Appendix A: Specifications
Model Number | UG1A1A015C6TB 1 | UG1A1A020C6TB1 | UG1A1A024C6TB1 | UG1G2L024C6TB | ||
|
|
|
|
|
| |
Rated Capacity | 1500VA (1.05KW) | 2000VA (1.4KW) | 2400VA (1.68KW) | 2300VA (1.61KW) | ||
|
|
|
|
|
| |
|
|
|
|
| Single phase | |
| Input voltage | Single phase 120VAC, +10% to | 208/240VAC, +10% | |||
| to | |||||
Input |
|
|
|
| (125 VAC to 229VAC) | |
Input transformer |
| Isolation Transformer |
| Auto Transformer | ||
|
|
| ||||
|
|
|
|
| ||
| Input frequency |
| 50/60 Hz +/- 3 Hz 3 |
| ||
|
|
|
|
|
| |
| Input capacity 5 | 1750VA | 2250VA | 2650VA | 2600VA | |
|
|
|
|
|
| |
| Input power factor |
| Approximately unity (0.95 to 1.0) |
| ||
|
|
|
|
|
| |
| Input voltage | Single phase 120VAC, +10% to | Single phase | |||
Bypass | 208/240 VAC +/- 10% 4 | |||||
|
|
|
|
| ||
Output voltage |
| Single phase 120VAC |
| Single phase | ||
|
|
|
|
| 208/240/120 VAC | |
| Overload rating |
| 125% for 10 minutes, 150% for 5 minutes |
| ||
| Output voltage |
| Single phase 120 VAC |
| Single phase | |
|
|
| 240/208 /120 VAC | |||
|
|
|
|
| ||
|
|
|
|
|
| |
| Output transformer |
| None |
| Isolation Transformer | |
|
|
|
|
| ||
| Output voltage regulation |
| Within +/- 3%, steady state |
| ||
|
|
|
|
|
| |
| Rated output current (rms) | 12.5A | 16.6A | 20A | 9.5A | |
|
|
|
|
|
| |
Output | Maximun output current | 31.25Apk | 41.5Apk | 50Apk | 23.75Apk | |
(peak) | ||||||
| ||||||
|
|
|
|
| ||
|
|
|
|
|
| |
| Inverter overload capacity |
| 125% for 60 seconds, 150% for 30 seconds |
| ||
| Crest factor |
| 2.5 at full load |
| ||
|
|
| ||||
| Output frequency | 50/60 Hz (+/- 0.5% in free running mode, line sync range | ||||
| Output voltage waveform | |||||
|
|
|
|
|
| |
| Rated load power factor |
| 0.7 |
|
| |
|
|
|
|
|
| |
| Effeciency | 80% | 80% | 80% | 79% | |
|
|
|
|
|
|
Note 1: Currently under development, unit specifications may be changed.
Note 2: Below 79% input voltage unit may begin parallel operation; supplementing input power with battery power. The point at which parallel operation begins is load dependent (for a detailed explanation of Parallel Operation see Appendix C: Parallel Operation).
Note 3: If input frequency is below 50 Hz, the input Voltage must not exceed 103% of rated input Voltage.
Note 4: In BYPASS mode if the Input voltage is below 90% or above 110%, the UPS output will be turned off. (See Appendix D: Bypass Under Voltage/Over Voltage)
Note 5: The input capacity is computed to include peak battery charging power.
38 | 1800 Series User Manual |