Toshiba TOSNIC-7000S instruction manual Fault Trip, LCD Message Description Indication

Page 47

 

 

 

 

 

6 F 3 H 1 0 0 1

 

 

 

 

Table 9.4 Fault (Trip)

 

 

 

 

 

 

 

#

Item

LCD Message

 

Description

 

 

 

 

Indication

 

 

 

 

1

52RT

52R TRIP

 

AC input circuit breaker #52R tripped.

 

 

2

72BT

72B TRIP

 

DC input circuit breaker #72B tripped.

 

 

3

71BF

DC FUSE BLW

 

DC Main circuit fuse blew.

 

 

4

86MU

MU FAULT1

 

An inverter or converted fuse blew.

 

 

5

WDCPU

WDCPU

 

An error occurred in the main control

 

 

 

 

 

 

microprocessor (CPU).

 

 

6

80PS

CONT. PS. ERR

 

The control power supply voltage fell.

 

 

7

80B1

BATT UV

 

Battery voltage is below discharged voltage.

 

 

8

5E

EPO SW ON

 

An emergency stop was specified by the external

 

 

 

 

 

 

contact input. (Option)

 

 

 

 

Table 9.5 Warning - 1 (Converter stop/Input power error)

 

 

 

 

 

 

#

Item

LCD Message

 

Description

 

 

 

 

Indication

 

 

 

 

1

27S

AC I/P UV

 

AC input voltage is low.

 

 

2

59S

AC I/P OV

 

AC input voltage is high.

 

 

3

95S

I/P FREQ. ERR

 

AC input frequency error.

 

 

 

 

Table 9.6 Warning - 2 (Stop and restart)

 

 

 

 

 

 

#

Item

LCD Message

 

Description

 

 

 

 

Indication

 

 

 

 

1

27I

AC O/P UV

 

AC output voltage is low.

 

 

2

59I

AC O/P OV

 

AC output voltage is high.

 

 

3

51L

AC O/P OL

 

Load is too high.

 

 

4

51I

AC O/P OC

 

Load overcurrent.

 

 

5

51IO

INV OC

 

Inverter overcurrent.

 

 

6

76

DC OC

 

Excessive current in DC section of main circuit.

 

 

7

45

DC OV

 

Excessive voltage in DC section of main circuit.

 

 

8

51C

AC I/P OC

 

AC input overcurrent.

 

 

9

51CO

CONV OC

 

Converter overcurrent.

 

 

 

 

 

 

 

 

 

10

30MU

MU FAULT2

 

The converter and/or inverter gate voltage fell,

 

 

 

 

 

 

or the converter and/or inverter overheated.

 

 

11

26C

OVER TEMP

 

Temperature high in cubicle.

 

 

 

 

 

 

 

 

 

12

WDDSP

CONTROL ERR

 

An error occurred in the control microprocessor

 

 

 

 

 

 

(DSP).

 

 

 

 

 

 

 

 

- 46 -

Image 47
Contents ALL Rights Reserved July3 H 1 0 0 Synchronized mode Vent type stand-alone lead storage batterySealed stand-alone lead storage battery Procedure and the status of the UPS unitExact nature of what must be done is indicated Safety PrecautionsIntroduction Use 3 H 1 0 0 Safety PrecautionsCards Accordance with customer stipulations Do not open the rear doorDo not touch rotating section Locations of the Warning Labels Example 300 kVABe always Do not turn off Turn on Running Handling Precautions 3 H 1 0 0 Handling Precautions 3 H 1 0 0 Handling Precautions Contents Example 300 kVA AppearanceThis may result in failure Controls and Circuit ConfigurationPanel Controls Example 300 kVA C52R D72B E52R F52M G52L H8A I6CHCircuit Configuration UPS FaultPanel Keys 3 H 1 0 0 Panel Key-switchKey-switch Function Name Remarks Name Function Remarks Key Functions For HS or AHH individual battery systemsGraphic Display Panel Panels2 Graphic Display Panel Control Operating. It blinks when the converter is starting up This LED lights up when the UPS is operatingThis LED lights up when the AC input circuit breaker This LED is unlit when the converter has stoppedScroll up Scroll down LCD Display50 % 3 H 1 0 0 Normal Display ScreenNormal Display Screen LCD Screen Description 200V401V Normal Display Screen60.0Hz BYP I/P-V98-09-09 3 H 1 0 0 Failure Display ScreenFailure Display Screen LCD Screen Description 52R Trip3 H 1 0 0 LCD Screen Switching Operation Startup Starts up and operates the stopped UPS Types of OperationPre-operational check Operation General Description/ObjectiveStartup ProceduresBypass Move #52R to ‘ON’ Position When the message Appears, turn onBypass Press ‘RUN’ Switch Main circuit AC input Circuit breaker 52RMain circuit DC input On page 14 for at least SecondWait several seconds For the startup process To finishOn page14 for at → The will start Power supply Changing processUPS power supply Hold down the UPS Key g in the Figure3 H 1 0 0 Switch Power Supply UPS → Bypass 3 H 1 0 0 Stop 3 H 1 0 0 StopBatteries LED unlit → This complete UPS Shutdown Restart Press ‘RUN’ Switch Shutdown Move #52R to ‘OFF’Breaker72B Complete Shutdown 3 H 1 0 0 Complete ShutdownWait about 20 minutes Until the DC capacitor Circuit switch 6CHUsing the scroll keys Turn off the prechargeChanging From Floating Charge to Equalized Charge Float Charge LED lit Equal Charge LED unlit Changing From Equalized Charge to Floating ChargeCheck to make sure That the Equal Second → Change to floating Charge is completeChanging from Protective Charge to Floating Charge Changing From UPS to maintenance Bypass Power Supply 3 H 1 0 0 Changing the Power Supply to Maintenance Bypass52R 72B 52C 52M 52L Changing From Maintenance Bypass to UPS Power SupplySame as steps 1-4 1 StartupName Description TroubleshootingTypes of Errors Failure Data Screen Descriptions LCD Failure DisplaysFailure Data Screen 52R Trip 98-09-09↓ indicates there is a warning screen after this screen Up to 10 screens of warning data can be displayedShows the nature of the warning. For details, see Section ↑ indicates there is a warning screen before this screenProtective Detector Locations 3 H 1 0 0 Failure MessagesLCD Message Description Indication Fault TripBattery fluid level has gone below prescribed level Bypass input frequency errorIncluding operation error Battery temperature has risenPosition of Scroll Keys in Failure Data Screens For Individual battery systems. For HS or AHH batteriesScrolls to the next screen see Figure Scroll KeysScrolls to the previous screen see Figure Saving Waveforms ProcedureRestoring UPS Operation Only open the front panel when performing necessaryPanel 11 Restoring UPS Operation ExampleAlso check for other Failure Data screens 98-09-09 By scrolling with scroll