Toshiba G8000 Series operation manual Press ‘RUN’ Switch, Complete Shutdown, BATT-V Batt

Page 48

3

Please wait.

Procedure completed.

BYPASS

PRESS ‘RUN’ SWITCH

￿

~

~

UPS

 

 

AC INPUT

CONVERTER

INVERTER

 

 

FLOAT CHARGE

 

AC

 

 

 

BATTERIES

EQUAL CHARGE

 

SWITCH

 

DISCHARGE

 

 

￿

BYPASS

BYPASS INPUT

￿

AC OUTPUT

14.3.4 Complete Shutdown

This section shows the procedure to turn off the control power and shut down the UPS completely.

Table 16 - Complete Shutdown.

Step

Procedure

 

LCD/LED Status

 

 

 

 

 

 

1-3

Same as steps 1-3 in "Stop" section.

 

 

 

 

 

 

 

 

4

Scroll the LCD screen

 

 

 

 

 

DC INPUT

 

 

 

to see the DC INPUT

 

 

 

 

and make sure DC bus

 

DC-V

0[V]

 

 

voltage is 0V.

 

BATT-V

0[V]

 

 

 

 

BATT- I

0[A]

 

 

 

 

 

 

 

 

 

 

 

 

5

*Turn off the control

Nothing is displayed on the LCD and all LED’s are off.

 

power supply switch

 

 

 

 

 

(8A).

 

 

 

 

 

 

 

 

 

6

Turn off all breakers at

(Shutdown is completed and UPS is isolated.)

 

AC output, Bypass

 

 

 

 

 

Input and AC Output.

 

 

 

 

 

 

 

 

 

 

*This operation is different from the displayed instruction on the screen. Be sure to perform the procedure specified here.

47

Image 48
Contents Uninterruptible Power System UPS G8000 Series Document Number FebruaryIntroduction Uninterruptible Power Supply Manual’s Purpose and Scope Contacting Toshiba’s Customer Support CenterTable of Contents General Safety Instructions Safety Alert SymbolSpecial Symbols Maintenance Precautions Qualified Personnel onlyPage Storage Preparation Storing ConditionsStorage Maintenance DisposalInstallation Precautions Conductor Routing and GroundingUPS is to be installed in a controlled environment Do not install the UPS close to a water sourceConnect ground wire to the earth ground terminal only MandatoryOperating Precautions Important Safety Instructions Safety Precautions Personal injury Do not open the front coverFaults by removing these panels Do not remove the rear/side panelsOperators should be certified* personnel Labeling Requirements UPS exterior showing warning label locationsUPS exterior/interior showing warning labels Battery Grounding Electrode Terminal Handling Precautions Keep the reset button pressed for 5 seconds to reset the UPS Do not operate the UPS in wet locationsOutline and Layout Do not open the front and/or rear panelShows the outline dimensions of the 300kVA UPS UPS Connections Recommended Cable Size and Tightening Torque for 150kVA UPSRecommended Cable Size and Tightening Torque for 225kVA UPS Cable knockout plates at the bottom 150 and 225kVABattery Bypass Input Recommended Cable Size and Tightening Torque for 300kVA UPSRecommended Lugs Cable knockout plates at the top 300kVAOperating Switches Operating SwitchesUPS Circuit Configuration Control FunctionsKey-Switch and Buttons Key-switchKey-switch function Name Function Remarks Operating Buttons Button functionsName Function Remarks External Connections External ConnectionsGraphics Interface LED IndicationLCD/LED Legend Name FunctionLCD Indication Scroll up Scroll downAC-VO AC- I OSync VoltDischarging 15MIN DC-VBatt No Fault No Warning No Alarm No WarningFuse Blown Another ItemUPS 35H Battery 56MIN Operation Operation TypesOperators should be qualified/trained personnel Operate the UPS in the specified conditionProcedures Pre-operational checkLED legend Off Flash System InitializeStartup Procedures Cont’d Press the RUN button For 0.5 secPress ‘UPS’ Switch Stopping procedure StopMove #72B to ‘OFF’ Position Press ‘RUN’ Switch Complete Shutdown Step Procedure LCD/LED StatusComplete Shutdown BATT-V BattFloat Charge LED Float Charge LED is On Equal Charge LED is Off Goes away Press FLOAT/EQAUL Button for 0.5 secFloat Charge is On Equal CAHRGE* LED is Off Troubleshooting Types of ErrorsLCD Fault Displays Fault Data ScreenNumber of the message in the detection order 1 Fault Messages UPSLCD Message Description Indication When the UPS has stopped due to a fault, be sure to remove LCD Scroll with faults or warningsData needed to determine the cause of the fault UPSScroll Buttons Changing screens with scroll buttonsContact Toshiba in the event of malfunction or fault Restoring UPS OperationDo not attempt to modify or relocate the UPS Do not open the front and/or rear panelsUPS Specifications General SpecificationMechanical Specification Electrical Specification Rated Capacity 150kVA 120kW 225kVA 180kW 300kVA 240kWAppendix Word Definitions