Appendix C: Parallel Operation

The 1800 Series UPS offers a standard feature that allows the unit to operate with very low input voltage without de-rating the output power. If the input voltage drops below a certain point the unit will switch to parallel mode. Parallel mode means that the unit is using the available input voltage and supplementing with battery power. Because battery power is being used, the time the unit can operate in parallel mode is limited. However, the time will be longer than that available when the unit is operating on battery power alone.

The point when the UPS will enter parallel mode will vary depending on the output load. The following graph illustrates the UPS’ transition from battery to line power as the line voltage increases from 40% to 100% of normal. Transition curves are shown for 75% and 100% output load.

Parallell Running: Input Power vs. Input Voltage

 

120

 

 

 

 

100

 

 

 

 

 

 

AC Input

 

(%)

80

 

 

 

 

 

 

 

Input Power

60

 

 

 

40

 

 

 

 

 

 

 

 

20

 

Battery

 

 

 

 

 

 

0

 

 

 

 

40

55

70

85

Input Voltage (%)

100% Load

75% Load

As shown in the graph, the lower the output load, the lower the input voltage can go before parallel mode is activated. However, the minimum input voltage will always remain at 60% (72 VAC for a 120 VAC system).

1800 Series User Manual

41

Image 41
Contents Series Page Product Use and Warranty Restrictions Qualified Personnel only Toshiba International Corporation Toshiba’s Customer Support CenterToshiba Customer Support Center Instructions Importantes Concernant LA Sécurité Appendix D Bypass Undervoltage / Overvoltage Preventive MaintenanceGeneral Safety Instructions Important Safety Instructions Instructions Importantes Concernant LA Sécurité Product Description Power BackupTheory of Operation Application and UsePower Conditioning Installation Precautions Inspection/InstallationInspection of the New UPS Equipment Unpacking InstructionsOperating Precautions Layout UPS Power Connections External DimensionsWiring the Unit Terminal Block Details Power Connections 120 V InputH2A H1A LOW COM High Power Connections 208/240 V InputDisplay Panel Layout Operating the UPSOption Starting the UPS SystemStopping the UPS Initial Mode Resultant Mode after Switch to Bypass UPS Display Status and Operating Condition UPS Display Status and Operating Condition Battery Recharge Time Battery Backup TimeFunction Control Button Battery Check FunctionRemote Contacts IBM AS/400 Communication InterfaceCTS RS-232COption Card Slot TroubleshootingOver Heat 100% Flash Sound for Voltage 20% Flash Sound for Frequency 60% Flash Sound for Faults Fault Over Heat 150% Second General Guidelines Storage of UPS EquipmentAvoid Before StoringRecharging requirements during storage DisposalParts Replacement Preventive and Scheduled Maintenance/Parts ReplacementPreventive Maintenance UG1G2L024C6TB Appendix a SpecificationsEvvironmental Physical Battery Appendix B System Overload Appendix C Parallel Operation Appendix D Bypass Undervoltage Overvoltage Appendix E 1800 Model/Wire Size Specifications Toshiba International Corporation Procedure Modifications Page Page Page Page Page Industrial Division
Related manuals
Manual 12 pages 33.79 Kb