Toshiba G8000 Series operation manual LCD Fault Displays, Fault Data Screen

Page 53

15.2 LCD Fault Displays

When a fault occurs, a screen is shown as in Figure 15. When a warning occurs, a screen is shown as in Figure 16.

BYPASS

FAULT STOP

FAULTS & WARNINGS

1 FUSE BLOWN

09-09-02 08:05:30

￿ANOTHER ITEM

Select the desired fault data with the scroll buttons. Detailed fault data will be displayed.

UPS SUPPLY

AC-VO

480[V]

AC- I O

50[%]

Figure 15 Fault Display

FAULTS & WARNINGS

1UPS OVER LOAD 09-09-02 08:05:30

￿ANOTHER ITEM

Select the desired warning data with the scroll buttons.

Detailed warning data will be displayed.

Figure 16 - Warning Display

15.2.1 Fault Data Screen

This screen appears when a trip error is detected.

Up to 10 screens of fault data can be displayed.

Figure 17 and Table 20 show a sample screen and describe the data shown in the screen.

￿

FAULTS & WARNINGS

 

 

 

 

 

 

1 FUSE BLOWN

￿

09-09-02 08:05:30

 

￿

￿ANOTHER ITEM

 

 

￿

 

 

 

 

 

 

Figure 17 - Sample Fault Data Screen.

Table 20 - Fault Data Screen Descriptions.

No.

Name

Description

 

 

 

￿

No.

The number of the message in the order that it was detected (1 - 10).

 

 

(Up to 10 screens of fault data can be displayed.)

 

 

 

￿

Fault Message

Shows the nature of the fault. For details, see the section titled "Fault

 

 

Messages."

 

 

 

￿

Time

The date and time (in 24-hour format) the fault was detected.

 

 

 

￿

Scroll indicator

Indicates whether there is a fault screen before or after this screen.

 

 

Indicates there is a previous fault screen.

 

 

Indicates there is a next fault screen.

 

 

−↓ Indicates there are previous and next fault screens.

 

 

 

52

Image 53
Contents Document Number February Uninterruptible Power System UPS G8000 SeriesIntroduction Uninterruptible Power Supply Contacting Toshiba’s Customer Support Center Manual’s Purpose and ScopeTable of Contents Safety Alert Symbol General Safety InstructionsSpecial Symbols Qualified Personnel only Maintenance PrecautionsPage Storing Conditions Storage PreparationDisposal Storage MaintenanceConductor Routing and Grounding Installation PrecautionsDo not install the UPS close to a water source UPS is to be installed in a controlled environmentConnect ground wire to the earth ground terminal only MandatoryOperating Precautions Important Safety Instructions Safety Precautions Do not open the front cover Personal injuryOperators should be certified* personnel Faults by removing these panelsDo not remove the rear/side panels UPS exterior showing warning label locations Labeling RequirementsUPS exterior/interior showing warning labels Battery Grounding Electrode Terminal Handling Precautions Do not operate the UPS in wet locations Keep the reset button pressed for 5 seconds to reset the UPSDo not open the front and/or rear panel Outline and LayoutShows the outline dimensions of the 300kVA UPS Recommended Cable Size and Tightening Torque for 150kVA UPS UPS ConnectionsCable knockout plates at the bottom 150 and 225kVA Recommended Cable Size and Tightening Torque for 225kVA UPSRecommended Cable Size and Tightening Torque for 300kVA UPS Battery Bypass InputCable knockout plates at the top 300kVA Recommended LugsOperating Switches Operating SwitchesControl Functions UPS Circuit ConfigurationKey-switch function Name Function Remarks Key-Switch and ButtonsKey-switch Name Function Remarks Operating ButtonsButton functions External Connections External ConnectionsLED Indication Graphics InterfaceName Function LCD/LED LegendScroll up Scroll down LCD IndicationAC- I O AC-VOSync VoltBatt Discharging 15MINDC-V No Alarm No Warning No Fault No WarningFuse Blown Another ItemUPS 35H Battery 56MIN Operation Types OperationOperators should be qualified/trained personnel Operate the UPS in the specified conditionPre-operational check ProceduresLED legend Off Flash System InitializePress the RUN button For 0.5 sec Startup Procedures Cont’dPress ‘UPS’ Switch Move #72B to ‘OFF’ Position Stopping procedureStop Complete Shutdown Step Procedure LCD/LED Status Press ‘RUN’ SwitchComplete Shutdown BATT-V BattFloat Charge LED Float Charge LED is On Equal Charge LED is Off Float Charge is On Equal CAHRGE* LED is Off Goes awayPress FLOAT/EQAUL Button for 0.5 sec Types of Errors TroubleshootingFault Data Screen LCD Fault DisplaysNumber of the message in the detection order 1 UPS Fault MessagesLCD Message Description Indication LCD Scroll with faults or warnings When the UPS has stopped due to a fault, be sure to removeData needed to determine the cause of the fault UPSChanging screens with scroll buttons Scroll ButtonsRestoring UPS Operation Contact Toshiba in the event of malfunction or faultDo not attempt to modify or relocate the UPS Do not open the front and/or rear panelsMechanical Specification UPS SpecificationsGeneral Specification Rated Capacity 150kVA 120kW 225kVA 180kW 300kVA 240kW Electrical SpecificationWord Definitions Appendix