nCompressor Motor Protector Fault (One for each compressor)
nChilled Water Circuit Low Flow (One per chilled water circuit)
nChilled Water Circuit Freezestat (One per chilled water circuit)
nChilled Water Circuit High Pressure (One per chilled water circuit)
nChilled Water Circuit Low Pressure (One per chilled water circuit)
nPump motor overload (One per system pump)
If an alarm condition occurs the follow screen is displayed:
Figure 15
Alarm Condition Screen
To acknowledge the alarm, press the alarm silence button to clear it. It will then appear in the alarm history screen. Except for High and Low Water Temperature, and Low Refrigerant Pressure, these alarms are considered fatal and maintenance must be preformed in order to allow the chiller to fully run. Should a compressor or