Toshiba S20 instruction manual Connection of optical fiber cables cords

Page 28

TOSLINE-S20 Active Star Coupler (ASC25) Instruction Manual

6F3B0360

9.2Connection of optical fiber cables (cords)

Connection is made between FC Type connectors, or between F07 Type connectors. For the case of CH1 and CH10, the connectors are FC Type, so that a transmission connector (TX) of the Active Star Coupler shall be connected to the FC Type receiving connector (OR) on the target station, and that a receiving connector (RX) of the Active Star Coupler shall be connected to the FC Type transmission connector (OT) on the target station, using respective optical cables.

For the connection between Active Star Couplers, a transmission connector (TX) of an Active Star Coupler shall be connected to a receiving connector (RX) of another Active Star Coupler, further a receiving connector (RX) of an Active Star Coupler shall be connected to a transmission connector (TX) of another Active Star Coupler, using respective optical cables.

(Notes)

At Active Star Coupler side, arbitrary port among CH1 through CH10 may be selected. (TX and RX of CH1 and CH10 are in a pair form.)

To the optical transmission/receiving sections (ports) which are not connected with cables shall be applied with black caps to avoid incoming ambient natural lights. Unnecessary lights may induce error-functioning.

F07 Type station

Active Star Coupler

FC Type station

Figure 9.4 Method for connecting an Active Star Coupler with stations

Active Star Coupler

Active Star Coupler

Figure 9.5 Method for connecting Active Star Couplers

TOSLINE S20

27

Image 28
Contents TOSLINE-S20 3 B 0 3 6Table of Contents Precautions on ordering cables/cords Introduction Page Overview Page System Configurations Page Outline of Functions Page Specifications Page Hardware External dimensionsProduct construction Component identification Function setting switch TX1Page Power LED displayOptical connector Terminal block Fuse holder Power down method Start up and Power down methodsStart up method Page Precautions on using Active Star Coupler Page Installation and Wiring Method for mounting the main unitRecommended mounting position Method for connecting an Active Star Coupler with stations Connection of optical fiber cables cordsOptical parts DCV-HC-20/07 Optical connector CF-2001H Cord length Precautions on handling optical fiber and optical connector Edge position of F07 Type connectorTosline S20 Method of F07optical connector assembly 10 Removal of housing13 Residual length of core cover Page Plug-holding cap Spring Procedure of design for laying optical fiber cables Transmission side end Precautions on ordering cables/cords Precautions on laying cables