Toshiba TOSNIC-7000S instruction manual 3 H 1 0 0 Normal Display Screen, 200V, 50 %, 50%

Page 22

6 F 3 H 1 0 0 1

7.2.1 Normal Display Screen

The Normal Display screen indicates the operational status of the UPS and provides a total of nine screens: one Operation Guidance Display screen and eight Measurement Value Display screens.

Table 7.2 presents examples of these screens.

Table 7.2 Normal Display Screen

No.

 

LCD Screen

 

 

 

Description

 

 

 

 

 

 

 

 

1

Help screen

 

 

 

Shows the status of the UPS at the top and help

 

 

(Example 1) Operation status

messages or measurements underneath.

 

 

 

 

 

 

(Example 1)Shows help messages when starting

 

 

 

OPERATION GUIDANCE

 

 

 

 

 

MOVE #52R TO “ON” POSITION

 

or stopping operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Example 2)

 

 

 

(Example 2)Shows the output voltage and output

 

 

 

 

 

 

 

 

current during operation.

 

 

 

UPS SUPPLY

 

 

 

 

 

 

 

 

 

 

 

AC-VO

200[V]

 

Voltage (example)

 

 

 

AC- I O

50[%]

 

 

 

 

 

 

 

Current ratio (example)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

Measurement screen

Shows the output voltage between lines.

 

 

(Example)

Output voltage

 

 

 

 

 

 

 

 

 

 

O/P VOLTAGE (LINE)

 

 

 

 

 

U - V

200[V]

 

 

 

 

 

 

V - W

200[V]

 

 

 

 

 

W - U

200[V]

 

 

 

 

 

 

 

 

 

 

 

3

 

Measurement screen

Shows the RMS value for the output current for

 

 

(Example)

Output current (RMS

each phase as a proportion (%) of the rated

 

 

value)

 

 

 

 

 

value.

 

 

 

O/P CURRENT (r.m.s)

 

 

 

 

 

 

U

50[%]

 

 

 

 

 

 

 

V

50[%]

 

 

 

 

 

 

 

W

50[%]

 

 

 

 

 

 

 

 

 

 

 

 

4

 

Measurement screen

Shows the peak value for the output current for

 

 

(Example)

Output current (peak)

each phase as a proportion (%) of the rated

 

 

 

 

 

 

 

 

value.

 

 

 

O/P CURRENT (PEAK)

 

 

Peak value for actual output current100 [%]

 

 

 

 

U

50[%]

 

 

 

 

 

 

V

50[%]

 

 

TMRS value for rated current 1.41

 

 

 

 

W

50[%]

 

 

 

 

 

 

 

 

 

 

 

 

- 21 -

Image 22
Contents 3 H 1 0 0 JulyALL Rights Reserved Procedure and the status of the UPS unit Vent type stand-alone lead storage batterySealed stand-alone lead storage battery Synchronized modeIntroduction Safety PrecautionsExact nature of what must be done is indicated 3 H 1 0 0 Safety Precautions UseCards Do not open the rear door Accordance with customer stipulationsBe always Do not turn off Turn on Running Locations of the Warning Labels Example 300 kVADo not touch rotating section Handling Precautions 3 H 1 0 0 Handling Precautions 3 H 1 0 0 Handling Precautions Contents Appearance Example 300 kVAExample 300 kVA C52R D72B E52R F52M G52L H8A I6CH Controls and Circuit ConfigurationPanel Controls This may result in failureCircuit Configuration Fault UPSKey-switch Function Name Remarks 3 H 1 0 0 Panel Key-switchPanel Keys Key Functions For HS or AHH individual battery systems Name Function RemarksPanels Graphic Display Panel2 Graphic Display Panel Control This LED is unlit when the converter has stopped This LED lights up when the UPS is operatingThis LED lights up when the AC input circuit breaker Operating. It blinks when the converter is starting upLCD Display Scroll up Scroll down200V 3 H 1 0 0 Normal Display ScreenNormal Display Screen LCD Screen Description 50 %BYP I/P-V Normal Display Screen60.0Hz 401V52R Trip 3 H 1 0 0 Failure Display ScreenFailure Display Screen LCD Screen Description 98-09-093 H 1 0 0 LCD Screen Switching Operation Operation General Description/Objective Types of OperationPre-operational check Startup Starts up and operates the stopped UPSProcedures StartupMain circuit AC input Circuit breaker 52R When the message Appears, turn onBypass Press ‘RUN’ Switch Bypass Move #52R to ‘ON’ PositionTo finish On page 14 for at least SecondWait several seconds For the startup process Main circuit DC inputHold down the UPS Key g in the Figure → The will start Power supply Changing processUPS power supply On page14 for at3 H 1 0 0 Switch Power Supply UPS → Bypass 3 H 1 0 0 3 H 1 0 0 Stop StopBreaker72B Restart Press ‘RUN’ Switch Shutdown Move #52R to ‘OFF’Batteries LED unlit → This complete UPS Shutdown 3 H 1 0 0 Complete Shutdown Complete ShutdownTurn off the precharge Circuit switch 6CHUsing the scroll keys Wait about 20 minutes Until the DC capacitorChanging From Floating Charge to Equalized Charge Second → Change to floating Charge is complete Changing From Equalized Charge to Floating ChargeCheck to make sure That the Equal Float Charge LED lit Equal Charge LED unlitChanging from Protective Charge to Floating Charge 3 H 1 0 0 Changing the Power Supply to Maintenance Bypass Changing From UPS to maintenance Bypass Power Supply1 Startup Changing From Maintenance Bypass to UPS Power SupplySame as steps 1-4 52R 72B 52C 52M 52LTypes of Errors TroubleshootingName Description 52R Trip 98-09-09 LCD Failure DisplaysFailure Data Screen Failure Data Screen Descriptions↑ indicates there is a warning screen before this screen Up to 10 screens of warning data can be displayedShows the nature of the warning. For details, see Section ↓ indicates there is a warning screen after this screen3 H 1 0 0 Failure Messages Protective Detector LocationsFault Trip LCD Message Description IndicationBattery temperature has risen Bypass input frequency errorIncluding operation error Battery fluid level has gone below prescribed levelFor Individual battery systems. For HS or AHH batteries Position of Scroll Keys in Failure Data ScreensScrolls to the previous screen see Figure Scroll KeysScrolls to the next screen see Figure Procedure Saving WaveformsOnly open the front panel when performing necessary Restoring UPS OperationFailure Data screens 98-09-09 By scrolling with scroll 11 Restoring UPS Operation ExampleAlso check for other Panel