Toshiba G8000 Series UPS Specifications, General Specification, Mechanical Specification

Page 60

16. UPS Specifications

16.1 General Specification

Terms

Specification

Remarks

 

 

 

Conforming Standard

UL1778-2001

UL, cUL, IEC

 

 

 

Ambient Temperature

0°~40° C ( 32°~104° F)

 

 

 

 

Relative Humidity

30% ~ 90%

Non-condensing

 

 

 

Altitude

< 1,000m ( < 3,280ft )

 

 

 

 

Insulation Resistance

3M￿

With 500V-Megger

 

 

 

Insulation withstanding

AC 2kV – 1min.

Main Circuit

voltage

AC 1.5kV – 1min.

External Interface

 

AC 500V – 1min.

Electronic Circuit

 

 

 

Audible Noise

68dB(150/225kVA), 72dB(300kVA)

1m (39”) away from front

 

 

 

16.2 Mechanical Specification

Rated Capacity

150kVA

225kVA

300kVA

 

 

 

 

Cabinet Protection Conformity

 

IEC298 IP20 ( * )

 

 

 

 

 

Exterior Paint

 

2.8Y7.7/0.3

 

 

 

 

 

Panel Thickness Front

 

1.6mm (1/16”)

 

~

Back / Side / Top

 

1.2mm (3/64”)

 

~

Bottom

 

3.2mm ( 1/8”)

 

 

 

 

 

Input / Output cabling entrance

Bottom

Top

 

 

 

 

Ground / Control wiring entrance

Bottom

Top

 

 

 

 

Clearance in Front

 

1,100mm (43” 7/16)

 

~ in Back and Side

 

0mm (0”)

 

~ on Top

 

400mm (15” 3/4)

 

 

 

 

 

Outline Dimension (Width)

1,400mm (55” 1/8)

1950mm (76” 3/4)

 

(Depth)

800mm (31” 1/2)

900mm (35” 7/16)

 

(Height)

2,000mm (78” 3/4)

2,000mm (78” 3/4)

 

 

 

 

 

Weight

 

1,200kg (2,640lbs)

1,500kg (3,300lbs)

2,000kg (4,400lbs)

 

 

 

 

Floor loading per footprint

1,071 kg/m2

1,339 kg/m2

1,139 kg/m2

 

 

( 219 lbs/ft2)

( 274 lbs/ft2)

( 233 lbs/ft2)

 

 

 

 

Heat Rejection

9,550 kcal/h

14,370 kcal/h

19,190 kcal/h

 

 

( 37,914 BTU/h)

( 57,049 BTU/h)

( 76,184 BTU/h)

 

 

 

 

 

(*) IP20 refers to foreign objects entrance and prevents objects of 12mm-diameter(15/32”) or larger.

59

Image 60
Contents Uninterruptible Power System UPS G8000 Series Document Number FebruaryIntroduction Uninterruptible Power Supply Manual’s Purpose and Scope Contacting Toshiba’s Customer Support CenterTable of Contents General Safety Instructions Safety Alert SymbolSpecial Symbols Maintenance Precautions Qualified Personnel onlyPage Storage Preparation Storing ConditionsStorage Maintenance DisposalInstallation Precautions Conductor Routing and GroundingUPS is to be installed in a controlled environment Do not install the UPS close to a water sourceConnect ground wire to the earth ground terminal only MandatoryOperating Precautions Important Safety Instructions Safety Precautions Personal injury Do not open the front coverFaults by removing these panels Do not remove the rear/side panelsOperators should be certified* personnel Labeling Requirements UPS exterior showing warning label locationsUPS exterior/interior showing warning labels Battery Grounding Electrode Terminal Handling Precautions Keep the reset button pressed for 5 seconds to reset the UPS Do not operate the UPS in wet locationsOutline and Layout Do not open the front and/or rear panelShows the outline dimensions of the 300kVA UPS UPS Connections Recommended Cable Size and Tightening Torque for 150kVA UPSRecommended Cable Size and Tightening Torque for 225kVA UPS Cable knockout plates at the bottom 150 and 225kVABattery Bypass Input Recommended Cable Size and Tightening Torque for 300kVA UPSRecommended Lugs Cable knockout plates at the top 300kVAOperating Switches Operating SwitchesUPS Circuit Configuration Control FunctionsKey-Switch and Buttons Key-switchKey-switch function Name Function Remarks Operating Buttons Button functionsName Function Remarks External Connections External ConnectionsGraphics Interface LED IndicationLCD/LED Legend Name FunctionLCD Indication Scroll up Scroll downAC-VO AC- I OSync VoltDischarging 15MIN DC-VBatt No Fault No Warning No Alarm No WarningFuse Blown Another ItemUPS 35H Battery 56MIN Operation Operation TypesOperators should be qualified/trained personnel Operate the UPS in the specified conditionProcedures Pre-operational checkLED legend Off Flash System InitializeStartup Procedures Cont’d Press the RUN button For 0.5 secPress ‘UPS’ Switch Stopping procedure StopMove #72B to ‘OFF’ Position Press ‘RUN’ Switch Complete Shutdown Step Procedure LCD/LED StatusComplete Shutdown BATT-V BattFloat Charge LED Float Charge LED is On Equal Charge LED is Off Goes away Press FLOAT/EQAUL Button for 0.5 secFloat Charge is On Equal CAHRGE* LED is Off Troubleshooting Types of ErrorsLCD Fault Displays Fault Data ScreenNumber of the message in the detection order 1 Fault Messages UPSLCD Message Description Indication When the UPS has stopped due to a fault, be sure to remove LCD Scroll with faults or warnings Data needed to determine the cause of the fault UPSScroll Buttons Changing screens with scroll buttonsContact Toshiba in the event of malfunction or fault Restoring UPS OperationDo not attempt to modify or relocate the UPS Do not open the front and/or rear panelsUPS Specifications General SpecificationMechanical Specification Electrical Specification Rated Capacity 150kVA 120kW 225kVA 180kW 300kVA 240kWAppendix Word Definitions
Related manuals
Manual 41 pages 8 Kb