6 F 3 H 1 0 0 1
(2)Table 8.5 shows the procedure used to change manually from equalized charge to floating charge.
After the charging mode has been changed to equalized charge using the procedure on the previous page, the mode will automatically change back to floating charge after a set period of time has elapsed. Therefore, normally there is no need to change the mode manually as described below.
Table 8.6 Changing From Equalized Charge to Floating Charge
Step | Procedure | LCD/LED Status (After Execution) |
|
| ||
1 | Check to make sure |
|
|
|
|
|
| that the "EQUAL |
| UPS SUPPLY |
|
|
|
| CHARGE" LED is lit. |
| 200[V] |
|
| |
|
|
|
|
| ||
|
|
| AC- I O | 50[%] |
|
|
|
| ~ | ~ | ~ | UPS |
|
|
|
|
|
| ||
|
| AC INPUT | CONVERTER | INVERTER |
|
|
|
|
| FLOAT CHARGE |
| AC | ~ |
|
|
|
|
|
| |
|
| BATTERIES | EQUAL CHARGE |
| SWITCH |
|
|
|
| DISCHARGE |
|
| AC OUTPUT |
|
| ~ |
|
| BYPASS |
|
|
| BYPASS INPUT |
|
|
| |
|
|
|
|
|
| |
2 | Hold down the "FLOAT |
|
|
|
|
|
| / EQUAL" key (h in |
| UPS SUPPLY |
|
|
|
| Figure 6.3.1 on page |
| 200[V] |
|
| |
| 14) for at least 0.5 |
|
|
| ||
|
| AC- I O | 50[%] |
|
| |
| second. |
|
|
| ||
|
|
|
|
|
| |
| → Change to floating |
|
|
|
|
|
| charge is complete. | ~ | ~ | ~ | UPS |
|
|
|
|
| |||
|
| AC INPUT | CONVERTER | INVERTER |
|
|
|
|
| FLOAT CHARGE |
| AC | ~ |
|
|
|
|
|
| |
|
| BATTERIES | EQUAL CHARGE |
| SWITCH |
|
|
|
|
|
|
| |
|
|
| DISCHARGE |
|
| AC OUTPUT |
|
| ~ |
|
| BYPASS |
|
|
| BYPASS INPUT |
|
|
| |
|
|
|
|
|
|
The "FLOAT CHARGE" LED lit.
The "EQUAL CHARGE" LED unlit.
- 38 -