SterlingTEK A0551797 manual Control Nipple, Control Probe, Chilled Water Manifold

Page 31

4-11 Control Nipple

All SSC Series chilling station evaporators have two control nipples. The flow switch, freezestat, and flush port are located in the control nipple. Optional pressure gages can be mounted in the control nipples to aid in achieving proper flow through the evaporator and balancing flows.

Coupling mounts for customer-installed pressure gauges are included on both control nipples. Pressure drop between evaporator entering water pressure and evaporator leaving water pressure can be converted to gallons per minute using the pressure drop charts provided.

4-12 Control Probe

Two control probes sense temperatures. One probe measures the temperature of the hot well and the other does the same for the cold well of the reservoir. These temperatures are used by the PLC controller to sequence the compressors, based on load.

4-13 Chilled Water Manifold

The chilled water manifold allows one-point connections of TO PROCESS piping. The Sch. 40 steel piping includes butterfly valves at each evaporator for flow balancing and circuit isolation; optional pressure gauges can be installed.

4-14 Condenser Water Manifold

The condenser water manifold allows one-point connection of TO TOWER (drain) and FROM TOWER (city water) piping. Sch. 40 steel include butterfly valves for each condenser. Drain points are at the bottom of the header.

SSC Series Central Chilling Stations

Page 31 of 86

Image 31
Contents SSC Series Central Chilling Stations SSC Series Central Chilling Stations Wear Safety Glasses and Work Gloves Safety ConsiderationsTable of Contents Getting Started on the SSC Series Advanced Touchscreen Startup ChecklistsCharts and Figures Necessary Documents IntroductionModels Covered Standard FeaturesAvailable Options Standard Features on Remote CondensersModel Number Nomeclature Model SSCW-xxx Typical Two-Circuit 60-100 Ton Water Cooled ChillerCooling Capacity tons @ 50F 10 C LWT 73.1 81.4 Model SSCR-xxx Typical Two-Circuit 60-100 Ton Remote Air Cooled ChillerSscr Series Remote Condenser Models Event of Shipping Damages Unpacking and InspectionIf the Shipment is Not Correct If the Shipment is Not CompleteReturns Uncrating Your New Chiller SSC Series Central Chilling Stations Installation Location Considerations 3InstallationMaking Electrical Connections SSC Series Central Chilling Stations Making Process Water Connections Piping ConsiderationsAll Models From Process Making Tank Piping ConnectionsMaking Water-Cooled Condenser Connections Water Connection Sizing ConsiderationsGalvanic Corrosion Considerations Water Treatment ConsiderationsCondenser Water Installing the Remote Air-Cooled CondenserCompressor Checking Motor DirectionSSC Series Central Chilling Stations Lead-Lag Pumps AlarmsStaging Lead-Lag CompressorsRefrigeration Circuit Chilled Water CircuitFreezestat Control Freezing Protection Curve VolumeHigh Pressure Cutout Flow SwitchLow Pressure Cutout Condenser Water Manifold Control NippleControl Probe Chilled Water ManifoldSSC Series Central Chilling Stations Water-Cooled SSC Series Startup Checklist Startup ChecklistsSSC Series Central Chilling Stations Water-Cooled SSC Series Startup Remote Air-Cooled SSC Series Startup ChecklistSSC Series Central Chilling Stations Remote Air-Cooled SSC Series Startup Shutdown Determining Flow RateSSC Series Central Chilling Stations SSC Series Central Chilling Stations Graphic Panel Devices Indicator Lights and Control Switches MMISSC Series Central Chilling Stations Touchscreen Interface Using the StandardTouchscreen Interface Introduction MMI SSC Series Standard Control Panel Using the SSC Series Standard Touchscreen InterfaceMain Menu Screen Viewing Compressor Status Viewing and Operating Chiller CompressorsCompressor Status Screen Operating the chiller compressors Chiller Configuration ScreenCompressor Lead/Lag Screen Compressor Enable ScreenCompressor Run Time Display Screen Viewing Compressor Run TimesViewing Chiller Pump Status Viewing and Operating Chiller PumpsPump Status Screen Operating Chiller Pumps Pump Enables ScreenPump Lead/Lag Screen Viewing Pump Run TimesPump Run Time Display Screen Alarm Condition Screen Viewing Active Alarms and Handling Alarm ConditionsOr Death Setting System Temperatures Viewing and Setting System TemperaturesSSC Series Central Chilling Stations Using the Advanced Using the SSC Series Advanced Touchscreen Interface Main Menu Screen Viewing and Operating Chiller Compressors Chiller Status Screen Operating the chiller compressors Viewing Compressor Run Times Viewing and Operating Chiller Pumps Viewing Chiller Pump Status Operating Chiller Pumps Hourmeters Pump Run Time screen displays Viewing Active Alarms and Handling Alarm Conditions Alarm Condition Screen Or Death System Status Screen Temperature Input Display Screen Lubrication Condenser MaintenanceRecommended Pump Tank Spare Parts Evaporator MaintenancePump Motor Seal Makeup ValvePreventive Maintenance Service SSC Series Central Chilling Stations Problem Possible Cause Solution 10TroubleshootingAllow time to cool and reset Verify proper rotation if Service Notes Index Water Treatment Service Notes Service Notes Service Notes Sterling Th Street New Berlin, WI 262 641-8610 ∙ Fax 262 Parts Department