Siemens DTU3005-B manual Main Menu, Using the Project Menu, Starting a New Project

Page 13

3 Starting the Software

3.2Main Menu

The main menu is located on the top line of the screen. In addition to the menu selections, the name of the current project and the time of day is displayed on the top line. There are five main menu selections. They are

≡, or the Program Information menu. Selecting it displays the program information screen.

The Project menu enables you to create, load, save, view and print project files. It also allows you to switch to a DOS prompt or quit the pro- gram. Its operation is described below in Section 3.3 and Section 3.4.

The Edit menu enables you to configure projects and is available only when a project is open. Chapters 4, 5, and 6 describe the process of con- figuring the different project types.

The Transfer menu uploads and downloads project files to the DTU3005 unit. These proce- dures are described in Chapter 7.

The Options menu allows you to change settings on where the program finds its project files, and which COM and LPT ports to use. Its operation is described in Chapter 8.

3.3Using the Project Menu

When you first start the DTU3005 Editor software, and no project file is loaded, the following menu selections are available in the Project menu (see example screen below):

Open, allows you to open any saved project file.

New, allows you to create a new project file.

Dos Shell, allows you to switch to MS-DOS with- out closing the DTU3005 Editor software. To return to the program, type exit and then press the Enter key at the DOS prompt.

Quit, allows you to exit the DTU3005 Editor soft- ware.

3.4Starting a New Project

Projects contain the configuration information to be downloaded to the DTU3005 device. To create a new project:

1.Select the Project menu with the mouse, or use the arrow keys to highlight Project and display the Project menu:

2.Select New with the mouse, use keyboard short- cut Ctrl + F3, or use the arrow keys to highlight New and press Enter. The New Project dialog box appears.

Note: All menus and dialog box selections are accessible from the keyboard or by using the mouse. From this point the manual will only say “select this” or “highlight this.” Refer to Section 3.1 for menu navigation instructions and keyboard shortcuts.

Siemens Energy & Automation, Inc.

9

Image 13
Contents DTU3005-B Qualified Personnel Table of Contents Warranty Diagnostic Data Format134 135Introduction FeaturesProduct Overview Software OverviewPLC to SEAbus Application Supported PLC WinPM PLC to SEAbusModbus Master to SEAbus Modbus Master to SEAbusMulti-Drop Modbus Master to SEAbus Connection to Modbus Master using a Multidrop CableSEAbus Port Expander Siemens Energy & Automation, Inc SEAbus Port Expander Installing the Software Installing the SoftwareInstalling the Software Menu Navigation Starting the SoftwareMain Menu Using the Project MenuStarting a New Project Starting the Software Starting the Software Creating Project Files-PLC to Devices Configuring the Project FileApplication Description PLC Setup-Port Wire RS422 or RS485 Communications Communications SettingsPLC Protocol DTU AddressSaving Port 1 Configuration Information Device Setup-PortOther Configuration Information Response Time-OutSaving Port 2 Configuration Information Passthrough Setup-PortSaving Port 3 Configuration Information Intermessage Time-OutAdding a Device Device List SetupCreating Project Files-PLC to Devices Saving the Device List Configuration Configuring Custom Device RegistersConfiguring Custom Registers for a Single Device Removing a DeviceCreating Project Files-PLC to Devices Configuring Default Custom Device Registers by Device Creating Project Files-PLC to Devices Device Text Setup 7SJ600 Only Description of Returned Trip Device Diagnostic Registers Global Command RegistersDevice Command Registers Saving the Project File Creating Project Files-Modbus Master to Devices Creating Project Files-Modbus Master to DevicesConfiguring the Project File Modbus Setup-Port RS-485 Connector two-wire Device Setup-Port Modbus Master Modbus/Passthrough Setup-PortPassthrough to Port 2 SEAbus With the 2-Wire RS422 or RS485 CommunicationsDevice List Setup Creating Project Files-Modbus Master to Devices Configuring Custom Device Registers Creating Project Files-Modbus Master to Devices Configuring Default Custom Device Registers Creating Project Files-Modbus Master to Devices Device Text Setup 7SJ600 Only Value Inputs 2 Global Command Registers Device Command Registers Creating Project Files-SEAbus Port Expander Creating Project Files-SEAbus Port ExpanderMenu, and the Port 1 Passthrough configuration Communications Settings Configuration Information SEAbus Device Setup-PortTransferring Project Files Transferring Project FilesDownloading Projects Personal Computer RS-232 Port