Siemens DTU3005-B manual RS-485 Connector two-wire

Page 35

5 Creating Project Files—Modbus Master to Devices

Select either ASCII or RTU as your Modbus protocol, then press the Tab key to highlight the Modbus ID selection box. The Modbus ID is used to identify the address of the DTU. Type in the Modbus ID number and press Enter.

2-Wire RS422 or RS485 Communications

After you have entered the Modbus ID number, high- light the 2-Wire RS422 or RS485 Communications selection box. This box will only need to be checked if the communications with your Modbus Master device uses a 2-wire RS485 or RS422 interface (see Figure 5.2). When 2-wire communications are being used, RTS must be looped back to CTS on the DTU side of the cable. This can be done on the RS232 side by looping pins 4 and 5 or on the RS422/485 side by looping 16 to 18 and 17 to 19. See Appendix D for wir- ing diagrams for your particular PLC, and whether it uses a 2-wire connection.

To select the checkbox, click on it with the mouse or, with the 2-Wire RS422 or RS485 Communications selection highlighted, press the spacebar. An “X” will appear inside the brackets when it is selected.

Press the Tab or Right Arrow key to move to the next field without selecting this checkbox.

RTS Control (Request to Send Control)

RTS Control selection is an option provided for modems or for Modbus Master devices that require RTS to be active only while the DTU is transmitting to the PLC.

If RTS/CTS is selected, the DTU will activate RTS and wait until CTS is active before transmitting to the PLC.

If RTS Delay is selected, the DTU will activate RTS and wait for the specified delay time to pass before transmitting to the PLC. When RTS Delay is selected, the program displays an entry box for the RTS delay time. Enter the time in milliseconds.

Figure 5.2 RS-485 Connector (two-wire)

Communications Settings

Before changing any of these settings, consult your device manual for the correct settings. To move between the communications settings, press the Tab or Enter keys. To select a setting, use the Up or Down Arrow key to move to the desired setting and press the spacebar to change your selection.

Response Time-Out

The Response Time-Outtells the DTU how long to wait after transmitting a request to the PLC if no response has been received from the PLC. After this amount of time passes with no response being received, the DTU will assume that no response is coming and will retry the request. Enter the time in milliseconds.

Saving Port 1 Configuration Information

Once you have entered all the configuration informa- tion, select Save to save the configuration to the project file. Then select Ok or press the Esc key to close the configuration screen.

If you have changed the configuration and have not saved it to the project file, you will be prompted to either save or discard the changes.

Select Revert to return to the last previously saved configuration without saving any changes.

Siemens Energy & Automation, Inc.

31

Image 35
Contents DTU3005-B Qualified Personnel Table of Contents 135 Diagnostic Data FormatWarranty 134Software Overview FeaturesIntroduction Product OverviewPLC to SEAbus Application Supported PLC WinPM PLC to SEAbusModbus Master to SEAbus Modbus Master to SEAbusMulti-Drop Modbus Master to SEAbus Connection to Modbus Master using a Multidrop CableSEAbus Port Expander Siemens Energy & Automation, Inc SEAbus Port ExpanderInstalling the Software Installing the SoftwareInstalling the Software Menu Navigation Starting the SoftwareStarting a New Project Using the Project MenuMain Menu Starting the Software Starting the Software Application Description Configuring the Project FileCreating Project Files-PLC to Devices PLC Setup-Port DTU Address Communications SettingsWire RS422 or RS485 Communications PLC ProtocolResponse Time-Out Device Setup-PortSaving Port 1 Configuration Information Other Configuration InformationIntermessage Time-Out Passthrough Setup-PortSaving Port 2 Configuration Information Saving Port 3 Configuration InformationAdding a Device Device List SetupCreating Project Files-PLC to Devices Removing a Device Configuring Custom Device RegistersSaving the Device List Configuration Configuring Custom Registers for a Single DeviceCreating Project Files-PLC to Devices Configuring Default Custom Device Registers by Device Creating Project Files-PLC to Devices Device Text Setup 7SJ600 Only Description of Returned Trip Device Diagnostic Registers Global Command RegistersDevice Command Registers Saving the Project File Creating Project Files-Modbus Master to Devices Creating Project Files-Modbus Master to DevicesConfiguring the Project File Modbus Setup-Port RS-485 Connector two-wire Device Setup-Port Modbus Master Modbus/Passthrough Setup-PortPassthrough to Port 2 SEAbus With the 2-Wire RS422 or RS485 CommunicationsDevice List Setup Creating Project Files-Modbus Master to Devices Configuring Custom Device Registers Creating Project Files-Modbus Master to Devices Configuring Default Custom Device Registers Creating Project Files-Modbus Master to Devices Device Text Setup 7SJ600 Only Value Inputs 2 Global Command Registers Device Command Registers Creating Project Files-SEAbus Port Expander Creating Project Files-SEAbus Port ExpanderMenu, and the Port 1 Passthrough configuration Communications Settings Configuration Information SEAbus Device Setup-PortTransferring Project Files Transferring Project FilesDownloading Projects Personal Computer RS-232 Port