Toshiba TOSNIC-7000S LCD Failure Displays, Failure Data Screen, 52R Trip 98-09-09

Page 44

6 F 3 H 1 0 0 1

9.2 LCD Failure Displays

When a failure occurs, a screen such as that shown in Figure 9.1, and when a warning occurs, a screen such as that shown in Figure 9.2, will be displayed on the LCD.

FAULT STOP

SERVICEMAN CALL

FAULT

1 52R TRIP

98-09-09 08:05:30

ANOTHER ITEM

Select the desired failure data with the scroll buttons. Detailed failure data can be displayed.

Figure 9.1 Failure Display

UPS SUPPLY

 

ALARM

AC-VO

200[V]

 

 

AC- I O

50[%]

 

 

 

WARNING

1 72B MIS OPE

98-09-09 08:05:30

ANOTHER ITEM

When a warning (a limitation on operation or a guidance failure) occurs, "ALARM" will be displayed in the upper right of the LCD.

Select the desired warning data with the scroll buttons. Detailed warning data can be displayed.

Figure 9.2 Warning Display

9.2.1 Failure Data Screen

This screen appears when a trip error is detected. Up to 10 screens of failure data can be displayed.

Figure 9.3 and Table 9.1 show a sample screen and describe the data shown in the screen.

 

 

 

FAULT

 

 

c

 

1 52R TRIP

d

 

 

 

98-09-09 08:05:30

e

 

 

 

ANOTHER ITEM

f

 

 

 

 

 

 

 

Figure 9.3 Sample Failure Data Screen

 

 

Table 9.1 Failure Data Screen Descriptions

 

 

 

 

 

No.

Name

Description

 

 

 

 

 

 

c

No.

The number of the message in the order that it was detected (1 - 10).

 

 

(Up to 10 screens of failure data can be displayed.)

 

 

 

 

 

d

Failure

Shows the nature of the failure. For details, see Section 9.2.3

 

Message

"Failure Messages".

 

 

 

 

 

 

e

Time

The date and time (in 24-hour time) that the failure was detected.

 

 

 

 

 

f

Scroll indicator

Indicates whether there is a failure screen before or after this screen.

 

 

indicates there is a failure screen before this screen.

 

 

indicates there is a failure screen after this screen.

 

 

↑↓ indicates there are failure screens both before and after this

 

 

screen.

 

- 43 -

Image 44
Contents ALL Rights Reserved July3 H 1 0 0 Vent type stand-alone lead storage battery Sealed stand-alone lead storage batteryProcedure and the status of the UPS unit Synchronized modeExact nature of what must be done is indicated Safety PrecautionsIntroduction 3 H 1 0 0 Safety Precautions UseCards Do not open the rear door Accordance with customer stipulationsDo not touch rotating section Locations of the Warning Labels Example 300 kVABe always Do not turn off Turn on Running Handling Precautions 3 H 1 0 0 Handling Precautions 3 H 1 0 0 Handling Precautions Contents Appearance Example 300 kVAControls and Circuit Configuration Panel ControlsExample 300 kVA C52R D72B E52R F52M G52L H8A I6CH This may result in failureCircuit Configuration Fault UPSPanel Keys 3 H 1 0 0 Panel Key-switchKey-switch Function Name Remarks Key Functions For HS or AHH individual battery systems Name Function RemarksPanels Graphic Display Panel2 Graphic Display Panel Control This LED lights up when the UPS is operating This LED lights up when the AC input circuit breakerThis LED is unlit when the converter has stopped Operating. It blinks when the converter is starting upLCD Display Scroll up Scroll down3 H 1 0 0 Normal Display Screen Normal Display Screen LCD Screen Description200V 50 %Normal Display Screen 60.0HzBYP I/P-V 401V3 H 1 0 0 Failure Display Screen Failure Display Screen LCD Screen Description52R Trip 98-09-093 H 1 0 0 LCD Screen Switching Operation Types of Operation Pre-operational checkOperation General Description/Objective Startup Starts up and operates the stopped UPSProcedures StartupWhen the message Appears, turn on Bypass Press ‘RUN’ SwitchMain circuit AC input Circuit breaker 52R Bypass Move #52R to ‘ON’ PositionOn page 14 for at least Second Wait several seconds For the startup processTo finish Main circuit DC input→ The will start Power supply Changing process UPS power supplyHold down the UPS Key g in the Figure On page14 for at3 H 1 0 0 Switch Power Supply UPS → Bypass 3 H 1 0 0 3 H 1 0 0 Stop StopBatteries LED unlit → This complete UPS Shutdown Restart Press ‘RUN’ Switch Shutdown Move #52R to ‘OFF’Breaker72B 3 H 1 0 0 Complete Shutdown Complete ShutdownCircuit switch 6CH Using the scroll keysTurn off the precharge Wait about 20 minutes Until the DC capacitorChanging From Floating Charge to Equalized Charge Changing From Equalized Charge to Floating Charge Check to make sure That the EqualSecond → Change to floating Charge is complete Float Charge LED lit Equal Charge LED unlitChanging from Protective Charge to Floating Charge 3 H 1 0 0 Changing the Power Supply to Maintenance Bypass Changing From UPS to maintenance Bypass Power SupplyChanging From Maintenance Bypass to UPS Power Supply Same as steps 1-41 Startup 52R 72B 52C 52M 52LName Description TroubleshootingTypes of Errors LCD Failure Displays Failure Data Screen52R Trip 98-09-09 Failure Data Screen DescriptionsUp to 10 screens of warning data can be displayed Shows the nature of the warning. For details, see Section↑ indicates there is a warning screen before this screen ↓ indicates there is a warning screen after this screen3 H 1 0 0 Failure Messages Protective Detector LocationsFault Trip LCD Message Description IndicationBypass input frequency error Including operation errorBattery temperature has risen Battery fluid level has gone below prescribed levelFor Individual battery systems. For HS or AHH batteries Position of Scroll Keys in Failure Data ScreensScrolls to the next screen see Figure Scroll KeysScrolls to the previous screen see Figure Procedure Saving WaveformsOnly open the front panel when performing necessary Restoring UPS Operation11 Restoring UPS Operation Example Also check for otherFailure Data screens 98-09-09 By scrolling with scroll Panel