APC 60-80kW manual System Configuration Parameters password protected

Page 39

Programming Parameters

System Configuration Parameters (password protected)

Parameter

Setting*

Comments

 

 

 

Isolation Transformer Input

YES, NO

YES if optional input isolation transformer is available

 

 

 

IsolationTransformer

YES, NO

YES if optional output isolation transformer is available

Output

 

 

 

 

 

Delta Soft Start Time

1, 10, 20, 40 sec.

Input current switching in ramp function. Use higher

 

 

values for smaller/unstable diesel generators

 

 

 

External SSW present

YES, NO

YES for systems with external static bypass switch

 

 

 

Normal Charge Voltage

410-460V

Setting of float charge voltage at 20°C

 

438V

(Automatic compensation for temperature deviations)

 

 

 

Boost Charge Voltage

438-460V

Setting of boost charge voltage at 20°C

 

438V

(Automatic compensation for temperature deviations)

 

 

 

Low Battery warning

336-384V

Discharged Battery warning

 

336V

 

 

 

 

Low Battery shut-down

310-336V

Switches off system at min. permissible battery

 

326V

voltage

 

 

 

Synchronization

0.25, 0.5, 1, 2, 4

Syncronization speed.

 

Hz/sec.

 

 

 

 

High Battery Temperature

15-40°C

Alarm - Ambient temperature for battery too high

 

35°C

 

 

 

 

Common fault delay

0, 10, 20,

Delay before common fault alarm relay is activated

 

30 sec.

 

 

 

 

Reset operation mode lock

YES, NO

YES resets system locked in bypass or battery

 

 

operation mode caused by system failures (only

 

 

applicable for service personnel)

 

 

 

Expected back-up time

0.1-999.9

Expected UPS back-up time in minutes when running

(min.)

5.0

at 100% ohmic load. Time used by ABM**

 

 

 

Battery Capacity in (Ah)

0.1-999.9

Total Battery capacity in Ah.

 

7.0

Setting used by ABM**.

 

 

 

Highest Station Address

2-9

Highest station address in parallel system

 

 

 

Station Address

1-9

Station address in parallel system

 

 

 

APM Mode Active

Disabled

Use only in parallel systems.

(Advanced Power

Redundant +1

Disabled: Advanced power management off.

Management)

Parallel +1

Redundant +1: Redundant operation with one unit

 

 

being inactive in parallel system

 

 

Parallel +1: Redundant operation with all units in

 

 

operation.

 

 

 

APM Test Mode Active

YES, NO

YES, if APM test mode is active

 

 

 

Battery Connection

Common,

Common: if common battery is used in parallel system.

 

Separate

Separate: if separate battery is used

 

 

 

*Bold text refers to factory standard setting **Advanced Battery Monitor

990-4051

Installation Guide APC Silcon 60-80kW 400V UPS

39

Image 39
Contents 60-80kW 400V UPS Installation Guide Installation Guide APC Silcon 60-80kW 400V UPS Safety Symbols used in this manualThank You Contents Appendix System SpecificationsWarranty 10.0 How to Contact APCTools IntroductionIntroduction Tools and EquipmentUnpacking UnpackingPlease Recycle Installation InstallationRequirements on Site 1 800mm Cabinet for 60-80kW UPS FootprintConnecting the UPS External ConnectionExternal Connection 125 Output CableFuses 100 80kWSystem Integration Interface Connections Parallel Board Parallel BoardTerminal Blocks X003/X004 Anxiliary Contacts X005 Output RelaysExternal Connection External Control Cables Power CablesCommunication Interface Board Connecting of APC Silcon Tripel Chassis 2.1Monitoring Port Safety WarningsAPC Silcon Triple Chassis Product DescriptionIf the LED is… Then the Silcon Triple Chassis… 2.4Optional Power InputInstalling Management Peripherals 2.3LEDs3.3Daisy-chaining the APC Silcon Triple Chassis 3.2Installing Management Peripheral Cards3.1Order of Management Peripheral Cards Management Priority Position Peripheral CardManagement Peripheral Draw mA Troubleshooting Problem Possible Cause Solution5.1If Problems Persist External Connection External Connection 6.2Power, Physical, and Environmental Specifications PhysicalEnvironmental Important Safety Instructions APC Silcon Battery CabinetsAPC Silcon Battery Cabinets 1.1Installation of Batteries Diagram UPS with Battery CabinetSilcon Battery Breaker Box/Fuse-box 80 kW Battery Breaker BoxAmpere Connection Max Dimensions Weight Rating Cable Short Circuit Current kA 60 kWBattery Battery Breaker Box Connection DiagramFuse-box 540x540x183 80 kW504x540x183 Fuse-box Connection Diagram External Connection Parameters Parameter Setting CommentsProgramming Parameters Programming ParametersProgramming Keys Programming Example Switch to Bypass Operation System ConfigurationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Change parameters by pressing Programming Parameters for Advanced Parallel Operation Description of SettingsProgramming example Battery MonitorOptions/Accessories Options/AccessoriesService Bypass Panel for Single Operation 10 x 0.75mm2 max mm2 Options/Accessories Display shows Operating The External Service Bypass SwitchLamp indication On Servive Bypass Panel 3.1Switching from External Bypass to Normal UPS OperationService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories H002a Action Options/Accessories Lamp indication On Service Bypass Panel ActionDisplay shows Following can be carried out on any UPS Isolating One UPS for Service/MaintenanceSwitching Back to Normal Parallel/Redundant Operation Intersystem Synchronization Unit Intersystem Synchronization Unit System ISU SystemIntersystem Synchronization Unit ISU Relays Relay BoardRelay Board/Relay Functions Relay Number Message Alarm-trigging EventsSee .2 in this guide for System configuration Footprint 600mm Weight EqualizerFootprint 1000mm Cabinet Remote Display Extension of Remote Display Communication DistanceStandard Short-haul RS232 Modem Async Pin Connections for cable from host to ME800A-R2 Host 1.1Connections Without ConverterHost DTE Remote Display DTE 1.2Connections With ConverterRemote Display Cables 2.2Remote Display Power SupplyRemote Display Use 3.2Communication FaultRemote Display Setting 3.6Alarms1400 600 800 625 Height mm Width mm Depth mm Weight kgIsolation Transformer Mm wideInput Fuses Input Cable PE Cable Output Temp FM a Connecting Isolation TransformerCable mm2 Signal Cable Isolation ExternalOptions/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Dimensions / Weight System SpecificationsSystem Specifications Technical DataWarranty WarrantyAPC Silcon Series Limited Factory Warranty Installation Planning Data AppendixAppendix Appendix APC Denmark How to Contact APCHow to Contact APC APC Corporate