Appendix C: Parallel Operation
The 1800 Series UPS offers a standard feature that allows the unit to operate with very low input voltage without
The point when the UPS will enter parallel mode will vary depending on the output load. The following graph illustrates the UPS’ transition from battery to line power as the line voltage increases from 40% to 100% of normal. Transition curves are shown for 75% and 100% output load.
Parallell Running: Input Power vs. Input Voltage
| 120 |
|
|
|
| 100 |
|
|
|
|
|
| AC Input |
|
(%) | 80 |
|
|
|
|
|
|
| |
Input Power | 60 |
|
|
|
40 |
|
|
| |
|
|
|
| |
| 20 |
| Battery |
|
|
|
|
| |
| 0 |
|
|
|
| 40 | 55 | 70 | 85 |
Input Voltage (%)
100% Load
75% Load
As shown in the graph, the lower the output load, the lower the input voltage can go before parallel mode is activated. However, the minimum input voltage will always remain at 60% (72 VAC for a 120 VAC system).
1800 Series User Manual | 41 |