5. Installation Precautions

CAUTION

1)Install the unit in a well-ventilated location; allow at least 10 cm (4 inches) on all sides for air ventilation and for maintenance.

2)Install the unit in a stable, level and upright position that is free of excessive vibration.

3)Install the unit where the ambient temperature is within the specified range.

4)Do not install the UPS in areas that are subject to high humidity.

5)Do not install the UPS in areas that allow exposure to direct sunlight.

6)Do not install the UPS in areas that allow exposure to high levels of airborne dust, metal particles, or flammable gases.

7)Do not install the UPS in areas near sources of electrical noise. Ensuring a proper earth ground will reduce the effects of electrical noise and will reduce the potential for electrical shock.

8)Do not install the UPS in areas that would allow fluids or any foreign object to get inside the UPS.

9)The UPS generates and can radiate radio-frequency energy during operation. Although RFI noise filters are installed inside of the unit, there is no guarantee that the UPS will not influence some sensitive devices that are operating near by. If such interference is experienced, the UPS should be installed farther away from the affected equipment and/or powered from a different source than that of the affected equipment.

10)The user should provide output over-current protection for hardwired UPS systems.

11)After ensuring that all power sources are turned off and isolated in accordance with established lockout/tagout procedures, connect the power source wiring of the correct voltage to the input terminals of the UPS.

12)Connect the output terminals of the UPS to the load (refer to NEC Article 300 – Wiring Methods and Article 310 – Conductors For General Wiring). Size the branch circuit conductors in accordance with NEC Table 310.16.

Conductor Routing and Grounding

1)Use separate metal conduits for routing the input power, output power, and control circuits.

2)Follow the wire size and tightening torque specifications.

3)Always ground the unit to reduce the potential for electrical shock and to help reduce electrical noise.

4)A separate ground cable should be run inside the conduit with the input power, output power, and control circuits.

WARNING

THE METAL OF CONDUIT IS NOT AN ACCEPTABLE GROUND.

11

Image 12
Contents Uninterruptible Power System UPS G8000 Series Document Number FebruaryIntroduction Uninterruptible Power Supply Manual’s Purpose and Scope Contacting Toshiba’s Customer Support CenterTable of Contents General Safety Instructions Safety Alert SymbolSpecial Symbols Maintenance Precautions Qualified Personnel onlyPage Storage Preparation Storing ConditionsStorage Maintenance DisposalInstallation Precautions Conductor Routing and GroundingUPS is to be installed in a controlled environment Do not install the UPS close to a water sourceConnect ground wire to the earth ground terminal only MandatoryOperating Precautions Important Safety Instructions Safety Precautions Personal injury Do not open the front coverFaults by removing these panels Do not remove the rear/side panelsOperators should be certified* personnel Labeling Requirements UPS exterior showing warning label locationsUPS exterior/interior showing warning labels Battery Grounding Electrode Terminal Handling Precautions Keep the reset button pressed for 5 seconds to reset the UPS Do not operate the UPS in wet locationsOutline and Layout Do not open the front and/or rear panelShows the outline dimensions of the 300kVA UPS UPS Connections Recommended Cable Size and Tightening Torque for 150kVA UPSRecommended Cable Size and Tightening Torque for 225kVA UPS Cable knockout plates at the bottom 150 and 225kVABattery Bypass Input Recommended Cable Size and Tightening Torque for 300kVA UPSRecommended Lugs Cable knockout plates at the top 300kVAOperating Switches Operating SwitchesUPS Circuit Configuration Control FunctionsKey-Switch and Buttons Key-switchKey-switch function Name Function Remarks Operating Buttons Button functionsName Function Remarks External Connections External ConnectionsGraphics Interface LED IndicationLCD/LED Legend Name FunctionLCD Indication Scroll up Scroll downAC-VO AC- I OSync VoltDischarging 15MIN DC-VBatt No Fault No Warning No Alarm No WarningFuse Blown Another ItemUPS 35H Battery 56MIN Operation Operation TypesOperators should be qualified/trained personnel Operate the UPS in the specified conditionProcedures Pre-operational checkLED legend Off Flash System InitializeStartup Procedures Cont’d Press the RUN button For 0.5 secPress ‘UPS’ Switch Stopping procedure StopMove #72B to ‘OFF’ Position Press ‘RUN’ Switch Complete Shutdown Step Procedure LCD/LED StatusComplete Shutdown BATT-V BattFloat Charge LED Float Charge LED is On Equal Charge LED is Off Goes away Press FLOAT/EQAUL Button for 0.5 secFloat Charge is On Equal CAHRGE* LED is Off Troubleshooting Types of ErrorsLCD Fault Displays Fault Data ScreenNumber of the message in the detection order 1 Fault Messages UPSLCD Message Description Indication When the UPS has stopped due to a fault, be sure to remove LCD Scroll with faults or warningsData needed to determine the cause of the fault UPSScroll Buttons Changing screens with scroll buttonsContact Toshiba in the event of malfunction or fault Restoring UPS OperationDo not attempt to modify or relocate the UPS Do not open the front and/or rear panelsUPS Specifications General SpecificationMechanical Specification Electrical Specification Rated Capacity 150kVA 120kW 225kVA 180kW 300kVA 240kWAppendix Word Definitions