Programming Parameters
System Configuration Parameters (password protected)
Parameter | Setting* | Comments |
|
|
|
Isolation Transformer Input | YES, NO | YES if optional input isolation transformer is available |
|
|
|
IsolationTransformer | YES, NO | YES if optional output isolation transformer is available |
Output |
|
|
|
|
|
Delta Soft Start Time | 1, 10, 20, 40 sec. | Input current switching in ramp function. Use higher |
|
| values for smaller/unstable diesel generators |
|
|
|
External SSW present | YES, NO | YES for systems with external static bypass switch |
|
|
|
Normal Charge Voltage | Setting of float charge voltage at 20°C | |
| 438V | (Automatic compensation for temperature deviations) |
|
|
|
Boost Charge Voltage | Setting of boost charge voltage at 20°C | |
| 438V | (Automatic compensation for temperature deviations) |
|
|
|
Low Battery warning | Discharged Battery warning | |
| 336V |
|
|
|
|
Low Battery | Switches off system at min. permissible battery | |
| 326V | voltage |
|
|
|
Synchronization | 0.25, 0.5, 1, 2, 4 | Syncronization speed. |
| Hz/sec. |
|
|
|
|
High Battery Temperature | Alarm - Ambient temperature for battery too high | |
| 35°C |
|
|
|
|
Common fault delay | 0, 10, 20, | Delay before common fault alarm relay is activated |
| 30 sec. |
|
|
|
|
Reset operation mode lock | YES, NO | YES resets system locked in bypass or battery |
|
| operation mode caused by system failures (only |
|
| applicable for service personnel) |
|
|
|
Expected | Expected UPS | |
(min.) | 5.0 | at 100% ohmic load. Time used by ABM** |
|
|
|
Battery Capacity in (Ah) | Total Battery capacity in Ah. | |
| 7.0 | Setting used by ABM**. |
|
|
|
Highest Station Address | Highest station address in parallel system | |
|
|
|
Station Address | Station address in parallel system | |
|
|
|
APM Mode Active | Disabled | Use only in parallel systems. |
(Advanced Power | Redundant +1 | Disabled: Advanced power management off. |
Management) | Parallel +1 | Redundant +1: Redundant operation with one unit |
|
| being inactive in parallel system |
|
| Parallel +1: Redundant operation with all units in |
|
| operation. |
|
|
|
APM Test Mode Active | YES, NO | YES, if APM test mode is active |
|
|
|
Battery Connection | Common, | Common: if common battery is used in parallel system. |
| Separate | Separate: if separate battery is used |
|
|
|
*Bold text refers to factory standard setting **Advanced Battery Monitor
Installation Guide APC Silcon | 39 |