Recharging requirements during storage:

Recharging the batteries requires that the UPS has AC input power available. The UPS can be in either the online or bypass mode. (See “Starting the UPS System”, page 20, and “Battery Recharge Time”, page 24).

1)If stored in an ambient temperature less than 68°F (20°C), recharge the batteries every 9 months.

2)If stored in an ambient temperature of 68° to 86°F (20° to 30°C), recharge the batteries every 6 months.

3)If stored in an ambient temperature of 86° to 104°F (30° to 40°C), recharge the batteries every 3 months.

Disposal

Please contact your local environmental agency for details on disposal of electrical components and packaging in your particular area. It is illegal to dump lead-acid batteries in landfills or dispose of improperly. Please help our Earth by contacting the environmental protection agencies in your area, the battery manufacturer, or call Toshiba toll-free at 877-867-8773 for more information about recycling.

36

1800 Series User Manual

Image 36
Contents Series Page Product Use and Warranty Restrictions Qualified Personnel only Toshiba’s Customer Support Center Toshiba Customer Support CenterToshiba International Corporation Instructions Importantes Concernant LA Sécurité Preventive Maintenance Appendix D Bypass Undervoltage / OvervoltageGeneral Safety Instructions Important Safety Instructions Instructions Importantes Concernant LA Sécurité Power Backup Product DescriptionTheory of Operation Application and UsePower Conditioning Inspection/Installation Installation PrecautionsInspection of the New UPS Equipment Unpacking InstructionsOperating Precautions Layout External Dimensions Wiring the UnitUPS Power Connections Power Connections 120 V Input Terminal Block DetailsPower Connections 208/240 V Input H2A H1A LOW COM HighOperating the UPS Display Panel LayoutStarting the UPS System Stopping the UPSOption Initial Mode Resultant Mode after Switch to Bypass UPS Display Status and Operating Condition UPS Display Status and Operating Condition Battery Backup Time Battery Recharge TimeBattery Check Function Function Control ButtonCommunication Interface Remote Contacts IBM AS/400RS-232C CTSTroubleshooting Option Card SlotOver Heat 100% Flash Sound for Voltage 20% Flash Sound for Frequency 60% Flash Sound for Faults Fault Over Heat 150% Second Storage of UPS Equipment General GuidelinesAvoid Before StoringDisposal Recharging requirements during storagePreventive and Scheduled Maintenance/Parts Replacement Preventive MaintenanceParts Replacement Appendix a Specifications UG1G2L024C6TBEvvironmental Physical Battery Appendix B System Overload Appendix C Parallel Operation Appendix D Bypass Undervoltage Overvoltage Appendix E 1800 Model/Wire Size Specifications Toshiba International Corporation Procedure Modifications Page Page Page Page Page Industrial Division
Related manuals
Manual 12 pages 33.79 Kb