Terminal Bus 300kVA
1 |
| 2 |
| 3 |
| 4 |
| 5 |
| 6 |
| 7 |
| 8 |
| 9 |
|
| 10 |
| 11 |
| 12 |
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
U V W - + | U V W | N | U V W |
AC INPUT | BATTERY | BYPASS INPUT | AC OUTPUT |
|
|
The terminal buses shown are located at the top inside of the 300kVA UPS. Dashed line in each terminal stands for side view of screw holes to tighten lugs.
External cable size is recommended in the Table 3. This table shows only the torque to tighten a terminal bus and a corresponding lug. Torque to tighten the cable end in a compression lug shall be specified by the lug vendor recommended in Table 4.
Table 3 - Recommended Cable Size and Tightening Torque for 300kVA UPS.
The tightening torque must be greater than 90 percent of the recommended torque.
Cable Size and Tightening Torque at 300kVA UPS Terminals
Bus Number |
| Cable Size | Torque to tighten |
| (Only copper wires allowed) | the terminal bus | |
|
| ||
|
|
|
|
1 |
| Two 4/0 AWG or larger | |
|
|
|
|
2 |
| Two 4/0 AWG or larger | |
|
|
|
|
3 |
| Two 4/0 AWG or larger | |
|
|
|
|
*4 |
| Three 350 MCM or larger | |
|
|
|
|
*5 |
| Three 350 MCM or larger | |
|
|
|
|
6 |
| Two 4/0 AWG or larger | |
|
|
|
|
7 |
| Two 4/0 AWG or larger | |
|
|
|
|
8 |
| Two 4/0 AWG or larger | |
|
|
|
|
9 |
| Two 4/0 AWG or larger | |
|
|
|
|
10 |
| Two 4/0 AWG or larger | |
|
|
|
|
11 |
| Two 4/0 AWG or larger | |
|
|
|
|
12 |
| Two 4/0 AWG or larger | |
|
|
|
|
| NOTE: Maximum cable size is 350MCM. | ||
| *Two battery strings (consult factory if using one battery string). |