APC 60-80kW manual Programming Parameters for Advanced Parallel Operation, Description of Settings

Page 42

Programming Parameters

5.3Programming Parameters for Advanced Parallel Operation

To use the advanced parallel functions, the following parameters must be programmed:

1.“Station number”

2.“Highest station address”

3.“Advanced power management”

4.“APM test mode active”

5.“Battery connection”

5.3.1 Description of Settings

1.“Station number”

Valid station numbers: 1-9 stating the UPS parallel address in system.

2.“Highest station number”

Valid station numbers: 2-9 stating the number of UPSs in system.

3.“Advanced power management”

“Disabled”: Advanced Power Management is inactive.

“PARALLEL+1”: Advanced Power Management is activated when the system operates as PARALLEL N+1, meaning that one system can be isolated without overloading the remaining systems (N systems/UPSs).

“REDUNDANT+1”: Advanced power management is activated when the system operates as REDUNDANT N+1, meaning that one system can be isolated without overloading the remaining systems (N systems/UPSs) with one spare system.

4.“APM test mode active”

“No”: Stand-by-time will be 24 hours - on-line time will be 48 hours (xN systems).

“Yes”: Stand-by-time will be 1 min. - on-line time will be 2 min (xN systems).

5.“Battery connection”

“Separate”: Separate battery for this UPS.

“Common”: Common battery in a parallel system.

NOTICE!

“Common”: Common battery in a parallel system. When this setting is chosen, the highest battery temperature that can be found in the parallelled systems (for charge voltage compensation).

NOTICE!

Common battery pack is a technical possibility.

However, APC recommend separate battery pack due to a higher safety degree in connection with redundant/parallel operation.

The UPS system is designed for both situations.

990-4051

42

Installation Guide APC Silcon 60-80kW 400V UPS

Image 42
Contents 60-80kW 400V UPS Installation Guide Installation Guide APC Silcon 60-80kW 400V UPS Safety Symbols used in this manualThank You Contents 10.0 How to Contact APC System SpecificationsWarranty AppendixTools and Equipment IntroductionIntroduction ToolsUnpacking UnpackingPlease Recycle Installation InstallationRequirements on Site Footprint 1 800mm Cabinet for 60-80kW UPSConnecting the UPS External ConnectionExternal Connection 100 80kW Output CableFuses 125System Integration Interface Connections X005 Output Relays Parallel BoardTerminal Blocks X003/X004 Anxiliary Contacts Parallel BoardExternal Connection Power Cables External Control CablesCommunication Interface Board Connecting of APC Silcon Tripel Chassis Product Description Safety WarningsAPC Silcon Triple Chassis 2.1Monitoring Port2.3LEDs 2.4Optional Power InputInstalling Management Peripherals If the LED is… Then the Silcon Triple Chassis…Management Priority Position Peripheral Card 3.2Installing Management Peripheral Cards3.1Order of Management Peripheral Cards 3.3Daisy-chaining the APC Silcon Triple ChassisManagement Peripheral Draw mA Troubleshooting Problem Possible Cause Solution5.1If Problems Persist External Connection External Connection 6.2Power, Physical, and Environmental Specifications PhysicalEnvironmental APC Silcon Battery Cabinets Important Safety InstructionsAPC Silcon Battery Cabinets 1.1Installation of Batteries Diagram UPS with Battery CabinetSilcon Battery Breaker Box/Fuse-box Circuit Current kA 60 kW Battery Breaker BoxAmpere Connection Max Dimensions Weight Rating Cable Short 80 kWBattery Breaker Box Connection Diagram BatteryFuse-box 540x540x183 80 kW504x540x183 Fuse-box Connection Diagram External Connection Programming Parameters Parameter Setting CommentsProgramming Parameters ParametersProgramming Keys System Configuration Programming Example Switch to Bypass OperationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Change parameters by pressing Description of Settings Programming Parameters for Advanced Parallel OperationBattery Monitor Programming exampleOptions/Accessories Options/AccessoriesService Bypass Panel for Single Operation 10 x 0.75mm2 max mm2 Options/Accessories Operating The External Service Bypass Switch Display shows3.1Switching from External Bypass to Normal UPS Operation Lamp indication On Servive Bypass PanelService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories H002a Action Options/Accessories Lamp indication On Service Bypass Panel ActionDisplay shows Isolating One UPS for Service/Maintenance Following can be carried out on any UPSSwitching Back to Normal Parallel/Redundant Operation Intersystem Synchronization Unit Intersystem Synchronization Unit System ISU SystemIntersystem Synchronization Unit ISU Relay Board RelaysRelay Number Message Alarm-trigging Events Relay Board/Relay FunctionsSee .2 in this guide for System configuration Weight Equalizer Footprint 600mmFootprint 1000mm Cabinet Remote Display Extension of Remote Display Communication DistanceStandard Short-haul RS232 Modem Async 1.2Connections With Converter 1.1Connections Without ConverterHost DTE Remote Display DTE Pin Connections for cable from host to ME800A-R2 Host2.2Remote Display Power Supply Remote Display Cables3.6Alarms 3.2Communication FaultRemote Display Setting Remote Display UseMm wide Height mm Width mm Depth mm Weight kgIsolation Transformer 1400 600 800 625Isolation External Connecting Isolation TransformerCable mm2 Signal Cable Input Fuses Input Cable PE Cable Output Temp FM aOptions/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Technical Data System SpecificationsSystem Specifications Dimensions / WeightWarranty WarrantyAPC Silcon Series Limited Factory Warranty Installation Planning Data AppendixAppendix Appendix APC Corporate How to Contact APCHow to Contact APC APC Denmark