Toshiba 1800 manual Voltage 20% Flash Sound for

Page 30

30

1800 Series User Manual

Warning (cont.)

Warning

Display State

LED State

 

Alarm State

Description and Resolution

 

 

 

 

 

 

 

Battery Over

 

 

 

Warning/Fault Flash

Alarm will

This warning can be caused by

Heat

 

 

 

Battery

Flash

sound for

the same conditions listed for

 

 

 

 

 

 

1-second at

Ambient Overheat. Another pos-

 

 

 

 

 

 

15- second

sible cause would be a problem

 

 

 

 

 

 

intervals.

with the battery module, which

 

 

 

 

 

 

 

could prevent the unit from provid-

 

 

 

 

 

 

 

ing backup power.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Under

 

 

 

Warning/Fault Flash

Alarm will

This warning will occur if the input

Voltage

 

 

 

20%

Flash

sound for

voltage drops below the minimum

(see Note 1,

 

 

 

 

 

1/2-second

allowable voltage. If the unit was

page 31)

 

 

 

 

 

at 10-second

online when the warning occurred it

 

 

 

 

 

 

intervals.

will transfer to battery backup. If the

 

 

 

 

 

 

unit was in bypass the output will be

 

 

 

 

 

 

 

 

 

 

 

 

 

 

turned off. The unit will reinitialize the

 

 

 

 

 

 

 

startup sequence if input power returns

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to within specified limits.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Over

 

 

 

Warning/Fault Flash

Alarm will

This warning will occur if the input volt-

Voltage

 

 

 

40%

Flash

sound for

age exceeds the maximum allowable

(see Note 1,

 

 

 

 

 

two 1/2-sec-

voltage. If the unit was online when

page 31)

 

 

 

 

 

ond beeps

the warning occurred it will transfer

 

 

 

 

 

to battery backup. If the unit was in

 

 

 

 

 

 

at 10-second

 

 

 

 

 

 

bypass the output will be turned off.

 

 

 

 

 

 

intervals.

The unit will return to normal operation

 

 

 

 

 

 

 

if input power returns to within speci-

 

 

 

 

 

 

 

fied limits.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Image 30
Contents Series Page Product Use and Warranty Restrictions Qualified Personnel only Toshiba’s Customer Support Center Toshiba Customer Support CenterToshiba International Corporation Instructions Importantes Concernant LA Sécurité Preventive Maintenance Appendix D Bypass Undervoltage / OvervoltageGeneral Safety Instructions Important Safety Instructions Instructions Importantes Concernant LA Sécurité Theory of Operation Power BackupProduct Description Application and UsePower Conditioning Inspection of the New UPS Equipment Inspection/InstallationInstallation Precautions Unpacking InstructionsOperating Precautions Layout External Dimensions Wiring the UnitUPS Power Connections Power Connections 120 V Input Terminal Block DetailsPower Connections 208/240 V Input H2A H1A LOW COM HighOperating the UPS Display Panel LayoutStarting the UPS System Stopping the UPSOption Initial Mode Resultant Mode after Switch to Bypass UPS Display Status and Operating Condition UPS Display Status and Operating Condition Battery Backup Time Battery Recharge TimeBattery Check Function Function Control ButtonCommunication Interface Remote Contacts IBM AS/400RS-232C CTSTroubleshooting Option Card SlotOver Heat 100% Flash Sound for Voltage 20% Flash Sound for Frequency 60% Flash Sound for Faults Fault Over Heat 150% Second Avoid Storage of UPS EquipmentGeneral Guidelines Before StoringDisposal Recharging requirements during storagePreventive and Scheduled Maintenance/Parts Replacement Preventive MaintenanceParts Replacement Appendix a Specifications UG1G2L024C6TBEvvironmental Physical Battery Appendix B System Overload Appendix C Parallel Operation Appendix D Bypass Undervoltage Overvoltage Appendix E 1800 Model/Wire Size Specifications Toshiba International Corporation Procedure Modifications Page Page Page Page Page Industrial Division