Toshiba 1800 manual Over Heat 100% Flash Sound for

Page 29

1800 Series User Manual

29

Warning

Warning

Display State

LED State

 

Alarm State

Description and Resolution

 

 

 

 

 

 

 

 

Low Battery

 

 

 

 

Warning/Fault Flash

Alarm will

The batteries have less than 30%

 

 

 

 

 

Backup

Flash

sound for

power remaining. The warning will

 

 

 

 

 

 

 

1-second at

continue until either the batteries

 

 

 

 

 

 

 

5- second

become completely exhausted or

 

 

 

 

 

 

 

intervals.

AC input power is restored.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current Limit

 

 

 

 

Warning/Fault Flash

Alarm will

An output current limit warning is

(Over

 

 

 

 

80%

Flash

sound for

typically a sign of misapplication.

Current)

 

 

 

 

 

 

1/2- sec-

The load may not be appropri-

 

 

 

 

 

 

 

ond at

ate for UPS support. For further

 

 

 

 

 

 

 

1-second

explanation contact your Toshiba

 

 

 

 

 

 

 

intervals.

UPS service representative at 1-

 

 

 

 

 

 

 

 

877-867-8773 (outside the U.S. call

 

 

 

 

 

 

 

 

713-466-0277).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ambient

 

 

 

 

Warning/Fault

Flash

Alarm will

The temperature of the UPS operating

Over Heat

 

 

 

 

100%

Flash

sound for

environment is too high. Causes of

 

 

 

 

 

 

 

1-second at

this condition include allowing the room

 

 

 

 

 

 

 

15- second

temperature to exceed 104°F (40°C), a

 

 

 

 

 

 

 

blocked vent, or direct sunlight on the

 

 

 

 

 

 

 

intervals.

 

 

 

 

 

 

 

unit. The unit will transfer to bypass

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

mode until the temperature is reduced.

 

 

 

 

 

 

 

 

If temperature is not reduced after an

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

allowable time, the unit will shut down.

 

 

 

 

 

 

 

 

 

Image 29
Contents Series Page Product Use and Warranty Restrictions Qualified Personnel only Toshiba International Corporation Toshiba’s Customer Support CenterToshiba Customer Support Center Instructions Importantes Concernant LA Sécurité Appendix D Bypass Undervoltage / Overvoltage Preventive MaintenanceGeneral Safety Instructions Important Safety Instructions Instructions Importantes Concernant LA Sécurité Product Description Power BackupTheory of Operation Application and UsePower Conditioning Installation Precautions Inspection/InstallationInspection of the New UPS Equipment Unpacking InstructionsOperating Precautions Layout UPS Power Connections External DimensionsWiring the Unit Terminal Block Details Power Connections 120 V InputH2A H1A LOW COM High Power Connections 208/240 V InputDisplay Panel Layout Operating the UPSOption Starting the UPS SystemStopping the UPS Initial Mode Resultant Mode after Switch to Bypass UPS Display Status and Operating Condition UPS Display Status and Operating Condition Battery Recharge Time Battery Backup TimeFunction Control Button Battery Check FunctionRemote Contacts IBM AS/400 Communication InterfaceCTS RS-232COption Card Slot TroubleshootingOver Heat 100% Flash Sound for Voltage 20% Flash Sound for Frequency 60% Flash Sound for Faults Fault Over Heat 150% Second General Guidelines Storage of UPS EquipmentAvoid Before StoringRecharging requirements during storage DisposalParts Replacement Preventive and Scheduled Maintenance/Parts ReplacementPreventive Maintenance UG1G2L024C6TB Appendix a SpecificationsEvvironmental Physical Battery Appendix B System Overload Appendix C Parallel Operation Appendix D Bypass Undervoltage Overvoltage Appendix E 1800 Model/Wire Size Specifications Toshiba International Corporation Procedure Modifications Page Page Page Page Page Industrial Division