Toshiba 1800 manual Appendix a Specifications, UG1G2L024C6TB

Page 38

Appendix A: Specifications

Model Number

UG1A1A015C6TB 1

UG1A1A020C6TB1

UG1A1A024C6TB1

UG1G2L024C6TB

 

 

 

 

 

 

Rated Capacity

1500VA (1.05KW)

2000VA (1.4KW)

2400VA (1.68KW)

2300VA (1.61KW)

 

 

 

 

 

 

 

 

 

 

 

Single phase

 

Input voltage

Single phase 120VAC, +10% to -40% 2 (72VAC to 132 VAC)

208/240VAC, +10%

 

to -40%1

Input

 

 

 

 

(125 VAC to 229VAC)

Input transformer

 

Isolation Transformer

 

Auto Transformer

 

 

 

 

 

 

 

 

 

Input frequency

 

50/60 Hz +/- 3 Hz 3

 

 

 

 

 

 

 

 

Input capacity 5

1750VA

2250VA

2650VA

2600VA

 

 

 

 

 

 

 

Input power factor

 

Approximately unity (0.95 to 1.0)

 

 

 

 

 

 

 

 

Input voltage

Single phase 120VAC, +10% to -10% 4

Single phase

Bypass

208/240 VAC +/- 10% 4

 

 

 

 

 

Output voltage

 

Single phase 120VAC

 

Single phase

 

 

 

 

 

208/240/120 VAC

 

Overload rating

 

125% for 10 minutes, 150% for 5 minutes

 

 

Output voltage

 

Single phase 120 VAC

 

Single phase

 

 

 

240/208 /120 VAC

 

 

 

 

 

 

 

 

 

 

 

 

Output transformer

 

None

 

Isolation Transformer

 

 

 

 

 

 

Output voltage regulation

 

Within +/- 3%, steady state

 

 

 

 

 

 

 

 

Rated output current (rms)

12.5A

16.6A

20A

9.5A

 

 

 

 

 

 

Output

Maximun output current

31.25Apk

41.5Apk

50Apk

23.75Apk

(peak)

 

 

 

 

 

 

 

 

 

 

 

 

 

Inverter overload capacity

 

125% for 60 seconds, 150% for 30 seconds

 

 

Crest factor

 

2.5 at full load

 

 

 

 

 

Output frequency

50/60 Hz (+/- 0.5% in free running mode, line sync range +/-1Hz)

 

Output voltage waveform

Computer-grade sine wave with less than 3.0% total harmonic distortion with linear load

 

 

 

 

 

 

 

Rated load power factor

 

0.7

 

 

 

 

 

 

 

 

 

Effeciency (AC-DC-AC)

80%

80%

80%

79%

 

 

 

 

 

 

Note 1: Currently under development, unit specifications may be changed.

Note 2: Below 79% input voltage unit may begin parallel operation; supplementing input power with battery power. The point at which parallel operation begins is load dependent (for a detailed explanation of Parallel Operation see Appendix C: Parallel Operation).

Note 3: If input frequency is below 50 Hz, the input Voltage must not exceed 103% of rated input Voltage.

Note 4: In BYPASS mode if the Input voltage is below 90% or above 110%, the UPS output will be turned off. (See Appendix D: Bypass Under Voltage/Over Voltage)

Note 5: The input capacity is computed to include peak battery charging power.

38

1800 Series User Manual

Image 38
Contents Series Page Product Use and Warranty Restrictions Qualified Personnel only Toshiba International Corporation Toshiba’s Customer Support CenterToshiba Customer Support Center Instructions Importantes Concernant LA Sécurité Preventive Maintenance Appendix D Bypass Undervoltage / OvervoltageGeneral Safety Instructions Important Safety Instructions Instructions Importantes Concernant LA Sécurité Theory of Operation Power BackupProduct Description Application and UsePower Conditioning Inspection of the New UPS Equipment Inspection/InstallationInstallation Precautions Unpacking InstructionsOperating Precautions Layout UPS Power Connections External DimensionsWiring the Unit Power Connections 120 V Input Terminal Block DetailsPower Connections 208/240 V Input H2A H1A LOW COM HighOperating the UPS Display Panel LayoutOption Starting the UPS SystemStopping the UPS Initial Mode Resultant Mode after Switch to Bypass UPS Display Status and Operating Condition UPS Display Status and Operating Condition Battery Backup Time Battery Recharge TimeBattery Check Function Function Control ButtonCommunication Interface Remote Contacts IBM AS/400RS-232C CTSTroubleshooting Option Card SlotOver Heat 100% Flash Sound for Voltage 20% Flash Sound for Frequency 60% Flash Sound for Faults Fault Over Heat 150% Second Avoid Storage of UPS EquipmentGeneral Guidelines Before StoringDisposal Recharging requirements during storageParts Replacement Preventive and Scheduled Maintenance/Parts ReplacementPreventive Maintenance Appendix a Specifications UG1G2L024C6TBEvvironmental Physical Battery Appendix B System Overload Appendix C Parallel Operation Appendix D Bypass Undervoltage Overvoltage Appendix E 1800 Model/Wire Size Specifications Toshiba International Corporation Procedure Modifications Page Page Page Page Page Industrial Division