Toshiba G8000 Series operation manual Battery Bypass Input

Page 29

Terminal Bus 300kVA

1

 

2

 

3

 

4

 

5

 

6

 

7

 

8

 

9

 

 

10

 

11

 

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U V W - +

U V W

N

U V W

AC INPUT

BATTERY

BYPASS INPUT

AC OUTPUT

3-phase 3-wire

 

3-phase 4-wire

3-phase 4-wire

The terminal buses shown are located at the top inside of the 300kVA UPS. Dashed line in each terminal stands for side view of screw holes to tighten lugs.

External cable size is recommended in the Table 3. This table shows only the torque to tighten a terminal bus and a corresponding lug. Torque to tighten the cable end in a compression lug shall be specified by the lug vendor recommended in Table 4.

Table 3 - Recommended Cable Size and Tightening Torque for 300kVA UPS.

The tightening torque must be greater than 90 percent of the recommended torque.

Cable Size and Tightening Torque at 300kVA UPS Terminals

Bus Number

 

Cable Size

Torque to tighten

 

(Only copper wires allowed)

the terminal bus

 

 

 

 

 

 

1

 

Two 4/0 AWG or larger

215-386 in-lbs

 

 

 

 

2

 

Two 4/0 AWG or larger

215-386 in-lbs

 

 

 

 

3

 

Two 4/0 AWG or larger

215-386 in-lbs

 

 

 

 

*4

 

Three 350 MCM or larger

215-386 in-lbs

 

 

 

 

*5

 

Three 350 MCM or larger

215-386 in-lbs

 

 

 

 

6

 

Two 4/0 AWG or larger

215-386 in-lbs

 

 

 

 

7

 

Two 4/0 AWG or larger

215-386 in-lbs

 

 

 

 

8

 

Two 4/0 AWG or larger

215-386 in-lbs

 

 

 

 

9

 

Two 4/0 AWG or larger

215-386 in-lbs

 

 

 

 

10

 

Two 4/0 AWG or larger

215-386 in-lbs

 

 

 

 

11

 

Two 4/0 AWG or larger

215-386 in-lbs

 

 

 

 

12

 

Two 4/0 AWG or larger

215-386 in-lbs

 

 

 

 

 

NOTE: Maximum cable size is 350MCM.

 

*Two battery strings (consult factory if using one battery string).

28

Image 29
Contents Document Number February Uninterruptible Power System UPS G8000 SeriesIntroduction Uninterruptible Power Supply Contacting Toshiba’s Customer Support Center Manual’s Purpose and ScopeTable of Contents Safety Alert Symbol General Safety InstructionsSpecial Symbols Qualified Personnel only Maintenance PrecautionsPage Storing Conditions Storage PreparationDisposal Storage MaintenanceConductor Routing and Grounding Installation PrecautionsDo not install the UPS close to a water source UPS is to be installed in a controlled environmentConnect ground wire to the earth ground terminal only MandatoryOperating Precautions Important Safety Instructions Safety Precautions Do not open the front cover Personal injuryOperators should be certified* personnel Faults by removing these panelsDo not remove the rear/side panels UPS exterior showing warning label locations Labeling RequirementsUPS exterior/interior showing warning labels Battery Grounding Electrode Terminal Handling Precautions Do not operate the UPS in wet locations Keep the reset button pressed for 5 seconds to reset the UPSDo not open the front and/or rear panel Outline and Layout Shows the outline dimensions of the 300kVA UPS Recommended Cable Size and Tightening Torque for 150kVA UPS UPS ConnectionsCable knockout plates at the bottom 150 and 225kVA Recommended Cable Size and Tightening Torque for 225kVA UPSRecommended Cable Size and Tightening Torque for 300kVA UPS Battery Bypass InputCable knockout plates at the top 300kVA Recommended LugsOperating Switches Operating SwitchesControl Functions UPS Circuit ConfigurationKey-switch function Name Function Remarks Key-Switch and ButtonsKey-switch Name Function Remarks Operating ButtonsButton functions External Connections External ConnectionsLED Indication Graphics InterfaceName Function LCD/LED LegendScroll up Scroll down LCD IndicationAC- I O AC-VOSync VoltBatt Discharging 15MINDC-V No Alarm No Warning No Fault No WarningFuse Blown Another ItemUPS 35H Battery 56MIN Operation Types OperationOperators should be qualified/trained personnel Operate the UPS in the specified conditionPre-operational check ProceduresLED legend Off Flash System InitializePress the RUN button For 0.5 sec Startup Procedures Cont’dPress ‘UPS’ Switch Move #72B to ‘OFF’ Position Stopping procedureStop Complete Shutdown Step Procedure LCD/LED Status Press ‘RUN’ SwitchComplete Shutdown BATT-V BattFloat Charge LED Float Charge LED is On Equal Charge LED is Off Float Charge is On Equal CAHRGE* LED is Off Goes awayPress FLOAT/EQAUL Button for 0.5 sec Types of Errors TroubleshootingFault Data Screen LCD Fault DisplaysNumber of the message in the detection order 1 UPS Fault MessagesLCD Message Description Indication LCD Scroll with faults or warnings When the UPS has stopped due to a fault, be sure to removeData needed to determine the cause of the fault UPSChanging screens with scroll buttons Scroll ButtonsRestoring UPS Operation Contact Toshiba in the event of malfunction or faultDo not attempt to modify or relocate the UPS Do not open the front and/or rear panelsMechanical Specification UPS SpecificationsGeneral Specification Rated Capacity 150kVA 120kW 225kVA 180kW 300kVA 240kW Electrical SpecificationWord Definitions Appendix
Related manuals
Manual 41 pages 8 Kb