7. Important Safety Instructions

This instruction contains important

SAVE THESE INSTRUCTIONS instructions for G8000U Series 100, 150, 225 and 300kVA that should be followed during the installation, operation, and maintenance of the UPS systems. Please refer to the battery manufacturer’s instructions for details on operating and maintaining the batteries for each system.

UPS System’s input and output are NOT equipped with an over-current protection device, or an output disconnection at the AC output. Therefore, a circuit breaker should be provided by the user between the UPS output and the critical load input. The minimum device ratings should be as follows:

Model

Rated Output

Breaker Rating

Model

Rated Output

Breaker Rating

100kVA

480V/277Vac

480V-150A

225kVA

480V/277Vac

480V-350A

150kVA

480V/277Vac

480V-225A

300kVA

480V/277Vac

480V-450A

Circuit breakers should be provided by the user between AC input (or Bypass input) and power sources. The minimum device ratings should be as follows:

Model

Rated Input

Breaker Rating

Model

Rated Input

Breaker Rating

100kVA

480V/277Vac

480V-150A

225kVA

480V/277Vac

480V-350A

150kVA

480V/277Vac

480V-225A

300kVA

480V/277Vac

480V-450A

The maximum ambient temperatures in which the UPS should be operated is 40°C (104°F) or 32°C (90°F) maximum if the battery system is to be subjected to the same temperature.

The nominal battery voltage for these models is 360Vdc. The nominal battery float voltage is 405Vdc.

Only a certified service representative with battery experience should perform service on batteries. Keep unauthorized people away from batteries.

Please refer to the battery manufacturer’s instruction when battery maintenance and/or replacement are scheduled.

Misuse of this equipment could result in personal injury and/or equipment damage.

In no event will Toshiba Corporation be responsible or liable for either CAUTION indirect or consequential damage or injury that may come from the use

of this equipment.

14

Image 15
Contents Document Number February Uninterruptible Power System UPS G8000 SeriesIntroduction Uninterruptible Power Supply Contacting Toshiba’s Customer Support Center Manual’s Purpose and ScopeTable of Contents Safety Alert Symbol General Safety InstructionsSpecial Symbols Qualified Personnel only Maintenance PrecautionsPage Storing Conditions Storage PreparationDisposal Storage MaintenanceConductor Routing and Grounding Installation PrecautionsMandatory UPS is to be installed in a controlled environmentDo not install the UPS close to a water source Connect ground wire to the earth ground terminal onlyOperating Precautions Important Safety Instructions Safety Precautions Do not open the front cover Personal injuryFaults by removing these panels Do not remove the rear/side panelsOperators should be certified* personnel UPS exterior showing warning label locations Labeling RequirementsUPS exterior/interior showing warning labels Battery Grounding Electrode Terminal Handling Precautions Do not operate the UPS in wet locations Keep the reset button pressed for 5 seconds to reset the UPSDo not open the front and/or rear panel Outline and LayoutShows the outline dimensions of the 300kVA UPS Recommended Cable Size and Tightening Torque for 150kVA UPS UPS ConnectionsCable knockout plates at the bottom 150 and 225kVA Recommended Cable Size and Tightening Torque for 225kVA UPSRecommended Cable Size and Tightening Torque for 300kVA UPS Battery Bypass InputCable knockout plates at the top 300kVA Recommended LugsOperating Switches Operating SwitchesControl Functions UPS Circuit ConfigurationKey-Switch and Buttons Key-switchKey-switch function Name Function Remarks Operating Buttons Button functionsName Function Remarks External Connections External ConnectionsLED Indication Graphics InterfaceName Function LCD/LED LegendScroll up Scroll down LCD IndicationVolt AC-VOAC- I O SyncDischarging 15MIN DC-VBatt Another Item No Fault No WarningNo Alarm No Warning Fuse BlownUPS 35H Battery 56MIN Operate the UPS in the specified condition OperationOperation Types Operators should be qualified/trained personnelSystem Initialize ProceduresPre-operational check LED legend Off FlashPress the RUN button For 0.5 sec Startup Procedures Cont’dPress ‘UPS’ Switch Stopping procedure StopMove #72B to ‘OFF’ Position BATT-V Batt Press ‘RUN’ SwitchComplete Shutdown Step Procedure LCD/LED Status Complete ShutdownFloat Charge LED Float Charge LED is On Equal Charge LED is Off Goes away Press FLOAT/EQAUL Button for 0.5 secFloat Charge is On Equal CAHRGE* LED is Off Types of Errors TroubleshootingFault Data Screen LCD Fault DisplaysNumber of the message in the detection order 1 UPS Fault MessagesLCD Message Description Indication UPS When the UPS has stopped due to a fault, be sure to removeLCD Scroll with faults or warnings Data needed to determine the cause of the faultChanging screens with scroll buttons Scroll ButtonsDo not open the front and/or rear panels Contact Toshiba in the event of malfunction or faultRestoring UPS Operation Do not attempt to modify or relocate the UPSUPS Specifications General SpecificationMechanical Specification Rated Capacity 150kVA 120kW 225kVA 180kW 300kVA 240kW Electrical SpecificationWord Definitions Appendix