14.2 Pre-operational check
Be sure to check the following items before operating the UPS:
(1)Make sure all covers/panels are in place and secured.
(2)Make sure the temperature control in the UPS/Battery room is within specified limits.
(3)Before starting the UPS, check the power source for the UPS to make sure AC input power is on.
(4)Make sure battery breaker’s auxiliary
14.3Procedures
14.3.1Startup
Table 13 shows the procedure to start up the UPS.
LED legend | : Off |
| : On |
| : Flash | |
|
| |||||
|
|
| Table 13 - Startup Procedures. | |||
|
|
|
|
|
| |
Step | Procedure |
|
|
| LCD/LED Status |
1Turn on the control power supply switch
| (8A). | SYSTEM INITIALIZE |
| ||
|
|
| |||
| ~ | ~ | UPS |
| |
|
|
|
| ||
| AC INPUT | CONVERTER | INVERTER |
|
|
|
| FLOAT CHARGE |
| AC | |
| BATTERIES | EQUAL CHARGE |
| SWITCH |
|
|
| DISCHARGE |
|
| AC OUTPUT |
|
|
|
|
| |
|
|
|
|
| |
| BYPASS INPUT |
|
| BYPASS |
|
|
|
|
|
| |
2 | Wait for a few seconds. |
|
|
|
|
|
| BYPASS |
|
|
|
|
| PRESS ‘RUN’ SWITCH |
| ||
| ~ | ~ | UPS |
| |
|
|
|
| ||
| AC INPUT | CONVERTER | INVERTER |
|
|
|
| FLOAT CHARGE |
| AC | |
| BATTERIES | EQUAL CHARGE |
| SWITCH |
|
|
| DISCHARGE |
|
| AC OUTPUT |
|
|
|
|
|
BYPASS
BYPASS INPUT
43