6 F 3 H 1 0 0 1
8.1 Types of Operation
This section summarizes the types of operations covered in this manual and their objectives. Refer to the attached operating procedures document for specific details on the operating procedures.
No. | Operation | General Description/Objective | Page No. |
|
|
|
|
1 | Startup | Starts up and operates the stopped UPS. | Page 27 |
|
|
|
|
2 | Switch Power Supply | Switches between UPS power supply and | Page.31 |
|
| bypass power supply. |
|
|
|
|
|
3 | Stop | Stops a UPS that is operating. | Page 32 |
|
|
|
|
4 | Complete shutdown | Turns off the control power supply and shuts | Page 34 |
|
| down the UPS completely. |
|
|
|
|
|
5 | Charge | Changes the mode for battery charging (in the | Page 36 |
| (floating/equalized) | case of HS or AHH individual battery). |
|
|
|
|
|
6 | Floating charge | Used to change the charging mode manually | Page 39 |
|
| from protective charge to floating charge (in |
|
|
| the case of an MSE individual battery). |
|
|
|
|
|
7 | Supply power to | Changes the supply of power to the load to | Page 39 |
| maintenance | bypass power supply (when the UPS must be |
|
| bypass | shut down completely for maintenance, |
|
|
| inspection, etc.). |
|
|
|
|
|
8.2 Pre-operational check
Be sure to check the following items before operating the UPS:
(1)Make sure all internal covers are in place.
(2)Make sure all doors are closed. If doors are opened to operate circuit breakers, switches and the like, be sure to close them afterward.
(3)Make sure the air conditioners in the UPS chamber and battery chamber are operating.
(4)When starting up the UPS, make sure all circuit breakers (52R,72B,52C,52L and 52M) and switches (8A and 6CH) are off. (Certain systems are also provided with the switch 8D.)
(5)When starting up the UPS, check on the equipment supplying power to the UPS to make sure AC input voltage is being supplied to the UPS.
- 26 -