SSC Series condensing pressure with 95ºF (35ºC) condenser air
Note: Due to the variables involved in remote
3-11 Checking Motor Direction
Compressor
Note:
∙Never switch contactor leads or motor leads for reversing rotation.
∙Do not use contactor or motor leads for phase matching.
∙Compressor noise from reverse rotation is noticeable. Do not run in this mode for more than ten (10) seconds. The compressor shuts off if run longer in this mode.
∙Reverse rotation can cause suction and discharge pressures to be approximately equal; amp draws will be lower than normal.
∙If you discover that compressor rotation is reversed, correct it by switching any two main power leads into the disconnect switch or distribution block on the unit.
Water Pump
A positive pressure of 20 to 30 psi (137.9 to 206.8 kPa/1.38 to 2.07 bars) on the TO PROCESS line indicates correct pump rotation.
Condenser Fan
On SSC Series remote
Changing fan rotation direction
∙Disconnect and lock out power at the fused disconnect.
∙If all fans are going backwards, reverse any two main power leads.
∙If only some of the fans are going backwards, switch any two of their respective motor leads.
SSC Series Central Chilling Stations | Page 25 of 86 |