Toshiba TOSNIC-7000S instruction manual Saving Waveforms, Procedure

Page 51

6 F 3 H 1 0 0 1

9.3 Saving Waveforms

NOTES

When the unit has stopped due to failure, be sure to remove the memory card before resetting the LCD Failure Error screen on the panel, so you can give it to the service person.

Resetting (restarting) the UPS without removing the memory card will delete the data needed to determine the cause of the failure.

Every effort has been made to ensure safety in unit handling. However, when removing the memory card, do not touch the other sections of the unit.

Touching the other sections of the unit may result in electric shock.

When a trip error occurs, do the following:

[Procedure]

Trip error occurs; UPS stops operating

(1)Open the front door on the UPS graphic display panel (see Figure 5.1 on page 11).

(2)Remove the memory card from the back of the door.

(Verify that the memory card write LED shown in Figure 9.10 goes out.)

(3)Insert a new memory card.

(4)Close the door.

(5)Give the memory cards that you have removed to the serviceman.

f

g e

c

d

Figure 9.10 Memory Card Unit

 

Table 9.10

Functions of the Memory Card Unit

 

 

 

 

 

Name

 

Description

 

 

 

 

c

Memory card

 

Records failure data and waveforms.

 

 

 

This memory card can record the data for four events.

 

 

 

 

d

Memory card eject button

 

Pressing this button ejects the memory card.*

 

 

 

 

e

Memory card write LED

 

Lights when data is being written o the memory card.*

 

 

 

 

f

Power LED

 

Lights when power is applied to the waveform

 

 

 

recording system from the operation power supply.

 

 

 

(This LED will always be lit when the UPS is

 

 

 

operating.)

 

 

 

g

Memory card manual write switch

Used to write arbitrary data to the memory card.**

 

 

 

 

Notes:

*Do not remove the memory card when the LED e is lit.

**The switch g is used when adjusting the UPS and should only be used by a Toshiba serviceman or by maintenance personnel. This switch is not used during normal operation.

- 50 -

Image 51
Contents July 3 H 1 0 0ALL Rights Reserved Synchronized mode Vent type stand-alone lead storage batterySealed stand-alone lead storage battery Procedure and the status of the UPS unitSafety Precautions IntroductionExact nature of what must be done is indicated Use 3 H 1 0 0 Safety PrecautionsCards Accordance with customer stipulations Do not open the rear doorLocations of the Warning Labels Example 300 kVA Be always Do not turn off Turn on RunningDo not touch rotating section Handling Precautions 3 H 1 0 0 Handling Precautions 3 H 1 0 0 Handling Precautions Contents Example 300 kVA AppearanceThis may result in failure Controls and Circuit ConfigurationPanel Controls Example 300 kVA C52R D72B E52R F52M G52L H8A I6CHCircuit Configuration UPS Fault3 H 1 0 0 Panel Key-switch Key-switch Function Name RemarksPanel Keys Name Function Remarks Key Functions For HS or AHH individual battery systemsGraphic Display Panel Panels2 Graphic Display Panel Control Operating. It blinks when the converter is starting up This LED lights up when the UPS is operatingThis LED lights up when the AC input circuit breaker This LED is unlit when the converter has stoppedScroll up Scroll down LCD Display50 % 3 H 1 0 0 Normal Display ScreenNormal Display Screen LCD Screen Description 200V401V Normal Display Screen60.0Hz BYP I/P-V98-09-09 3 H 1 0 0 Failure Display ScreenFailure Display Screen LCD Screen Description 52R Trip3 H 1 0 0 LCD Screen Switching Operation Startup Starts up and operates the stopped UPS Types of OperationPre-operational check Operation General Description/ObjectiveStartup ProceduresBypass Move #52R to ‘ON’ Position When the message Appears, turn onBypass Press ‘RUN’ Switch Main circuit AC input Circuit breaker 52RMain circuit DC input On page 14 for at least SecondWait several seconds For the startup process To finishOn page14 for at → The will start Power supply Changing processUPS power supply Hold down the UPS Key g in the Figure3 H 1 0 0 Switch Power Supply UPS → Bypass 3 H 1 0 0 Stop 3 H 1 0 0 StopRestart Press ‘RUN’ Switch Shutdown Move #52R to ‘OFF’ Breaker72BBatteries LED unlit → This complete UPS Shutdown Complete Shutdown 3 H 1 0 0 Complete ShutdownWait about 20 minutes Until the DC capacitor Circuit switch 6CHUsing the scroll keys Turn off the prechargeChanging From Floating Charge to Equalized Charge Float Charge LED lit Equal Charge LED unlit Changing From Equalized Charge to Floating ChargeCheck to make sure That the Equal Second → Change to floating Charge is completeChanging from Protective Charge to Floating Charge Changing From UPS to maintenance Bypass Power Supply 3 H 1 0 0 Changing the Power Supply to Maintenance Bypass52R 72B 52C 52M 52L Changing From Maintenance Bypass to UPS Power SupplySame as steps 1-4 1 StartupTroubleshooting Types of ErrorsName Description Failure Data Screen Descriptions LCD Failure DisplaysFailure Data Screen 52R Trip 98-09-09↓ indicates there is a warning screen after this screen Up to 10 screens of warning data can be displayedShows the nature of the warning. For details, see Section ↑ indicates there is a warning screen before this screenProtective Detector Locations 3 H 1 0 0 Failure MessagesLCD Message Description Indication Fault TripBattery fluid level has gone below prescribed level Bypass input frequency errorIncluding operation error Battery temperature has risenPosition of Scroll Keys in Failure Data Screens For Individual battery systems. For HS or AHH batteriesScroll Keys Scrolls to the previous screen see FigureScrolls to the next screen see Figure Saving Waveforms ProcedureRestoring UPS Operation Only open the front panel when performing necessaryPanel 11 Restoring UPS Operation ExampleAlso check for other Failure Data screens 98-09-09 By scrolling with scroll