APC 60-80kW manual 3.1Switching from External Bypass to Normal UPS Operation

Page 48

Options/Accessories

6.1.3.1Switching from External Bypass to Normal UPS Operation

Action

1.Turn the input switch (Q002) to position ”0“

2.Open the UPS front door and press the green "ON” key

3.Press on the keyboard

4.Press or on the keyboard until

5.Press on the keyboard

6.Press on the keyboard

7.Check lamp indication on the bypass panel

8.Turn the output switch (Q002) to position ”1“

9.Turn the bypass switch (Q003) to position ”0“

10.Press on the keyboard

11.Press or on the keyboard until

12.Press on the keyboard

11.Press on the keyboard

11.Press on the keyboard

Display shows

** System OFF **

Normal operation

load power %

Bypass operation :NO

Bypass operation :YES

Lamp indication

on Servive Bypass Panel

The Green lamp (H002) above the output switch handle (Q002) lights

Now also the green lamp (H003) above the bypass switch handle (Q003) lights

Only the Green lamp (H003) above the bypass switch handle (Q003) lights

Display shows

Bypass operation :YES

Bypass operation :NO

Normal operation load power xx %

No lamps on the Service Bypass Panel light any longer

990-4051

48

Installation Guide APC Silcon 60-80kW 400V UPS

Image 48
Contents 60-80kW 400V UPS Installation Guide Installation Guide APC Silcon 60-80kW 400V UPS Safety Symbols used in this manualThank You Contents System Specifications Warranty10.0 How to Contact APC AppendixIntroduction IntroductionTools and Equipment ToolsUnpacking UnpackingPlease Recycle Installation InstallationRequirements on Site Footprint 1 800mm Cabinet for 60-80kW UPSConnecting the UPS External ConnectionExternal Connection Output Cable Fuses100 80kW 125System Integration Interface Connections Parallel Board Terminal Blocks X003/X004 Anxiliary ContactsX005 Output Relays Parallel BoardExternal Connection Power Cables External Control CablesCommunication Interface Board Connecting of APC Silcon Tripel Chassis Safety Warnings APC Silcon Triple ChassisProduct Description 2.1Monitoring Port2.4Optional Power Input Installing Management Peripherals2.3LEDs If the LED is… Then the Silcon Triple Chassis…3.2Installing Management Peripheral Cards 3.1Order of Management Peripheral CardsManagement Priority Position Peripheral Card 3.3Daisy-chaining the APC Silcon Triple ChassisManagement Peripheral Draw mA Troubleshooting Problem Possible Cause Solution5.1If Problems Persist External Connection External Connection 6.2Power, Physical, and Environmental Specifications PhysicalEnvironmental APC Silcon Battery Cabinets Important Safety InstructionsAPC Silcon Battery Cabinets 1.1Installation of Batteries Diagram UPS with Battery CabinetSilcon Battery Breaker Box/Fuse-box Battery Breaker Box Ampere Connection Max Dimensions Weight Rating Cable ShortCircuit Current kA 60 kW 80 kWBattery Breaker Box Connection Diagram BatteryFuse-box 540x540x183 80 kW504x540x183 Fuse-box Connection Diagram External Connection Parameter Setting Comments Programming ParametersProgramming Parameters ParametersProgramming Keys System Configuration Programming Example Switch to Bypass OperationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Change parameters by pressing Description of Settings Programming Parameters for Advanced Parallel OperationBattery Monitor Programming exampleOptions/Accessories Options/AccessoriesService Bypass Panel for Single Operation 10 x 0.75mm2 max mm2 Options/Accessories Operating The External Service Bypass Switch Display shows3.1Switching from External Bypass to Normal UPS Operation Lamp indication On Servive Bypass PanelService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories H002a Action Options/Accessories Lamp indication On Service Bypass Panel ActionDisplay shows Isolating One UPS for Service/Maintenance Following can be carried out on any UPSSwitching Back to Normal Parallel/Redundant Operation Intersystem Synchronization Unit Intersystem Synchronization Unit System ISU SystemIntersystem Synchronization Unit ISU Relay Board RelaysRelay Number Message Alarm-trigging Events Relay Board/Relay FunctionsSee .2 in this guide for System configuration Weight Equalizer Footprint 600mmFootprint 1000mm Cabinet Remote Display Extension of Remote Display Communication DistanceStandard Short-haul RS232 Modem Async 1.1Connections Without Converter Host DTE Remote Display DTE1.2Connections With Converter Pin Connections for cable from host to ME800A-R2 Host2.2Remote Display Power Supply Remote Display Cables3.2Communication Fault Remote Display Setting3.6Alarms Remote Display UseHeight mm Width mm Depth mm Weight kg Isolation TransformerMm wide 1400 600 800 625Connecting Isolation Transformer Cable mm2 Signal CableIsolation External Input Fuses Input Cable PE Cable Output Temp FM aOptions/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories System Specifications System SpecificationsTechnical Data Dimensions / WeightWarranty WarrantyAPC Silcon Series Limited Factory Warranty Installation Planning Data AppendixAppendix Appendix How to Contact APC How to Contact APCAPC Corporate APC Denmark