee .2 in this guide for System configuration Footprint 600mm Weight EqualizerFootprint 1000mm Cabinet Standard Short-haul RS232 Modem Async Remote DisplayExtension of Remote Display Communication Distance Host DTE Remote Display DTE 1.1Connections Without Converter1.2Connections With Converter Pin Connections for cable from host to ME800A-R2 HostRemote Display Cables 2.2Remote Display Power SupplyRemote Display Setting 3.2Communication Fault3.6Alarms Remote Display UseIsolation Transformer Height mm Width mm Depth mm Weight kgMm wide 1400 600 800 625Cable mm2 Signal Cable Connecting Isolation TransformerIsolation External Input Fuses Input Cable PE Cable Output Temp FM aOptions/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories System Specifications System SpecificationsTechnical Data Dimensions / WeightAPC Silcon Series Limited Factory Warranty WarrantyWarranty Appendix Installation Planning DataAppendix Appendix How to Contact APC How to Contact APCAPC Corporate APC Denmark