Toshiba TOSNIC-7000S Restoring UPS Operation Example, Also check for other, Panel, Turn 6CH OFF

Page 53

6 F 3 H 1 0 0 1

Table 9.11 Restoring UPS Operation (Example)

Step

Procedure

LCD/LED Status (After Execution)

 

 

 

1

Check the LCD screen.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAULT

 

 

 

 

Also check for other

 

 

 

 

 

 

 

 

 

1

52R TRIP

 

 

 

 

Failure Data screens

 

 

 

 

 

98-09-09 08:05:30

 

 

 

by scrolling with scroll

 

 

 

 

 

ANOTHER ITEM

 

 

 

keys i and j on the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

panel.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS

 

 

2

Turn 6CH OFF.

AC INPUT

CONVERTER

 

INVERTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLOAT CHARGE

 

 

 

AC

 

 

 

 

 

 

 

 

 

 

 

 

 

BATTERIES

 

EQUAL CHARGE

 

 

 

SWITCH

 

 

 

 

 

 

DISCHARGE

 

 

 

 

 

AC OUTPUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BYPASS

 

 

 

 

BYPASS INPUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3Remove the memory card in the panel and insert a new memory card.*

4

Contact the Toshiba

Follow the directions given by Service Center personnel.

 

Service Center.

 

In the case of other failures as well, restore by doing the following:

(1)Check the nature of the failure on the LCD screen.

(2)Contact the Toshiba Service Center.

(3)Follow the directions given by Service Center personnel.

Note:

*Before removing the memory card, always verify that the memory card write LED shown in figure 9.10 is not lit.

- 52 -

Image 53
Contents ALL Rights Reserved July3 H 1 0 0 Sealed stand-alone lead storage battery Vent type stand-alone lead storage batteryProcedure and the status of the UPS unit Synchronized modeExact nature of what must be done is indicated Safety PrecautionsIntroduction Use 3 H 1 0 0 Safety PrecautionsCards Accordance with customer stipulations Do not open the rear doorDo not touch rotating section Locations of the Warning Labels Example 300 kVABe always Do not turn off Turn on Running Handling Precautions 3 H 1 0 0 Handling Precautions 3 H 1 0 0 Handling Precautions Contents Example 300 kVA AppearancePanel Controls Controls and Circuit ConfigurationExample 300 kVA C52R D72B E52R F52M G52L H8A I6CH This may result in failureCircuit Configuration UPS FaultPanel Keys 3 H 1 0 0 Panel Key-switchKey-switch Function Name Remarks Name Function Remarks Key Functions For HS or AHH individual battery systemsGraphic Display Panel Panels2 Graphic Display Panel Control This LED lights up when the AC input circuit breaker This LED lights up when the UPS is operatingThis LED is unlit when the converter has stopped Operating. It blinks when the converter is starting upScroll up Scroll down LCD DisplayNormal Display Screen LCD Screen Description 3 H 1 0 0 Normal Display Screen200V 50 %60.0Hz Normal Display ScreenBYP I/P-V 401VFailure Display Screen LCD Screen Description 3 H 1 0 0 Failure Display Screen52R Trip 98-09-093 H 1 0 0 LCD Screen Switching Operation Pre-operational check Types of OperationOperation General Description/Objective Startup Starts up and operates the stopped UPSStartup ProceduresBypass Press ‘RUN’ Switch When the message Appears, turn onMain circuit AC input Circuit breaker 52R Bypass Move #52R to ‘ON’ PositionWait several seconds For the startup process On page 14 for at least SecondTo finish Main circuit DC inputUPS power supply → The will start Power supply Changing processHold down the UPS Key g in the Figure On page14 for at3 H 1 0 0 Switch Power Supply UPS → Bypass 3 H 1 0 0 Stop 3 H 1 0 0 StopBatteries LED unlit → This complete UPS Shutdown Restart Press ‘RUN’ Switch Shutdown Move #52R to ‘OFF’Breaker72B Complete Shutdown 3 H 1 0 0 Complete ShutdownUsing the scroll keys Circuit switch 6CHTurn off the precharge Wait about 20 minutes Until the DC capacitorChanging From Floating Charge to Equalized Charge Check to make sure That the Equal Changing From Equalized Charge to Floating ChargeSecond → Change to floating Charge is complete Float Charge LED lit Equal Charge LED unlitChanging from Protective Charge to Floating Charge Changing From UPS to maintenance Bypass Power Supply 3 H 1 0 0 Changing the Power Supply to Maintenance BypassSame as steps 1-4 Changing From Maintenance Bypass to UPS Power Supply1 Startup 52R 72B 52C 52M 52LName Description TroubleshootingTypes of Errors Failure Data Screen LCD Failure Displays52R Trip 98-09-09 Failure Data Screen DescriptionsShows the nature of the warning. For details, see Section Up to 10 screens of warning data can be displayed↑ indicates there is a warning screen before this screen ↓ indicates there is a warning screen after this screenProtective Detector Locations 3 H 1 0 0 Failure MessagesLCD Message Description Indication Fault TripIncluding operation error Bypass input frequency errorBattery temperature has risen Battery fluid level has gone below prescribed levelPosition of Scroll Keys in Failure Data Screens For Individual battery systems. For HS or AHH batteriesScrolls to the next screen see Figure Scroll KeysScrolls to the previous screen see Figure Saving Waveforms ProcedureRestoring UPS Operation Only open the front panel when performing necessaryAlso check for other 11 Restoring UPS Operation ExampleFailure Data screens 98-09-09 By scrolling with scroll Panel