30
1800 Series User Manual
Warning (cont.)
Warning  | Display State  | LED State  | 
  | Alarm State  | Description and Resolution  | ||
  | 
  | 
  | 
  | 
  | 
  | 
  | |
Battery Over  | 
  | 
  | 
  | Warning/Fault Flash  | Alarm will  | This warning can be caused by  | |
Heat  | 
  | 
  | 
  | Battery  | Flash  | sound for  | the same conditions listed for  | 
  | 
  | 
  | 
  | 
  | 
  | Ambient Overheat. Another pos-  | |
  | 
  | 
  | 
  | 
  | 
  | 15- second  | sible cause would be a problem  | 
  | 
  | 
  | 
  | 
  | 
  | intervals.  | with the battery module, which  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | could prevent the unit from provid-  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | ing backup power.  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
Input Under  | 
  | 
  | 
  | Warning/Fault Flash  | Alarm will  | This warning will occur if the input  | |
Voltage | 
  | 
  | 
  | 20% | Flash | sound for | voltage drops below the minimum  | 
(see Note 1,  | 
  | 
  | 
  | 
  | 
  | allowable voltage. If the unit was  | |
page 31)  | 
  | 
  | 
  | 
  | 
  | at   | online when the warning occurred it  | 
  | 
  | 
  | 
  | 
  | 
  | intervals.  | will transfer to battery backup. If the  | 
  | 
  | 
  | 
  | 
  | 
  | unit was in bypass the output will be  | |
  | 
  | 
  | 
  | 
  | 
  | 
  | |
  | 
  | 
  | 
  | 
  | 
  | 
  | turned off. The unit will reinitialize the  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | startup sequence if input power returns  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |
  | 
  | 
  | 
  | 
  | 
  | 
  | to within specified limits.  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
Input Over  | 
  | 
  | 
  | Warning/Fault Flash  | Alarm will  | This warning will occur if the input volt-  | |
Voltage  | 
  | 
  | 
  | 40%  | Flash  | sound for  | age exceeds the maximum allowable  | 
(see Note 1,  | 
  | 
  | 
  | 
  | 
  | two   | voltage. If the unit was online when  | 
page 31)  | 
  | 
  | 
  | 
  | 
  | ond beeps  | the warning occurred it will transfer  | 
  | 
  | 
  | 
  | 
  | to battery backup. If the unit was in  | ||
  | 
  | 
  | 
  | 
  | 
  | at   | |
  | 
  | 
  | 
  | 
  | 
  | bypass the output will be turned off.  | |
  | 
  | 
  | 
  | 
  | 
  | intervals.  | The unit will return to normal operation  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | if input power returns to within speci-  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | fied limits.  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  |