14.3.5 Changing Between Float Charge and Equalize Charge
This section shows the procedure to change the recharge mode between float charge and equalize charge.
(1) Table 17 shows the procedure to change from float charge to equalize charge.
Table 17 - Change From Float Charge to Equalize Charge.
Step | Procedure | LCD/LED Status |
|
| |
1 | Make sure that the |
|
|
|
|
| FLOAT CHARGE LED | UPS SUPPLY |
|
| |
| is On. |
| 480[V] |
|
|
|
|
|
| ||
|
| AC- I O | 50[%] |
|
|
| ~ | ~ | UPS |
| |
|
|
|
| ||
| AC INPUT | CONVERTER | INVERTER |
|
|
|
|
|
|
| |
|
| FLOAT CHARGE |
| AC | |
| BATTERIES | EQUAL CHARGE |
| SWITCH |
|
|
| DISCHARGE |
|
| AC OUTPUT |
|
|
|
|
| |
|
|
|
|
| |
| BYPASS INPUT |
|
| BYPASS |
|
|
|
|
|
| |
2 | Press FLOAT/EQUAL |
|
|
|
|
| button for 0.5 sec. | UPS SUPPLY |
|
| |
| → Change completed. |
| 480[V] |
|
|
|
| AC- I O | 50[%] |
|
|
| ~ | ~ | UPS |
| |
|
|
|
| ||
| AC INPUT | CONVERTER | INVERTER |
|
|
|
| FLOAT CHARGE |
| AC | |
| BATTERIES | EQUAL CHARGE |
| SWITCH |
|
|
| DISCHARGE |
|
| AC OUTPUT |
|
|
|
|
| |
|
|
|
|
| |
| BYPASS INPUT |
|
| BYPASS |
|
|
|
|
|
| |
| EQUAL CHARGE LED is On; FLOAT CHARGE LED is Off. |
*In equalize charge mode, the battery is charged for a programmed period at a specified voltage (depending on the battery spec) rather than the float charge, in order to prevent voltage deviations among battery cells. This should be done once every six months if possible.
The G8000 UPS has an automatic function to perform the equalize recharge after battery backup operation.