Toshiba 1800 manual Frequency 60% Flash Sound for

Page 31

1800 Series User Manual

31

Warnings (cont.)

Warning

Display State

LED State

 

Alarm State

Description and Resolution

 

 

 

 

 

 

 

 

Input

 

 

 

Warning/Fault

Flash

Alarm will

The input frequency is outside

Frequency

 

 

 

60%

Flash

sound for 3

specified limits. If the unit was online

Regulation

 

 

 

 

 

1/2-second

when the warning occurred it will

(see Note 1)

 

 

 

 

 

beeps at

transfer to battery backup. After the

 

 

 

 

 

backup the output will shutdown. If

 

 

 

 

 

 

10-second

 

 

 

 

 

 

the unit was in bypass the output will

 

 

 

 

 

 

intervals.

 

 

 

 

 

 

be turned off. The unit will return to

 

 

 

 

 

 

 

normal operation if input frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

returns to within specified limits.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

 

 

 

Warning/Fault

Flash

Alarm will

The connected load exceeds the

Overload

 

 

 

150%

Flash

sound for 1

UPS power rating. Reduce the

 

 

 

 

 

 

second at

load attached to the UPS. The unit

 

 

 

 

 

 

15-second

will automatically return to normal

 

 

 

 

 

 

when the load is reduced within the

 

 

 

 

 

 

intervals.

 

 

 

 

 

 

allowable time limit. If the load is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

not reduced, the output will be shut

 

 

 

 

 

 

 

down. (Details see Appendix B.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

= Flashing LED

= LED lit continuously

Note 1: If any of these warnings occur while the UPS is in online mode it will immediately transfer to backup mode. In this case the percentage LED’s will be used to show the battery power status. To identify the cause of the warning listen to the number of consecutive beeps. One beep indicates an input undervoltage, two beeps means input overvoltage, three beeps is a frequency problem.

Image 31
Contents Series Page Product Use and Warranty Restrictions Qualified Personnel only Toshiba Customer Support Center Toshiba’s Customer Support CenterToshiba International Corporation Instructions Importantes Concernant LA Sécurité Appendix D Bypass Undervoltage / Overvoltage Preventive MaintenanceGeneral Safety Instructions Important Safety Instructions Instructions Importantes Concernant LA Sécurité Application and Use Power BackupProduct Description Theory of OperationPower Conditioning Unpacking Instructions Inspection/InstallationInstallation Precautions Inspection of the New UPS EquipmentOperating Precautions Layout Wiring the Unit External DimensionsUPS Power Connections Terminal Block Details Power Connections 120 V InputH2A H1A LOW COM High Power Connections 208/240 V InputDisplay Panel Layout Operating the UPSStopping the UPS Starting the UPS SystemOption Initial Mode Resultant Mode after Switch to Bypass UPS Display Status and Operating Condition UPS Display Status and Operating Condition Battery Recharge Time Battery Backup TimeFunction Control Button Battery Check FunctionRemote Contacts IBM AS/400 Communication InterfaceCTS RS-232COption Card Slot TroubleshootingOver Heat 100% Flash Sound for Voltage 20% Flash Sound for Frequency 60% Flash Sound for Faults Fault Over Heat 150% Second Before Storing Storage of UPS EquipmentGeneral Guidelines AvoidRecharging requirements during storage DisposalPreventive Maintenance Preventive and Scheduled Maintenance/Parts ReplacementParts Replacement UG1G2L024C6TB Appendix a SpecificationsEvvironmental Physical Battery Appendix B System Overload Appendix C Parallel Operation Appendix D Bypass Undervoltage Overvoltage Appendix E 1800 Model/Wire Size Specifications Toshiba International Corporation Procedure Modifications Page Page Page Page Page Industrial Division