Toshiba G8000 Series operation manual Startup Procedures Cont’d, Press the RUN button For 0.5 sec

Page 45

Table 13 - Startup Procedures (Cont’d).

3

Press the "RUN" button

 

 

 

 

 

for 0.5 sec.

BYPASS

 

 

 

 

 

UPS STARTING

 

 

 

 

WAIT FOR A WHILE

 

 

￿

~

~

UPS

 

 

 

 

 

 

AC INPUT

CONVERTER

INVERTER

 

 

 

 

FLOAT CHARGE

 

AC

￿

 

BATTERIES

EQUAL CHARGE

 

SWITCH

 

 

 

DISCHARGE

 

 

AC OUTPUT

 

 

 

 

 

 

￿

 

 

 

 

 

BYPASS INPUT

 

 

BYPASS

 

 

 

 

 

 

 

CONVERTER LED is on and INVERTER LED flashes.

4

Turn on the DC input

 

 

 

 

 

breaker.

BYPASS

 

 

 

 

 

MOVE #72B TO ‘ON’ POSITION

 

 

￿

~

~

UPS

 

 

 

 

 

 

AC INPUT

CONVERTER

INVERTER

 

 

 

 

FLOAT CHARGE

 

AC

￿

 

BATTERIES

EQUAL CHARGE

 

SWITCH

 

 

 

DISCHARGE

 

 

AC OUTPUT

 

 

 

 

 

 

￿

 

 

 

 

 

BYPASS INPUT

 

 

BYPASS

 

 

 

 

 

 

 

BATTERIES LED is on.

 

 

5

Press the “UPS” button

 

 

 

 

 

for 0.5 sec.*

UPS SUPPLY

 

 

 

 

AC-VO

480[V]

 

 

 

This completes UPS

AC- I O

50[%]

 

 

 

 

 

 

 

 

startup procedure.

 

 

 

 

 

￿

~

~

UPS

 

 

 

 

 

 

AC INPUT

CONVERTER

INVERTER

 

 

 

 

FLOAT CHARGE

 

AC

￿

 

BATTERIES

EQUAL CHARGE

 

SWITCH

 

 

 

DISCHARGE

 

 

AC OUTPUT

 

 

 

 

 

 

￿

 

 

 

 

 

BYPASS INPUT

 

 

BYPASS

 

 

 

 

 

 

 

 

BYPASS LED is off and UPS LED is on.

 

* Notes:

-If the AC switch dose not function, contact Toshiba or authorized representatives.

-If the bypass power source is out of specification, this operation will be inhibited. In order to switch manually, press the “UPS” button for 5 seconds or more.

44

Image 45
Contents Document Number February Uninterruptible Power System UPS G8000 SeriesIntroduction Uninterruptible Power Supply Contacting Toshiba’s Customer Support Center Manual’s Purpose and ScopeTable of Contents Safety Alert Symbol General Safety InstructionsSpecial Symbols Qualified Personnel only Maintenance PrecautionsPage Storing Conditions Storage PreparationDisposal Storage MaintenanceConductor Routing and Grounding Installation PrecautionsDo not install the UPS close to a water source UPS is to be installed in a controlled environmentConnect ground wire to the earth ground terminal only MandatoryOperating Precautions Important Safety Instructions Safety Precautions Do not open the front cover Personal injuryFaults by removing these panels Do not remove the rear/side panelsOperators should be certified* personnel UPS exterior showing warning label locations Labeling RequirementsUPS exterior/interior showing warning labels Battery Grounding Electrode Terminal Handling Precautions Do not operate the UPS in wet locations Keep the reset button pressed for 5 seconds to reset the UPSDo not open the front and/or rear panel Outline and LayoutShows the outline dimensions of the 300kVA UPS Recommended Cable Size and Tightening Torque for 150kVA UPS UPS ConnectionsCable knockout plates at the bottom 150 and 225kVA Recommended Cable Size and Tightening Torque for 225kVA UPSRecommended Cable Size and Tightening Torque for 300kVA UPS Battery Bypass InputCable knockout plates at the top 300kVA Recommended LugsOperating Switches Operating SwitchesControl Functions UPS Circuit ConfigurationKey-Switch and Buttons Key-switchKey-switch function Name Function Remarks Operating Buttons Button functionsName Function Remarks External Connections External ConnectionsLED Indication Graphics InterfaceName Function LCD/LED LegendScroll up Scroll down LCD IndicationAC- I O AC-VOSync VoltDischarging 15MIN DC-VBatt No Alarm No Warning No Fault No WarningFuse Blown Another ItemUPS 35H Battery 56MIN Operation Types OperationOperators should be qualified/trained personnel Operate the UPS in the specified conditionPre-operational check ProceduresLED legend Off Flash System InitializePress the RUN button For 0.5 sec Startup Procedures Cont’dPress ‘UPS’ Switch Stopping procedure StopMove #72B to ‘OFF’ Position Complete Shutdown Step Procedure LCD/LED Status Press ‘RUN’ SwitchComplete Shutdown BATT-V BattFloat Charge LED Float Charge LED is On Equal Charge LED is Off Goes away Press FLOAT/EQAUL Button for 0.5 secFloat Charge is On Equal CAHRGE* LED is Off Types of Errors TroubleshootingFault Data Screen LCD Fault DisplaysNumber of the message in the detection order 1 UPS Fault MessagesLCD Message Description Indication LCD Scroll with faults or warnings When the UPS has stopped due to a fault, be sure to removeData needed to determine the cause of the fault UPSChanging screens with scroll buttons Scroll ButtonsRestoring UPS Operation Contact Toshiba in the event of malfunction or faultDo not attempt to modify or relocate the UPS Do not open the front and/or rear panelsUPS Specifications General SpecificationMechanical Specification Rated Capacity 150kVA 120kW 225kVA 180kW 300kVA 240kW Electrical SpecificationWord Definitions Appendix