Toshiba TOSNIC-7000S 3 H 1 0 0 Panel Key-switch, Panel Keys, Key-switch Function Name Remarks

Page 16

6 F 3 H 1 0 0 1

6.3.1Panel Key-switch

Table 6.2 shows the function of the key-switch on the graphic display panel.

Table 6.2 Key-switch Function

No.

Name

Function

Remarks

 

 

 

 

c

OPERATION

Setting this key-switch to the "OPERATION"

Normally setting the

 

LOCK

side enables operation using the buttons on

switch to the

 

 

the panel; setting it to the "OPERATION

OPERATION INHIBITED"

 

 

INHIBITED" side prevents operation. When

prevents operational

 

 

the switch is set to the "OPERATION

errors. The key can be

 

 

INHIBITED" side, buttons d - h and k in

removed when it is set to

 

 

Table 6.3 are inoperative and pressing them

the "OPERATION

 

 

has no effect upon the operation of the UPS.

INHIBITED" position; it

 

 

LCD scroll buttons i and j are effective

cannot be removed when

 

 

regardless of the position of this switch.

the switch is set to the

 

 

 

"OPERATION" position.

 

 

 

 

6.3.2 Panel Keys

Table 6.3 shows the functions of the keys on the graphic display panel.

NOTES

When operating the keys on the graphic display panel, hold down the key for at least 0.5 second.

When operating the reset key on the graphic display panel, hold down the key for at least 5 seconds.

The operation may not be performed if the key is held down for shorter periods of time.

Table 6.3 Key Functions (For HS or AHH individual battery systems)

No.

Name

Function

Remarks

 

 

 

 

d

RUN

Starts up the UPS.

The UPS starts up when this key is

 

 

 

pressed after the required operational

 

 

 

preparations are complete.

 

 

 

 

e

STOP

Stops the UPS.

Pressing this key during operation

 

 

 

prepares the UPS to be stopped with

 

 

 

the required procedure.*

 

 

 

 

f

UPS

Changes to UPS power

Pressing this key during UPS operation

 

 

supply

when bypass power is being supplied

 

 

 

changes it to UPS power.

 

 

 

 

g

BYPASS

Changes to bypass power

Pressing this key during UPS operation

 

 

supply

when the bypass is normal changes it to

 

 

 

bypass power.

 

 

 

 

- 15 -

Image 16
Contents 3 H 1 0 0 JulyALL Rights Reserved Vent type stand-alone lead storage battery Sealed stand-alone lead storage batteryProcedure and the status of the UPS unit Synchronized modeIntroduction Safety PrecautionsExact nature of what must be done is indicated 3 H 1 0 0 Safety Precautions UseCards Do not open the rear door Accordance with customer stipulationsBe always Do not turn off Turn on Running Locations of the Warning Labels Example 300 kVADo not touch rotating section Handling Precautions 3 H 1 0 0 Handling Precautions 3 H 1 0 0 Handling Precautions Contents Appearance Example 300 kVAControls and Circuit Configuration Panel ControlsExample 300 kVA C52R D72B E52R F52M G52L H8A I6CH This may result in failureCircuit Configuration Fault UPSKey-switch Function Name Remarks 3 H 1 0 0 Panel Key-switchPanel Keys Key Functions For HS or AHH individual battery systems Name Function RemarksPanels Graphic Display Panel2 Graphic Display Panel Control This LED lights up when the UPS is operating This LED lights up when the AC input circuit breakerThis LED is unlit when the converter has stopped Operating. It blinks when the converter is starting upLCD Display Scroll up Scroll down3 H 1 0 0 Normal Display Screen Normal Display Screen LCD Screen Description200V 50 %Normal Display Screen 60.0HzBYP I/P-V 401V3 H 1 0 0 Failure Display Screen Failure Display Screen LCD Screen Description52R Trip 98-09-093 H 1 0 0 LCD Screen Switching Operation Types of Operation Pre-operational checkOperation General Description/Objective Startup Starts up and operates the stopped UPSProcedures StartupWhen the message Appears, turn on Bypass Press ‘RUN’ SwitchMain circuit AC input Circuit breaker 52R Bypass Move #52R to ‘ON’ PositionOn page 14 for at least Second Wait several seconds For the startup processTo finish Main circuit DC input→ The will start Power supply Changing process UPS power supplyHold down the UPS Key g in the Figure On page14 for at3 H 1 0 0 Switch Power Supply UPS → Bypass 3 H 1 0 0 3 H 1 0 0 Stop StopBreaker72B Restart Press ‘RUN’ Switch Shutdown Move #52R to ‘OFF’Batteries LED unlit → This complete UPS Shutdown 3 H 1 0 0 Complete Shutdown Complete ShutdownCircuit switch 6CH Using the scroll keysTurn off the precharge Wait about 20 minutes Until the DC capacitorChanging From Floating Charge to Equalized Charge Changing From Equalized Charge to Floating Charge Check to make sure That the EqualSecond → Change to floating Charge is complete Float Charge LED lit Equal Charge LED unlitChanging from Protective Charge to Floating Charge 3 H 1 0 0 Changing the Power Supply to Maintenance Bypass Changing From UPS to maintenance Bypass Power SupplyChanging From Maintenance Bypass to UPS Power Supply Same as steps 1-41 Startup 52R 72B 52C 52M 52LTypes of Errors TroubleshootingName Description LCD Failure Displays Failure Data Screen52R Trip 98-09-09 Failure Data Screen DescriptionsUp to 10 screens of warning data can be displayed Shows the nature of the warning. For details, see Section↑ indicates there is a warning screen before this screen ↓ indicates there is a warning screen after this screen3 H 1 0 0 Failure Messages Protective Detector LocationsFault Trip LCD Message Description IndicationBypass input frequency error Including operation errorBattery temperature has risen Battery fluid level has gone below prescribed levelFor Individual battery systems. For HS or AHH batteries Position of Scroll Keys in Failure Data ScreensScrolls to the previous screen see Figure Scroll KeysScrolls to the next screen see Figure Procedure Saving WaveformsOnly open the front panel when performing necessary Restoring UPS Operation11 Restoring UPS Operation Example Also check for otherFailure Data screens 98-09-09 By scrolling with scroll Panel