Toshiba 1800 manual Evvironmental Physical Battery

Page 39

Evvironmental Physical Battery

Model Number

UG1A1A015C6TB1

 

UG1A1A020C6TB1

 

UG1A1A024C6TB1

 

UG1G2L024C6TB

 

 

 

 

 

 

 

 

Battery rated voltage

 

 

48 Vdc

 

 

 

 

 

 

 

 

 

 

Estimated Battery backup

13 minutes

 

10 minutes

 

7 minutes

time (fully charged, 0.7 load

 

 

(at full load)

 

(at full load)

 

(at full load)

power factor, 77°F (25°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type

 

 

12V, flame retardant, valve regulated lead acid

Configuration

 

 

2 strings in parallel, 4 batteries per string

 

 

External Dimensions

--

 

--

 

--

 

23.3 x 9.9 x 28.3 (in.)

 

 

 

(HxWxD)

 

 

 

 

 

 

 

 

 

 

Net Weight (unpacked,

--

 

--

 

--

 

181 lbs. (82 kg)

unpalleted)

 

 

 

 

 

 

 

 

 

 

Operating temperature

 

32° to 104°F (0° to 40°C), optimal at 77°F (25°C)

Storage temperature

 

 

-4 to 104°F (-20 to 40°C)

 

 

 

 

 

 

 

 

Operating Humidity

 

 

30 to 90%, non-condensing

 

 

Altitude

 

 

Up to 3000 ft (1000m) above sea level

 

 

 

 

Acoustical noise

55 dB at max. output, measured 3.3ft (1m) from front panel

 

 

 

 

 

 

 

 

Note 1: Currently under development, unit specifications may be changed.

1800 Series User Manual

39

Image 39
Contents Series Page Product Use and Warranty Restrictions Qualified Personnel only Toshiba’s Customer Support Center Toshiba Customer Support CenterToshiba International Corporation Instructions Importantes Concernant LA Sécurité Appendix D Bypass Undervoltage / Overvoltage Preventive MaintenanceGeneral Safety Instructions Important Safety Instructions Instructions Importantes Concernant LA Sécurité Application and Use Power BackupProduct Description Theory of OperationPower Conditioning Unpacking Instructions Inspection/InstallationInstallation Precautions Inspection of the New UPS EquipmentOperating Precautions Layout External Dimensions Wiring the UnitUPS Power Connections Terminal Block Details Power Connections 120 V InputH2A H1A LOW COM High Power Connections 208/240 V InputDisplay Panel Layout Operating the UPSStarting the UPS System Stopping the UPSOption Initial Mode Resultant Mode after Switch to Bypass UPS Display Status and Operating Condition UPS Display Status and Operating Condition Battery Recharge Time Battery Backup TimeFunction Control Button Battery Check FunctionRemote Contacts IBM AS/400 Communication InterfaceCTS RS-232COption Card Slot TroubleshootingOver Heat 100% Flash Sound for Voltage 20% Flash Sound for Frequency 60% Flash Sound for Faults Fault Over Heat 150% Second Before Storing Storage of UPS EquipmentGeneral Guidelines AvoidRecharging requirements during storage DisposalPreventive and Scheduled Maintenance/Parts Replacement Preventive MaintenanceParts Replacement UG1G2L024C6TB Appendix a SpecificationsEvvironmental Physical Battery Appendix B System Overload Appendix C Parallel Operation Appendix D Bypass Undervoltage Overvoltage Appendix E 1800 Model/Wire Size Specifications Toshiba International Corporation Procedure Modifications Page Page Page Page Page Industrial Division